4 Installation

Installation manual

9

RZQG7 RZQG71~12 RZQG140L7Y1L
Split system air conditioners
4P473073-1 – 2017.03

4

Route the wiring through the frame and connect it to it.

Routing through
the frame

Choose one of the 3 possibilities:

a

b

a

b

a

b

2

3

1

a

 Power supply cable

b

 Interconnection cable

Connecting to the
frame

When cables are routed from the unit, a
protection sleeve for the conduits (PG
insertions) can be inserted at the knockout
hole.

When you do not use a wire conduit,
protect the wires with vinyl tubes to
prevent the edge of the knockout hole from
cutting the wires.

a b c

d

e

A B

A

 Inside of the outdoor unit

B

 Outside of the outdoor unit

a

 Wire

b

 Bush

c

 Nut

d

 Frame

e

 Hose

5

Reattach the service cover.

6

Connect an earth leakage circuit breaker and fuse to the power
supply line.

4.6

Finishing the outdoor unit
installation

4.6.1

To finish the outdoor unit installation

1

Insulate and fix the refrigerant piping and interconnection cable
as follows:

f

b

a

e

d

c

a

Gas pipe

b

Gas pipe insulation

c

Interconnection cable

d

Liquid pipe

e

Liquid pipe insulation

f

Finishing tape

2

Install the service cover.

4.6.2

To check the insulation resistance of the
compressor

NOTICE

If,  after  installation,  refrigerant  accumulates  in  the
compressor,  the  insulation  resistance  over  the  poles  can
drop,  but  if  it  is  at  least  1  MΩ,  then  the  unit  will  not  break
down.

▪ Use a 500 V mega-tester when measuring insulation.

▪ Do not use a mega-tester for low-voltage circuits.

1

Measure the insulation resistance over the poles.

If

Then

≥1 MΩ

Insulation resistance is OK. This procedure
is finished.

<1 MΩ

Insulation resistance is not OK. Go to the
next step.

2

Turn ON the power and leave it on for 6 hours.

Result: 

The  compressor  will  heat  up  and  evaporate  any

refrigerant in the compressor.

3

Measure the insulation resistance again.

Summary of Contents for RZQG71L8Y1L

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners RZQG71L9V1L RZQG71L8Y1L RZQG100L8Y1L RZQG125L8Y1L RZQG140L7Y1L...

Page 2: ...500 HU HD HU 200 1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300...

Page 3: ...sor 9 5 Commissioning 10 5 1 Checklist before commissioning 10 5 2 To perform a test run 10 5 3 Error codes when performing a test run 11 6 Technical data 12 6 1 Service space Outdoor unit 12 6 2 Pipi...

Page 4: ...5 3 5 5 4 M12 a a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts us...

Page 5: ...piping to the outdoor unit 1 Do the following Remove the service cover a with screw b Remove the piping intake plate c with screw d c a b d 2 Choose a piping route a b c or d a b c d 3 If you have cho...

Page 6: ...plate NOTICE Make sure to use a recommended bubble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture t...

Page 7: ...g refrigerant piping Setup on page 6 4 4 4 To charge refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated greenhouse gases I...

Page 8: ...circuit power Ssc greater than or equal to the minimum Ssc value Model Minimum Ssc value RZQG71_V1 RZQG100 140_Y1 1170 kVA 4 5 2 Specifications of standard wiring components Component V1 Y1 71 71 100...

Page 9: ...6 Finishing the outdoor unit installation 4 6 1 To finish the outdoor unit installation 1 Insulate and fix the refrigerant piping and interconnection cable as follows f b a e d c a Gas pipe b Gas pipe...

Page 10: ...nts or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liqui...

Page 11: ...rrently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user...