13.CAUTION  {RZVFQ50,71AV16)

THIS IS NECESSARY FOR AFTER

SERVICE, SO PLEASE REQUEST 

CUSTOMER TO KEEP THIS PAPER. 

CAUTION (NEW REFRIGERANT  R32 SERIES) 

I � 

WARNING 

I� 

ELECTRIC SHOCK CAUTION

O Caution about electric shock when do service inspection. 

1. After intercept power supply, do not open outside panel for 10 minutes. 

2. Follow manufacturing label on electric box cover, please take off outdoor fan motor 

connector to confirm voltage and body static electricity discharge. 

General caution items when do service inspection 

Caution to confirm compressor and fan motor running 

Do not directly connect power input (3 Phase 50Hz) to compressor and fan motor. 

(If not connect to print board (PCB), compressor and fan motor will be burned cut.) 

Caution when recharge refigerant 

1. To prevent the mixing of impurities,  pressure resistance and contamination mix, 

please use manifold gauge especially for R32. 

2. Make sure to do Nitrogen blow if brazing when flare connection. 

Apply ether oil or ester oil at inside flare only. 

3. Do air tight test at 4.1 7MPa 

4. Do dry vacuum, make sure to charge refrigerant in liquid condition from liquid side 

service port. (Compressor will be broken if charge from gas side service port.) 

Caution when use outdoor PCB 

Make sure to touch earth terminal and earthed metal before touch pcb, 

to prevent electric shock. 

Caution when break down diagnosis from letter code in remote control 

Please refer to service guide or outdoor unit installation manual. 

Charging refrigerant 

•Charging the system with refrigerant 

(For more infonmation such as calculation method  of  additional refrigerant charge, additional 

charge method, refrigerant charge caution, refer to the Installation Manual and Technical Guide.) 

• For refrigerant charge, be sure to charge from the service port of the liquid side stop 

A\ 

valve in liquid states.(lf you charge from the service port of the gas side stop valve, 

�  it may break the compressor.) 

• Never charge other than the specified refrigerant. (It may cause fire and bursting.) 

Table 1. Chargeless piping length 

Liquid piping size 

Pipe length which is not required additional charging 

¢6.35 

x t0.8mm 

10m 

1. In case of additional refrigerant charging 

Please add refrigerant amount according to the following table. 

Pipe length which 

Additional ref. amount

is not required 

Outdoor 

Liquid piping size 

addi1ional 

chari;ing 

above 1 Omtr. 

RZVFQ50,71AV16 

¢6.35 

x t0.8mm 

10m 

20gm/mtr 

2. Total refrigerant charging (Details please see service guide) 

1. Please recover the refrigerant until becoming 0.09 Mpa (gauge 

pressure: -0.011MPa) or less by the refrigerant recovery machine 

from stop valve service port (liquid·gas side) at the same time. 

2. Exchange service parts · Modify leak point. 

3. Perform airtightness test air-purge. 

Please refer installation manual of outdoor unit or service guide. 

4. Charge refrigerant amount selected by table 2 from liquid stop 

valve service port. 

Caution  Do not turn on power during evacuation. The motor 

may be damaged due to vacuum discharge. 

Table 2  Charge refrigerant amount  (After a leak  etc  ) 

... 

Piping length, R 32  complete 

Outdoor 

Liquid piping size 

additional amount ( g) 

5~10m 

20m 

RZVFQ50AV16 

¢6.35 

x 10.8mm 

980g 

1180g 

RZVFQ71AV16 

i/,6.35 

x 10.8mm 

1040g 

1240g 

• Making a record of the added refrigerant charge amount 

Max. 

Pipe 

Length 

20mtr 

Be sure to record the piping length and added refrigerant charge amount or refrigerant recharge amount 

with an oil-based or other indelible marker so the figures will not fade over time. 

This information is necessary for after service and maintenance. 

Liauid oioina size 

i/,6.35 

mm x t0.8mm 

Refriaerant oioina lenath 

Additional refrigerant charging 

kg 

Recharge of refrigerant 

kg 

How to execute a pumping-down 

(for example,when moving or 

reinstalling an indoor or outdoor unit) 

The outdoor unit is equiped with a high pressure switch to protect the compressor. 

Caution 

I  Never short-circuit the high pressure switch during pump-down operation. 

•  It is not allowed to let the refrigerant out into the air. 

The refrigerant should be recovered completely. 

•  Although pumping-down operation allows most of the refrigerant to be recovered in a short 

period of time, some refrigerant will remain inside the indoor unit and the refrigerant piping. 

Using a refrigerant recovery machine, recover remaining refrigerant from the stop valve 

service port until the pressure falls to 0.09MPa (gauge pressure:-0.011 MPa) or less. 

•  Be sure to execute the pumping-down before refrigerant piping and wiring is taken off. 

For pumping-down operation 

1. Please follow the !Caution about electric shock when service inspection J 

which attached on Top panel (Caution: Do not take off the connector X106A) 

2. To prevent electric shock, please protect power input terminal block by insulation sheet 

refer to below figure. 

3. Turn on the power supply and carry out pumping-down operation acoording to the following procedure. 

Insulation sheet 

Outdoor Unit figure 

Protection method 

/2\ 

To prevent electric shock when inspection, protect by use 

l.Ll.  insulation sheet on  ower in  ut terminal block and  rint board  A2P 

For pumping-down operation procedure 

6

2

1. Remove the valve caps from the liquid stop valve and the gas stop valve. 

2. By Long Pressing Switch button (SW1 )on PCB for 5 sec then unit will go on 

pump down operation & LED continuous fast blinking on PCB (A2P) .

3.Close the liquid stop valve with a hexagonal wrench.

4.After 2 to 3 minutes, close the gas stop valve and Turn off the main power

supply this will automatically deactivate the Pump Down operation.

Pump down operation is allowed on below 2 conditions:-

(1 )The outdoor unit is not abnormal and not in the 3-minute standby mode. 

(2)The outdoor unit is not operating.

Hexagonal 

wrench 

� 

When installing and relocating, be sure to install the earth leakage breaker to protect 

from the electric shock disaster and fire due to leakage of electricity. For installing the 

earth leakage breaker, request to the qualified electrician. 

Summary of Contents for RZVFQ50

Page 1: ...1...

Page 2: ...2...

Page 3: ...3...

Page 4: ...4...

Page 5: ...5...

Page 6: ...6...

Page 7: ...7...

Page 8: ...8...

Page 9: ...9...

Page 10: ...10...

Page 11: ...111...

Page 12: ...12...

Page 13: ...13...

Page 14: ...14...

Page 15: ...15...

Page 16: ...16...

Page 17: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase 111 Gurgaon 122002 Haryana India Tel 91 124 4555444 Fax 91 124 4555333 17...

Page 18: ...18 18 20 20 21 24 24 27 28 29 32 33...

Page 19: ...19...

Page 20: ...20...

Page 21: ...21...

Page 22: ...22...

Page 23: ...23...

Page 24: ...24...

Page 25: ...25...

Page 26: ...26...

Page 27: ...27...

Page 28: ...28...

Page 29: ...29...

Page 30: ...30...

Page 31: ...31...

Page 32: ...32...

Page 33: ...33...

Page 34: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase 111 Gurgaon 122002 Haryana India Tel 91 124 4555444 Fax 91 124 4555333 344...

Page 35: ...cassette type Non Sensing flow model FCVFQ50AV16 FCVFQ71AV16 FCVFQ90AV16 FCVFQ100AV16 FCVFQ125AV16 FCVFQ140AV16 FCFQ90AV16 FCFQ100AV16 FCFQ125AV16 FCFQ140AV16 READ THESE INSTRUCTIONS CAREFULLY BEFORE...

Page 36: ...CAUTION Failure to observe these instructions properly may result in property damage or personal injury which may be serious depending on the circumstances i h WARNING Ask your dealer or qualified per...

Page 37: ...ence and noise Depending on the incoming signal strength a distance of 1 meter may not be sufficient to eliminate noise Remote controller wireless kit transmitting distance can be shorter than expecte...

Page 38: ...stallation starts When selecting installation site refer to the paper pattern Do not use the unit in locations with high salt content in the air such as beachfront property locations where the voltage...

Page 39: ...TAKE SPECIAL CARE DURING CONSTRUCTION AND CHECK AFTER INSTALLATION IS FINISHED 1 Items to be checked after completion of work Items to be checked If not properly done what is likely to occur Check Ar...

Page 40: ...x and moving it and do not exert pressure on to any other part piping refrigerant drain etc or plastic parts If the temperature or humidity inside the ceiling might rise above 30 C or RH 80 respective...

Page 41: ...nerated even if1 meter is kept If installing the wireless kit the distance of the signal sent from the remote controller might be shorter if there are fluorescent lights which are electrically started...

Page 42: ...a a a 0 C C C _g 0 C 8 _ _ O c cn o Q E ffi 0 C a Cl o en 0 0 t I co f5 C O i i i 71O Suspe l n bolt pitch 840 Indoor unit 860 910 Ceiling opening 950 Decoration panel f A Fig 4 Refrigerant piping Su...

Page 43: ...allation where applicable For existing ceilings Refer to the paper pattern for installation 5 for ceiling opening dimensions Create the ceiling opening required for installation implement the refriger...

Page 44: ...iling opening dimension Consult the builder or carpenter for details The center of the ceiling opening is indicated on the paper pattern for installation The center of the unit is indicated on the tri...

Page 45: ...step 1 1 in 1 For new ceilings 2 2 Adjust the height and position of the unit Refer to 4 PREPARATIONS BEFORE INSTALLATION 1 and 1 3 in 1 For new ceilings 2 3 Perform steps 1 4 1 5 in 1 For new ceiling...

Page 46: ...s are used it may cause refrigerant leakage To prevent contamination or moisture from getting into the piping take measures such as pinching or taping the pipings Do not mix substance other than the s...

Page 47: ...prevent the pipings from getting exposed Then tighten the both ends of insulating material with the clamp Wrap the sealing material Medium 1 2 9 10 around the joint insulating for fitting 6 and 7 fla...

Page 48: ...connecting outdoor unit installation manual for test pressure Refer to also the outdoor unit installation manual or technical document for refrigerant piping 4 In case of refrigerant shortage due to f...

Page 49: ...accessory 1 Level or I 1 1 Sm Hanger bracket Adjustable rw tilted I t slightly up To prevent air bubbles in the drain hose part keep it level or slightly tilted up Any bubbles in the hose might cause...

Page 50: ...hase power supply SINGLE PHASE 230V to connections No 1 and No 2 on the terminal block for wiring the units Do not connect to No 3 of the terminal block for wiring the units The drain pump will not op...

Page 51: ...ic watering can Tube should be about 100mm long Service drain outlet with rubber plug Use this outlet to drain water from the drain pan Adding water through air discharge outlet Method of adding water...

Page 52: ...earth wires or lightning rods might cause abnormally high electric potential in the earth during lighting storms For electric wiring work refer to also WIRING DIAGRAM attached to the control box lid...

Page 53: ...nsects from entering the unit from outside If any do get in they could cause short circuits in the control box Wiring through hole Transmission wire earth wire or remote controller wire Sealing pad Sm...

Page 54: ...that external forces are not applied to the terminals Attach insulation sleeve Round crimp style terminal Connect wires of the same gauge to both side GOOD Good Fig 27 Do not connect wires of the same...

Page 55: ...re copper Minimum thickness Length 2 0mm2 2 0mm2 S50m cj 1 6 cj 1 6 For wiring length of indoor and outdoor connection wiring will be changed depends on connect model quantity power size For details p...

Page 56: ...eight is for the all round outlet For the settings for four direction part of corner closed off three direction and two direction outlets see the installation manual and technical guide supplied with...

Page 57: ...ng to the amount of dust or pollution in the room Though the indoor unit is equipped with the long life filter it is necessary to periodically clean the filter I to avoid clogging of the filter Please...

Page 58: ...plain to the customer not to operate the air conditioner for the protection of the indoor unit until the interior finishing work is completed If the air conditioner is operated substances generated fr...

Page 59: ...king for the Malfunction code which can be found by following procedures 1 Press the INSPECTION TEST OPERATION button is displayed and 0 flashes 2 Press the Temp button and find the unit No which stop...

Page 60: ...e system thermo run is possible Reverse phase Reverse two phase of thel1 L2 and L3 Wrong wiring between indoor and outdoor units or malfunction of PC board mounted on indoor and the outdoor units tran...

Page 61: ...or unit Inverter system error outdoor unit Reactor thermister error outdoor Overheated heat radiating fin outdoor unit Inverter cooling defect Instantaneous overcurrent outdoor unit Possible earth fau...

Page 62: ...stop valve service port Caution Do not turn on power during evacuation The motor may be damaged due to vacuum discharge Table 2 Charge refrigerant amount After a leak etc Piping length R32 complete O...

Page 63: ...when moving or reinstalling an indoor or outdoor unit The outdoor unit is equipped with a high pressure switch to protect the compressor I Caution I Never short circuit the high pressure switch durin...

Page 64: ...d to let the refrigerant out into the air The refrigerant should be recovered completely Although pumping down operation allows most of the refrigerant to be be recovered in a short period of time som...

Page 65: ...stallation opertion service manual Aft finished push the confirm button B83 and reset the carry out the check again and confirm the abnormal need to not show error code in remote controller and 7 er c...

Page 66: ...ner is gas oil heat pump type Clean pipe if used compressor oil in existing air conditioner is other than SUNISO MS HAB Barrel freeze JOMO Ethereal oil Ester Dill Clean pipe if existing indoor and out...

Page 67: ...ultaneous if there has no refrigerant recovery port Retaining oil recovery amount improved approx 5 times from regular refrigerant recovery method pipe length height difference pipe path etc is differ...

Page 68: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase 111 Gurgaon 122002 Haryana India Tel 91 124 4555444 Fax 91 124 4555333 68...

Page 69: ...SPLIT SYSTEM Air Conditioners MODEL Ceiling mounted cassette type Non Sensing flow model FCVFQ50AV16 FCVFQ71AV16 FCVFQ90AV16 English FCVFQ100AV16 FCVFQ125AV16 FCVFQ140AV16 FCFQ90AV16 FCFQ100AV16 FCFQ...

Page 70: ...al before using the air conditioner It will tell you how to use the unit properly and help you if any trouble occurs This manual explains about the indoor unit only Use it along with the operation man...

Page 71: ...st be done by a qualified installer in accordance with relevant local and national legislation Air conditioners must be treated at a specialized treatment facility for reuse recycling and recovery By...

Page 72: ...72 72 74 75 75 75 75 76 77 79 80...

Page 73: ...73...

Page 74: ...74...

Page 75: ...75...

Page 76: ...76 77 77...

Page 77: ...77...

Page 78: ...78...

Page 79: ...79 77...

Page 80: ...80 77 77 75 75...

Page 81: ...81...

Page 82: ...DAIKIN AIRCONDITIONING IND A PVT LTD 12th Floor Building No 9 Tower A DLF Cyber City DLF Phase 111 Gurgaon 122002 Haryana India Tel 91 124 4555444 Fax 91 124 4555333 3P727715 1 82...

Reviews: