Specifications
Seasonal efficiency
(according to
EN14825)
Cooling
Energy label
A
Pdesign
kW
12.00
SEER
5.20
Annual energy consumption
kWh
808
A Condition (35°C
- 27/19)
Pdc
kW
12.00
EERd
3.09
power input
kW
3.89
B Condition (30°C
- 27/19)
Pdc
kW
8.84
EERd
3.41
power input
kW
2.60
C Condition (25°C
- 27/19)
Pdc
kW
5.69
EERd
6.59
power input
kW
0.87
D Condition (20°C
- 27/19)
Pdc
kW
4.04
EERd
8.52
power input
kW
0.48
Heating (Average
climate)
Energy label
A
Pdesign
kW
7.60
SCOP/A
3.90
SCOPnet/A
3.91
Annual energy consumption
kWh
2,729
Required back up heating cap at design conditions
kW
0.58
TOL
Tol (temperature operating limit)
°C
-15
Pdh (declared heating cap)
kW
7.51
COPd (declared COP)
2.21
Power input
kW
3.40
TBivalent
Tbiv (bivalent temperature)
°C
-7
Pdh (declared heating cap)
kW
6.72
COPd (declared COP)
2.89
Power input
kW
2.33
A Condition (-7°C) Pdh (declared heating cap)
kW
6.72
COPd (declared COP)
2.89
Power input
kW
2.33
B Condition (2°C) Pdh (declared heating cap)
kW
4.85
COPd (declared COP)
3.86
Power input
kW
1.26
C Condition (7°C) Pdh (declared heating cap)
kW
3.02
COPd (declared COP)
5.12
Power input
kW
0.59
D Condition
(12°C)
Pdh (declared heating cap)
kW
3.42
COPd (declared COP)
6.00
Power input
kW
0.57
Pto (Thermostat off)
W
7.0
Cooling
Psb (Standby mode cooling)
W
7.0
Cdc (Degradation cooling)
0.25
Heating
Psb (Standby mode heating)
W
7.0
Cdh (Degradation heating)
0.25
Pck (Crankcase heater mode)
W
0.0
Poff (Off mode)
W
0.0
Cooling function included
Yes
Heating function included
Yes
Average climate included
Yes
Cold season included
No
Warm season included
No