background image

11

English

CAUTION

<To electrician>

• Do not operate the air conditioner until the refrigerant piping work is 

completed.  
(Operating the air conditioner before the refrigerant piping work is 
completed may damage the compressor.)

• Install a ground fault circuit interrupter.

(The inverter is provided in the air conditioner.  In order to prevent 
malfunction of the ground fault circuit interrupter itself, use a breaker 
resistant to higher harmonics.)

• Electricians having sufficient knowledge should perform the electri-

cal wiring work.
All wiring must comply with local electrical codes and National Elec-
trical Code (NEC).

• Perform the electric wiring work in accordance with the “wiring dia-

gram label”.
Make sure to turn OFF the branch switch and overcurrent breaker 
before starting the work.

• Perform grounding to the indoor unit and outdoor unit.
• Use only copper wires.
• Make sure to turn the power off before starting the electric wiring 

work.
Do not turn ON any switch until the work is completed.

• The outdoor unit has an inverter which generates noise and charges 

the outer casing with the leakage current. The outdoor unit should be 
grounded so that the effect of the generated noise on other equip-
ment can be reduced, and that the outer casing can be discharged.

• As this unit is equipped with an inverter, installing a phase advancing 

capacitor will not only reduce the power factor improvement factor, 
but may also cause the capacitor to overheat due to high-frequency 
waves.  Therefore, never install a phase advancing capacitor.

• Never push excessive electric wires into the units.
• Protect electric wires with conduit tubes or vinyl tubes so that they 

will not be damaged by edges of knockout holes.

• Fix electric wires with clamps as accessories so that they will not 

come to contact with pipes and stop valves.  
(Refer to  

“7-3 Power supply wiring connection procedure”

.)

7-1 Connection example of whole system wiring

7-2 Routing power supply wiring and transmission 

wiring

Let the power supply wiring and transmission wiring with a conduit pass 
through one of the knockout holes on the front or side piping cover, and 
let the transmission wiring with a conduit pass through another knockout 
hole.

• For protection from uninsulated live parts, thread the power supply 

wiring and the transmission wiring through the included insulation 
tube and secure it with the included clamp.

Precautions knockout holes

• Open the knockout holes with a hammer or the like.
• After knocking out the holes, we recommend you remove burrs in the 

knockout holes and paint the edges and areas around the edges 
using the repair paint to prevent rusting.

• When passing wiring through knockout holes, make sure there are 

no burrs, and protect the wiring with protective tape.

CAUTION

• Use conduit for both the power supply wiring and transmission wiring.
• Outside the unit, make sure to keep the wirings 5 inch away. 

Otherwise, the outdoor unit may be affected by electrical noise 
(external noise), and malfunction or fail.

• Be sure to connect the power supply wiring to the terminal block and 

secure it as described in  “7-3 Power supply wiring connection procedure”.

• Fix the wiring between the units in accordance with “7-4 Transmis-

sion wiring connection procedure”.

• Secure the wirings with the clamps (accessory) so that do not touch 

the piping.

• Make sure the wirings will not be pinched by the front panel, and 

close the panel firmly.

• Route the conduit along the unit by using a elbow socket and so on 

to prevent it from being stepped on.

Power

Remote 
controller 

Indoor 

unit

Ground

Power

Ground

Outdoor unit

16V

208/230V

208/230V

16V

Ground fault 
circuit interrupter

overcurrent 
breaker (fuse)

Branch switch

Insulation tube (Large)
(accessory)

Clamp
(accessory)

Power supply 
wiring

(3in.)

(5/8in.)

2in. 
or 
more

(5/8in.)

Insulation tube (Small)
(accessory)

Clamp
(accessory)

Transmission
wiring

(3in.)

<Power supply wiring>

<Transmission wiring>

Ground wire

If small animals might enter the unit, 
block the knockout holes with an 
appropriate material (field supply).

Burr

01_EN_3PN07193-7H.fm  Page 11  Monday, December 27, 2010  4:30 PM

Summary of Contents for RZR36PVJU

Page 1: ...t l installation Conserver ce manuel port e de main pour r f rence ult rieure Ce manuel doit tre donn au propri taire de l quipement Lea cuidadosamente estas instrucciones antes de instalar Guarde est...

Page 2: ...t in water leakage elec tric shock or fire When installing the unit in a small room take measures to keep the refrigerant concentration from exceeding allowable safety limits Excessive refrigerant lea...

Page 3: ...the air or where volatile flammables such as thinner or gasoline are handled Oper ating the unit in such conditions can cause a fire Take adequate measures to prevent the outdoor unit from being used...

Page 4: ...ind whose velocity is 11 mph or more blows to the out door unit from the air outlet side the air flow rate of the outdoor unit is reduced the outlet air is sucked again short circuit and the following...

Page 5: ...onduit and servicing between the units A When an obstruction is present on the air inlet side When the upward area is open 1 When one outdoor unit is installed individually When an obstruction is pres...

Page 6: ...door unit is installed individually The dimensional relationship between H L and A is as shown in the table below NOTE Close the area under the frame so that the outlet air does not bypass there 2 Whe...

Page 7: ...Only two outdoor units can be installed side by side D When outdoor units are stacked 1 When an obstruction is present on the air outlet side NOTE 1 Only two outdoor units can be stacked 2 About 4 in...

Page 8: ...nut 3 Remove the transportation metal and the washer as shown in the above figure 4 Return and tighten the fixing nut again 5 Return the sound proof cover to achieve the former status CAUTION If the...

Page 9: ...efrigerant other than the specified refrigerant enter the refrigerant system Do not let any gas such as air enter the refrigerant system Precautions when connecting the piping See the following table...

Page 10: ...acuum pressure indi cated by the vacuum gage does not increase If the vacuum pressure increases the system may contain moisture or have leakage If there is a possibility of moisture remaining in the p...

Page 11: ...a hexagon wrench into the valve stem and turn the valve stem clockwise 2 When the valve stem cannot be turned any more stop turning Now the valve is closed The valve is sealed in the arrow area Take c...

Page 12: ...upply wiring and transmission wiring Let the power supply wiring and transmission wiring with a conduit pass through one of the knockout holes on the front or side piping cover and let the transmissio...

Page 13: ...e below for tightening torque for the terminal screws Model Phase and frequency Voltage Max Overcurrent Protective device Min Circuit Amps RZQ30PVJU9 60Hz 208 230V 30A 27A RZQ36PVJU9 RZR36PVJU RZQ42PV...

Page 14: ...K 5 Piping size and heat insulation Refer to 6 1 Selection of piping material 6 5 Heat insulation of piping 6 Check of stop valve Confirm that the stop valve is open on both the liquid line and gas li...

Page 15: ...utdoor unit may continue to operate for a further 3 minutes If the system has not undergone the check operation by the test run button since it was first installed a malfunction code U3 is dis played...

Page 16: ...op valves in the outdoor unit remain closed Open the stop valve on both the gas and liquid lines The refrigerant is overcharged Calculate again the required amount of refrigerant to be charged based o...

Page 17: ...ns in steps 1 and 2 above 4 Deal with the situations where the result exceeds the maximum con centration level Where the installation of a facility results in a concentration in excess of the maximum...

Page 18: ...1101 HT 3PN07193 7H EM10A070 00_CV_3PN07193 7H fm Page 2 Saturday December 25 2010 1 03 PM...

Reviews: