• Outdoor Units • R-410A • RZQ71-140C7V1B
1
5
• Split Sky Air • Outdoor Units
15
5
Capacity tables
5 - 2
Cooling capacity tables
RZQ140C (Pair)
Cooling
Cooling capacity
400V [50Hz]
Indoor
Outdoor temp. (°CDB)
EWB
EDB
25
30
35
40
(°C)
(°C)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
TC
(kW)
SHC
(kW)
CPI
(-)
16.0
22
12.3
8.29
0.76
12.2
8.37
0.89
12.5
8.73
0.99
12.1
8.46
1.09
18.0
25
14.0
9.09
0.83
13.§
8.91
0.91
13.1
8.70
1.00
12.6
8.44
1.10
19.0
27
14.4
9.06
0.84
13.9
8.89
0.91
13.4
8.68
1.00
12.8
8.42
1.10
19.5
27
14.5
9.05
0.84
14.1
8.87
0.91
13.5
8.66
1.00
13.0
8.41
1.10
22.0
30
15.2
8.93
0.85
14.7
8.77
0.92
14.3
8.57
1.01
13.7
8.32
1.11
24.0
32
15.8
8.81
0.85
15.3
8.64
0.93
14.8
8.45
1.02
14.3
8.22
1.12
3TW28149
SYMBOLS
AFR:
Air flow rate
(m
3
/min)
BF:
Bypass factor
EWB:
Entering wet bulb temp.
(°CWB)
EDB:
Entering dry bulb temp.
(°CDB)
TC:
Total cooling/heating capacity
(kW)
SHC:
Sensible heating capacity
(kW)
PI:
Power input
(kW)
(comp.+outdoor fan motor)
CPI:
Coefficient of power input.
(-)
Caution:
TC and SHC are shown by kW
NOTES
1. This capacity table is only valid for pair combination with FBQ140
2. Ratings shown are net capacities which include a deduction for indoor fan motor heat
3. On the figure the mark
j
show the max. at standard conditions.
On the figure the mark
Q
show rated capacity and rated coefficient of power input.
However the max. capacity is not guaranteed, except at standard condition.
4. On the tables
Q
show rated capacity and rated coefficient of power input.
5. SHC is based on each EWB and EDB
SHC* = SHC correction for other dry bulb
SHC* = 0.02 x AFR (m
3
/min.) x (1
−
BF) x (DB*
−
EDB)
Add SHC* to SHC.
6. Capacities are based on following conditions:
Outdoor air : 85 % RH. however, the condition on nominal capacity is 7° CDB/6° CWB (heating)
Corresponding refrigerant piping length
: 7.5 m
Level difference
: 0 m
7. Coefficient of power input is the percentage when the rated valve is defined as 1.00.
8. The value contains less than 5% error acording to indoor unit type.
9. Heating capacity include the drop of frost formation.
10. Air flow rate and BF are tabulated below.
Pair
Model
FBQ140
AFR
(BF)
35
(0.14)
11. Rated power input of each model is tabulated below.
Pair
Outdoor
RZQ140C7
Indoor
RZQ140C7
Cooling
4.76kW
Heating
4.82kW
Capacity range
(Rated point)
Cooling capacity
Coefficient
of
power
input.
(-)