background image

English

14

9-1 Power on and check operation

• Make sure to perform the check operation after installation. (If the air 

conditioner is operated using the indoor remote controller without 
performing the check operation, the malfunction code “U3” is dis-
played in the indoor remote controller, and normal operation is dis-
abled.)

• In the check operation, the status of the outdoor unit is checked, and 

incorrect wiring is checked for.

<Cautions on check operation>

• If the air conditioner is started within about 12 minutes after the 

power of the indoor/outdoor unit is turned on, the H2P indicator lights 
and the compressor does not run. 
Confirm that the LED status is as shown in the table in (2) in  

“9-1 Power on and check operation”

 before starting the air condi-

tioner.

• The air conditioner may require about 10 minutes maximum until it 

can start the compressor after start of operation. 
This period of time is required to homogenize the refrigerant status, 
and does not indicate any failure.

• The check operation does not provide any means of checking the 

indoor unit individually.  For that purpose, perform the normal oper-
ation using the remote controller after finishing the check operation.

• The check operation is not available in any other mode such as the 

recovery mode.

• Before running a check on the unit, changing the indoor remote con-

troller settings might cause the error code “UF” to be displayed and 
prevent a proper check to be run.

9-2 Checks in normal operation

• After finishing the check operation, operate the air conditioner nor-

mally. (Heating operation is only available for RZQ-P models.)
(Heating is not available if the outside air temperature is 75 °F or 
more.  Refer to the operation manual  supplied together with the 
unit.)

• Confirm that the indoor and outdoor units are operating normally.

(If a knocking sound is heard in the liquid compression of the com-
pressor, stop the air conditioner immediately and energize the crank-
case heater for a sufficient period of time, then start the operation 
again.)

• Run the indoor unit one by one in turn, and confirm that the corre-

sponding outdoor unit is running.

• Check to see if cold (or hot) air is coming out of the indoor unit.
• Press the fan direction button and fan speed control button on the 

remote controller to see if the fan is operating normally.

<Cautions for normal operation check>

• Once stopped, the compressor will not start for about 5 minutes even 

if the

 “ON/OFF”

  button on the remote controller is pressed.

• When the system operation is stopped by the remote control, the 

outdoor unit may continue to operate for a further 3 minutes.

• If the system has not undergone the check operation by the test run 

button since it was first installed, a malfunction code “U3” is dis-
played.
In this case, perform the check operation by referring to 

“9-1 Power 

on and check operation”

.

Make sure to turn 
on the power 6 hours 
before starting operation 
for supplying the power 
to the crankcase heater.

Caution

Outdoor 

unit installed

H1P

H5P

H4P

H6P

H7P

H2P

H3P

HAP

Blinking

ON

OFF

LED display:

LED display 
(Default 
status 
before 
delivery)

Do not leave any stop 
valve closed. 
Otherwise the compressor 
will fail.

 SER

VICE MONIT

OR

MODE

IND

SLA

VE

MASTER

TEST/HWL

L.N.O

.P

.

DEMAND

• Close the front panel 

of the outdoor unit.

• Turn ON the power 

to the outdoor unit 
and indoor unit.

(1)

(2) • Open the front panel of the outdoor unit.

• Check the LED on the PC board (A1P 

and A2P) in the outdoor unit to see if the 
data transmission is performed normally.

(3)

(4) Confirm that the stop 

valves are open on both the 
liquid and gas lines.  If they 
are closed, open them.

(5)

(6) After the check operation, make sure to close the front 

panel of the outdoor unit. 

Caution

The power is 
supplied to the 
outdoor unit.  
Take due care 
during the work 
to prevent 
electric shock.

• When performing the

low-noise operation
(L.N.O.P.) or demand
(DEMAND) operation
upon request from the
customer, perform the
setting using the
pushbutton switches
(BS1 to BS5) on the
PC board (A2P) in the
outdoor unit.

• Press each

pushbutton switch
from the opening of
the insulation cover.

(Do not remove the

insulation cover.)

• The power is supplied to the outdoor 

unit.  Take due care during the work to 
prevent electric shock.

• Before using the pushbutton switches 

(BS1 to BS5) for setting, confirm that 
the microcomputer (SERVICE) monitor 
is lit.

• For the setting method, refer to the 

[Cautions on service] label attached on 
the back of the front panel of the 
outdoor unit.  (Make sure to write the 
contents of setting on the [Cautions on 
service] label.)

Press and hold the test run 
button (BS4) for 5 seconds or 
more to start the check 
operation.
For the details, refer to the 

 Check operation procedure

  

on the [Cautions on service]  
label.

•  When leaving the outdoor unit during the 

check operation for unavoidable reasons, 
ask another installation worker to watch the 
outdoor unit, or close the front panel.

•  The system operates the check operation 

for about 15 minutes (30 minutes
maximum), then stops automatically.

The system can start normal operation 

about 5 minutes after the check operation if 
the remote controller does not display any 
malfunction code.

•  During the check operation, the status 

under execution is indicated on the remote 
controller.

A2P

A1P

01_EN_3PN07193-7H.fm  Page 14  Monday, December 27, 2010  4:30 PM

Summary of Contents for RZR36PVJU

Page 1: ...t l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente estas instrucciones antes de instalar Guarde est...

Page 2: ...t in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant lea...

Page 3: ...the air or where volatile flammables such as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used...

Page 4: ...ind whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following...

Page 5: ...onduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is pres...

Page 6: ...door unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 Whe...

Page 7: ...Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 in...

Page 8: ...nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If the...

Page 9: ...efrigerant other than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table...

Page 10: ...acuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture or have leakage If there is a possibility of moisture remaining in the p...

Page 11: ...a hexagon wrench into the valve stem and turn the valve stem clockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is closed The valve is sealed in the arrow area Take c...

Page 12: ...upply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmissio...

Page 13: ...e below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU9 60Hz 208 230V 30A 27A RZQ36PVJU9 RZR36PVJU RZQ42PV...

Page 14: ...K 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas li...

Page 15: ...utdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis played...

Page 16: ...op valves in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based o...

Page 17: ...ns in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximum...

Page 18: ...1101 HT 3PN07193 7H EM10A070 00_CV_3PN07193 7H fm Page 2 Saturday December 25 2010 1 03 PM...

Reviews: