15. REFRIGERANT RECOVERY
[Working procedure]
1.Recovery retaining oil in existing gas pipe Approx. 1 min
Close gas stop valve (liquid stop valve: open)
and recovery refrigerant from gas stop valve port.(Fig.1)
2.Recovery retaining oil in existing liquid pipe Approx.1 min
Recovery refrigerant from liquid stop valve port.(Fig.2)
3.Recovery refrigerant in outdoor unit Approx 2-3 min
Recovery refrigerant from outdoor unit refrigerant recovery port *1• (Fig.3)
NOTE M*1 Can be omit this procedure if there has no refrigerant recovery port.
4.Recovery refrigerant in accordance with Fluorocarbons Recovery
and Destruction Law
If refrigerant recovery port "2 pressure became lower than gas stop valve
port pressure, refrigerant will recover at the simultaneous from the gas
stop valve port, open gas stop valve (Fig.3-G)) gradually to avoid from
pressure rising rapidly. (Fig.3-Q))
NOTE MM*2 Recovery refrigerant from liquid valve port and stop valve port
simultaneous if there has no refrigerant recovery port.
Retaining oil recovery amount improved
approx. 5 times from regular refrigerant
recovery method
(pipe length, height difference, pipe path etc. is difference by installation condition)
ABOUT FLARE PROCESSING
I
Fi 9. 1
n oor
:e;i
t="'=-:71
Liq.
stop valve
I ®>
Fig, 2
n oo r
i1
n·
-,
�==':::7
Liq,
stop valve
I ®>
Fig, 3
n oo r
Uni
Liq,
stop valve
• Flare connection area of existed piping will cause
processing deterioration, make sure to do newly
• Please use flare nut which attached with product
(Do not use existed flare nut)
Pressure guage
Ref, recovery
machine
Preuure guage
Ref, recovery
machine
Preuure guage
Tau
Tant
Ref, recovery
Tant
machine
re-processing.
■
Flare processing
[Unit:mm]
Piping outside
diameter
A(+O, -0.4)
"'Flare nut
�[Unit:mm]
Piping outside >--A_(+_o ,_-o_ ._4)__,
diameter
For R32
For R32
{D=
06.35
9
09.5
13
012.7
16.2
015.9
19.7
{@
0 6.35
17
0 9.5
22
012.7
26
015.9
29
(
REFRIGERANT PIPE SIZE TABLE
)
■ Refer to the installation manual for details other than those mentioned above table such as additional refrigerant charge amount.
■ Standard pipe (R32)
Pipe size (mm)
06.35
09.5
012.7
015.9
Thickness (mm)
t 0.8
t 0.8
t 1.0
t 1.0
67
Summary of Contents for RZVFQ50
Page 1: ...1...
Page 2: ...2...
Page 3: ...3...
Page 4: ...4...
Page 5: ...5...
Page 6: ...6...
Page 7: ...7...
Page 8: ...8...
Page 9: ...9...
Page 10: ...10...
Page 11: ...111...
Page 12: ...12...
Page 13: ...13...
Page 14: ...14...
Page 15: ...15...
Page 16: ...16...
Page 18: ...18 18 20 20 21 24 24 27 28 29 32 33...
Page 19: ...19...
Page 20: ...20...
Page 21: ...21...
Page 22: ...22...
Page 23: ...23...
Page 24: ...24...
Page 25: ...25...
Page 26: ...26...
Page 27: ...27...
Page 28: ...28...
Page 29: ...29...
Page 30: ...30...
Page 31: ...31...
Page 32: ...32...
Page 33: ...33...
Page 72: ...72 72 74 75 75 75 75 76 77 79 80...
Page 73: ...73...
Page 74: ...74...
Page 75: ...75...
Page 76: ...76 77 77...
Page 77: ...77...
Page 78: ...78...
Page 79: ...79 77...
Page 80: ...80 77 77 75 75...
Page 81: ...81...