6 Technical data

Installation manual

12

RZQG7 RZQG71~12 RZQG140L7Y1L

Split system air conditioners

4P473073-1 – 2017.03

6

Technical data

subset

  of  the  latest  technical  data  is  available  on  the  regional  Daikin  website  (publicly  accessible).  The 

full  set

  of  latest  technical  data  is

available on the Daikin extranet (authentication required).

6.1

Service space: Outdoor unit

Suction side

In the illustrations below, the service space at the suction side is based on 35°C DB and cooling operation. Forsee
more space in the following cases:

▪ When the suction side temperature regularly exceeds this temperature.

▪ When the heat load of the outdoor units is expected to regularly exceed the maximum operating capacity.

Discharge side

Take refrigerant piping work into account when positioning the units. If your layout does not match any of the
layouts below, contact your dealer.

Single unit (

) | Single row of units (

)

See figure 1 on the inside of the front cover.

A,B,C,D

Obstacles (walls/baffle plates)

E

Obstacle (roof)

a,b,c,d,e

Minimum service space between the unit and obstacles A, B, C, D and E

e

B

Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle B

e

D

Maximum distance between the unit and the edge of obstacle E, in the direction of obstacle D

H

U

Height of the unit

H

B

,H

D

Height of obstacles B and D

1

Seal the bottom of the installation frame to prevent discharged air from flowing back to the suction side through the bottom of the unit.

2

Maximum two units can be installed.
Not allowed

Multiple rows of units (

)

See figure 2 on the inside of the front cover.

Stacked units (max. 2 levels) (

)

See figure 3 on the inside of the front cover.

A1=>A2

(A1) If there is danger of drainage dripping and freezing between the upper and lower units…
(A2) Then install a 

roof

 between the upper and lower units. Install the upper unit high enough above the lower unit to prevent ice buildup at the

upper unit's bottom plate.

B1=>B2

(B1) If there is no danger of drainage dripping and freezing between the upper and lower units…
(B2) Then it is not required to install a roof, but 

seal the gap

 between the upper and lower units to prevent discharged air from flowing back to the

suction side through the bottom of the unit.

6.2

Piping diagram: Outdoor unit

R2T

R4T

R6T

R1T

e

d

i

j

h

g

f

a

c

c

b

e

Y1E

Y1S

M1F-M2F

M1C

S1PL

S1PH

R5T

R3T

a

Field piping (liquid: Ø9.5 flare connection)

b

Field piping (gas: Ø15.9 flare connection)

c

Stop valve (with service port 5/16")

d

Accumulator

e

Filter

f

Heat exchanger

g

Internal service port 5/16"

h

Switch box cooling (only for RZQG_V1)

i

Compressor accumulator

j

Check valve (only for RZQG71)

M1C

Motor (compressor)

M1F‑M2F

Motor (upper and lower fan)

R1T

Thermistor (air)

R2T

Thermistor (discharge)

R3T

Thermistor (suction)

R4T

Thermistor (heat exchanger)

R5T

Thermistor (heat exchanger middle)

R6T

Thermistor (liquid)

S1PH

High pressure switch

S1PL

Low pressure switch (only for RZQG_V1)

Y1E

Electronic expansion valve

Y1S

Solenoid valve (4‑way valve)
Heating
Cooling

Summary of Contents for RZQG71L8Y1L

Page 1: ...Installation manual Split system air conditioners English Installation manual Split system air conditioners RZQG71L9V1L RZQG71L8Y1L RZQG100L8Y1L RZQG125L8Y1L RZQG140L7Y1L...

Page 2: ...500 HU HD HU 200 1000 1000 500 HD HU HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300...

Page 3: ...sor 9 5 Commissioning 10 5 1 Checklist before commissioning 10 5 2 To perform a test run 10 5 3 Error codes when performing a test run 11 6 Technical data 12 6 1 Service space Outdoor unit 12 6 2 Pipi...

Page 4: ...5 3 5 5 4 M12 a a Make sure not to cover the drain holes INFORMATION The recommended height of the upper protruding part of the bolts is 20 mm 20 NOTICE Fix the outdoor unit to the foundation bolts us...

Page 5: ...piping to the outdoor unit 1 Do the following Remove the service cover a with screw b Remove the piping intake plate c with screw d c a b d 2 Choose a piping route a b c or d a b c d 3 If you have cho...

Page 6: ...plate NOTICE Make sure to use a recommended bubble test solution from your wholesaler Do not use soap water which may cause cracking of flare nuts soap water may contain salt which absorbs moisture t...

Page 7: ...g refrigerant piping Setup on page 6 4 4 4 To charge refrigerant WARNING Only use R410A as refrigerant Other substances may cause explosions and accidents R410A contains fluorinated greenhouse gases I...

Page 8: ...circuit power Ssc greater than or equal to the minimum Ssc value Model Minimum Ssc value RZQG71_V1 RZQG100 140_Y1 1170 kVA 4 5 2 Specifications of standard wiring components Component V1 Y1 71 71 100...

Page 9: ...6 Finishing the outdoor unit installation 4 6 1 To finish the outdoor unit installation 1 Insulate and fix the refrigerant piping and interconnection cable as follows f b a e d c a Gas pipe b Gas pipe...

Page 10: ...nts or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The correct pipe size is installed and the pipes are properly insulated The stop valves gas and liqui...

Page 11: ...rrently set temperature is not displayed The wiring is disconnected or there is a wiring error between power supply and outdoor unit between outdoor unit and indoor units between indoor unit and user...

Page 12: ...discharged air from flowing back to the suction side through the bottom of the unit 2 Maximum two units can be installed Not allowed Multiple rows of units See figure 2 on the inside of the front cov...

Page 13: ...citor DS1 DIP switch F1U F8U RZQG71_V1 F1U F2U Fuse F6U Fuse T 3 15 A 250 V F7U F8U Fuse F 1 0 A 250 V F1U F8U RZQG_Y1 F1U F2U Fuse 31 5 A 250 V F1U A2P Fuse T 5 0 A 250 V F3U F6U Fuse T 6 3 A 250 V F...

Page 14: ......

Page 15: ......

Page 16: ...4P473073 1 2017 03 Copyright 2017 Daikin...

Reviews: