4 Installation

Installation manual

7

RZQG7 RZQG71~12 RZQG140L7Y1L
Split system air conditioners
4P473073-1 – 2017.03

4.4

Charging refrigerant

4.4.1

To determine the additional refrigerant
amount

To determine if adding additional refrigerant is necessary

If

Then

L1 ≤ chargeless length

L1 (m)

Chargeless length=

▪ 10 m (size‑down)

▪ 30 m (standard)

▪ 15 m (size‑up)

You do not have to add
additional refrigerant.

L1 > chargeless length

You must add additional
refrigerant.

For future servicing, encircle the
selected amount in the tables
below.

INFORMATION

Piping length is the largest one way length of liquid piping.

To determine the additional refrigerant amount (R in kg)

L1 (m)

L1 (standard): 30~40 m 40~50 m 50~60 m

(a)

60~75 m

(a)

L1 (size-up): 15~20 m 20~25 m 25~30 m

(a)

30~35 m

(a)

R:

0.5 kg

1.0 kg

1.5 kg

2.0 kg

(a)

Only for RZQG100~140.

4.4.2

To determine the complete recharge
amount

When  piping  length  is  <5  m,  a  complete  recharge  of  the  unit  is
required.

To determine the complete recharge amount (kg) (in case of
standard liquid pipe size)

Model

L1 (m)

3~10 10~20 20~30 30~40 40~50 50~60 60~75

RZQG71

1.9

2.4

2.9

3.4

3.9

RZQG100~140

3.0

3.5

4.0

4.5

5.0

5.5

6.0

To determine the complete recharge amount (kg) (in case of
size‑up liquid pipe size)

Model

L1 (m)

3~5

5~10 10~15 15~20 20~25 25~30 30~35

RZQG71

1.9

2.4

2.9

3.4

3.9

RZQG100~140

3.0

3.5

4.0

4.5

5.0

5.5

6.0

To determine the complete recharge amount (kg) (in case of
size‑down liquid pipe size)

Model

L1 (m)

3~10

RZQG71

1.9

RZQG100~140

3.0

4.4.3

Charging refrigerant: Setup

See 

"4.3.1 Checking refrigerant piping: Setup" on page 6

.

4.4.4

To charge refrigerant

WARNING

▪ Only use R410A as refrigerant. Other substances may

cause explosions and accidents.

▪ R410A  contains  fluorinated  greenhouse  gases.  Its

global  warming  potential  (GWP)  value  is  2087.5.  Do
NOT vent these gases into the atmosphere.

▪ When  charging  refrigerant,  always  use  protective

gloves and safety glasses.

Prerequisite: 

Before charging refrigerant, make sure the refrigerant

piping is connected and checked (leak test and vacuum drying).

1

Connect  the  refrigerant  cylinder  to  both  the  service  port  of  the
gas stop valve and the service port of the liquid stop valve.

2

Charge the additional refrigerant amount.

3

Open the stop valves.

4.4.5

To fix the fluorinated greenhouse gases
label

1

Fill in the label as follows:

b

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

GWP × kg

1000

=
=

+

kg

=

kg

=

GWP: XXX

RXXX

a

f

c

d
e

a

If a multilingual fluorinated greenhouse gases label is
delivered with the unit (see accessories), peel off the
applicable language and stick it on top of 

a

.

b

Factory refrigerant charge: see unit name plate

c

Additional refrigerant amount charged

d

Total refrigerant charge

e

Greenhouse gas emissions

 of the total refrigerant charge

expressed as tonnes CO

2

-equivalent

f

GWP = Global warming potential

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant  charge  in  the  system  (expressed  as  tonnes
CO

2

-equivalent)  is  used  to  determine  the  maintenance

intervals. Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

2

Fix  the  label  on  the  inside  of  the  outdoor  unit.  There  is  a
dedicated place for it on the wiring diagram label.

Summary of Contents for RZQG71L8Y1L

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners RZQG71L9V1L RZQG71L8Y1L RZQG100L8Y1L RZQG125L8Y1L RZQG140L7Y1L...

Page 2: ...500 HU HD HU 200 1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300...

Page 3: ...sor 9 5 Commissioning 10 5 1 Checklist before commissioning 10 5 2 To perform a test run 10 5 3 Error codes when performing a test run 11 6 Technical data 12 6 1 Service space Outdoor unit 12 6 2 Pipi...

Page 4: ...5 3 5 5 4 M12 a a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts us...

Page 5: ...piping to the outdoor unit 1 Do the following Remove the service cover a with screw b Remove the piping intake plate c with screw d c a b d 2 Choose a piping route a b c or d a b c d 3 If you have cho...

Page 6: ...plate NOTICE Make sure to use a recommended bubble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture t...

Page 7: ...g refrigerant piping Setup on page 6 4 4 4 To charge refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated greenhouse gases I...

Page 8: ...circuit power Ssc greater than or equal to the minimum Ssc value Model Minimum Ssc value RZQG71_V1 RZQG100 140_Y1 1170 kVA 4 5 2 Specifications of standard wiring components Component V1 Y1 71 71 100...

Page 9: ...6 Finishing the outdoor unit installation 4 6 1 To finish the outdoor unit installation 1 Insulate and fix the refrigerant piping and interconnection cable as follows f b a e d c a Gas pipe b Gas pipe...

Page 10: ...nts or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liqui...

Page 11: ...rrently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user...

Page 12: ...discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the front cov...

Page 13: ...citor DS1 DIP switch F1U F8U RZQG71_V1 F1U F2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG_Y1 F1U F2U Fuse 31 5 A 250 V F1U A2P Fuse T 5 0 A 250 V F3U F6U Fuse T 6 3 A 250 V F...

Page 14: ......

Page 15: ......

Page 16: ...4P473073 1 2017 03 Copyright 2017 Daikin...

Reviews: