• Split Sky Air • Outdoor Units
12
• Outdoor Units • R-410A • RZQ71-140C7V1B
5
Capacity tables
5 - 2
Cooling capacity tables
RZQ100C
Cooling
3D059957
Indoor
Outdoor temperature (°C DB)
EWB
EDB
25
30
35
40
°C
°C
TC
(kW)
SHC
(kW)
CPI
( - )
TC
(kW)
SHC
(kW)
CPI
( - )
TC
(kW)
SHC
(kW)
CPI
( - )
TC
(kW)
SHC
(kW)
CPI
( - )
16.0
22
10.2
6.93
0.86
10.2
7.00
1.01
10.5
7.29
1.12
10.1
7.08
1.23
18.0
25
11.8
7.59
0.94
11.3
7.45
1.03
11.0
7.27
1.13
10.5
7.06
1.24
19.0
27
12.0
7.57
0.95
11.6
7.43
1.03
11.2
7.26
1.13
10.8
7.04
1.24
19.5
27
12.1
7.56
0.95
11.8
7.41
1.03
11.3
7.25
1.13
10.9
7.03
1.24
22.0
30
12.7
7.46
0.96
12.3
7.32
1.04
11.9
7.16
1.14
11.4
6.96
1.25
24.0
32
13.2
7.36
0.96
12.8
7.22
1.05
12.4
7.06
1.15
11.9
6.87
1.27
NOTES
1
Ratings shown are net capacities which include a deduction for indoor fan motor heat.
2
On the figure the mark with show the max, onces at standard conditions.
On the figure the mark with show rated capacity and rated coefficient of power input.
However the max. Capacity is not guaranteed ecxept at standard condition.
3
SHC* is based on each EWB and EDB.
SHC= SHC correction for other dry bulb.
= 0.02xAFR (m
3
/min.)x(1-BF)x(DB*-EDB)
Add SHC to SHC*.
4
Capacities are based on the following conditions.
Outdoor air: 85% RH. However, the condition
rated capacity is 7°C DB/6°C WB. (heating)
Corresponding refrigerant piping length
: 5.0m
Level difference
: 0m
5
Coefficient of power input is the percentage when the rated value is defined as 1.00.
6
The value contains less than 5% error acording to indoor unit type.
7
Heating performance include the drop of frost formation.
8
Air flow rate and (BF) are tabulated below.
9
Rated power input of each model is tabulated below.
(Pair)
(Twin)
FCQH100C
FCQ100C
FBQ100
FHQ100
FAQ100
FUQ100
FCQ50Cx2
FCQ50Bx2
FFQ50x2
FBQ50x2
AFR
(BF)
32.5
(0.17)
23.5
(0.16)
27
(0.20)
24
(0.14)
23
(0.10)
29
(0.07)
AFR
(BF)
12.5x2
(0.21x2)
12x2
(0.16x2)
14x2
(0.15x2)
13x2
(0.1x2)
(Triple)
FCQ35Cx3
FFQ35Bx3
FBQ35x3
FHQ35x3
AFR
(BF)
10.5x3
(0.28x3)
10x3
(0.25x3)
11.5x3
(0.15x3)
13x3
(0.2x3)
(Pair)
(Twin)
FCQH100C
FCQ100C
FBQ100
FHQ100
FAQ100
FUQ100
FCQ50Cx2
FFQ50x2
FBQ50x2
FHQ50x2
Cooling
2.66
2.77
3.00
3.30
3.45
3.12
Cooling
2.92
2.93
3.16
3.48
Heating
2.55
3.02
2.99
3.49
3.27
3.37
Heating
3.18
3.20
3.15
3.67
(Triple)
FCQ35Cx3
FFQ35x3
FBQ35x3
FHQ35x3
Cooling
2.92
2.93
3.16
3.48
Heating
3.18
3.20
3.15
3.67
SYMBOLS
AFR :
Air
flow
rate
(m3/mim.)
BF
:
Bypass factor
EWB
:
Entering wet bulb temp.
(°C DB)
EDB
:
Entering dry bulb temp.
(°C DB)
TC
:
Total cooling (heating) capacity
(kW)
SHC
:
Sensible heat capacity
(kW)
PI
:
Power input (Comp.+outdoor fan motor).
(kW)
CPI
:
Coefficient of power input
( - )
Caution
:
TC and SHC are shown by kW.
Cooling
Coefficien
t of power input
( -
)
Cooling Capacity (kW)
Rated point
Capacity range