3
2
• Split - Sky Air • RZQSG-L3/9V1
19
• Outdoor Unit • RZQSG-L3/9V1
2
Specifications
Standard Accessories : Tie-wraps; Quantity : 2;
Standard Accessories : Installation manual; Quantity : 1;
Operation range
Cooling
Ambien
t
Min.
°CDB
-15.0
Max.
°CDB
46
Heating
Ambien
t
Min.
°CWB
-15
Max.
°CWB
15.5
Refrigerant
Type
R-410A
Charge
kg
2.75
2.9
4.0
TCO
2
eq
5.7
6.1
8.4
Control
Expansion valve (electronic type)
GWP
2,087.5
Circuits
Quantity
1
Piping connections
Liquid
Quantity
1
Type
Flare connection
OD
mm
9.52
Gas
Quantity
1
Type
Flare connection
OD
mm
15.9
Drain
Quantity
3
5
Type
Hole
ID
mm
-
OD
mm
26
Piping length
OU - IU Min.
m
5
Max.
m
50
System Equival
ent
m
70
Chargel
ess
m
30
Additional refrigerant charge
kg/m
See installation manual
Level difference
IU - OU Max.
m
15
30.0
IU - IU
Max.
m
0.5
Heat insulation
Both liquid and gas pipes
Refrigerant oil
Type
FVC50K
Charged volume
l
0.75
0.9
1.35
Defrost method
Pressure equalising
Reversed cycle
Defrost control
Sensor for outdoor heat exchanger temperature
Safety devices
Item
01
High pressure switch
02
Fan motor thermal
protection
Low pressure switch
03
Fuse
Fan driver overload protector
04
-
Fuse
2-10 Electrical Specifications
RZQSG71L3V1
RZQSG100L9V1
RZQSG125L9V1
RZQSG140L9V1
Power supply
Name
V1
Phase
1~
Frequency
Hz
50
Voltage
V
220-240
Voltage range
Min.
%
-10
Max.
%
10
Current - 50Hz
Maximum fuse amps (MFA)
A
20
-
Current
Zmax
List
-
Complies to EN61000-3-11
Recommended fuses
A
25
40
Current - 60Hz
Maximum fuse amps (MFA)
A
-
Wiring connections
For power supply
Remark
See installation manual outdoor unit
For connection with
indoor
Remark
See installation manual outdoor unit
Power supply intake
Outdoor unit only
2-9 Technical Specifications
RZQSG71L3V1
RZQSG100L9V1
RZQSG125L9V1
RZQSG140L9V1