Installation manual

7

RZQS71~125B7V3

Split System air conditioners

4PW32097-1

Preventing foreign objects from entering

Plug the pipe through-holes with putty or insulating material
(procured locally) to stop up all gaps, as shown in the figure.

Insects or small animals entering the outdoor unit may cause a short
circuit in the electrical box.

Cautions for handling stop valve

The stop valves for indoor-outdoor connecting piping are closed
at shipment from the factory.

The names of parts of the stop valve are shown in the figure.

Since the side boards may be deformed if only a torque wrench
is used when loosening or tightening flare nuts, always lock the
shut-off valve with a wrench and then use a torque wrench.
Do not place wrenches on the valve cover.

Applying an excessive torque may distort the interior stop valve
surface causing gas to leak inside the valve and causing the
flare nut to crack eventually.
Do not apply force on the valve cover, this may result in a
refrigerant leak.

For cooling operation under low ambient temperature or any
other operation under low pressure, apply silicon pad or similar
to prevent freezing of the gas stop valve flare nut (see figure).
Freezing of the flare nut may cause refrigerant leak.

How to use the shut-off valve

Use hexagonal wrenches 4 mm and 6 mm.

Opening the valve

1.

Place the hex wrench on the valve bar and turn counter-
clockwise.

2.

Stop when the valve bar no longer turns. It is now open.

Closing the valve

1.

Place the hex wrench on the valve bar and turn clockwise.

2.

Stop when the valve bar no longer turns. It is now closed.

Cautions for handling the valve cover

The valve cover is sealed where indicated by the arrow. 
Refer to the figure.
Take care not to damage it.

After operating the valve, be sure to tighten the valve cover
properly.

Check for refrigerant leakage after tightening the cap.

Cautions for handling service port

Always use a flexible charge hose with a push-rod and valve to
enable recovery of remaining refrigerant in the charge hose.

After the work, tighten the valve cover in place.
Tightening torque: 10.8~14.7 N•m

Precautions when connecting field piping and regarding 
insulation

Be careful not to let the indoor and outdoor branch piping come
into contact with the compressor terminal cover.
If the liquid-side piping insulation might come into contact with it,
adjust the height as shown in the figure below. Also, make sure
the field piping does not touch the bolts or outer panels of the
compressor.

When the outdoor unit is installed above the indoor unit the
following can occur:
The condensated water on the stop valve can move to the
indoor unit. To avoid this, please cover the stop valve with
sealing material.

If the temperature is higher than 30°C and the humidity is higher
than RH 80%, then the thickness of the sealing materials should
be at least 20 mm in order to avoid condensation on the surface
of the sealing.

Be sure to insulate the liquid and gas-side field piping and the
refrigerant branch kit.

(The highest temperature that the gas-side piping can reach is
around 120°C, so be sure to use insulating material which is
very resistant.)

1

Putty or insulating material 
(produced locally)

Make sure to keep the valve open during operation.

1

Service port

2

Shut-off valve

3

Field piping connection

4

Valve cover

1

Spanner

2

Torque wrench

Silicon sealing pad
(Make sure there is no gap)

1

3

4

1

2

2

 Closing direction

A

Liquid side

B

Gas side

Tightening torque

Liquid pipe

13.5~16.5 N•m

Gas pipe

22.5~27.5 N•m

Any exposed piping may cause condensation or burns
if touched.

A

B

Summary of Contents for RZQ-BW1

Page 1: ...INSTALLATION MANUAL RZQS71B7V3 RZQS100B7V3 RZQS125B7V3 Split System air conditioners...

Page 2: ...7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 H1 H2 L7 L1 L6 L5 L4 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B...

Page 3: ...u condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili 20 on va...

Page 4: ...on may result in water leakage electric shocks or fire Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or fire Whe...

Page 5: ...rding to national regulations Do not connect the earth wire to gas or water pipes lightning conductor or telephone earth wire Incomplete grounding may cause electric shocks Gas pipe Ignition or explos...

Page 6: ...ration of the operational capacity Frequent frost acceleration in heating operation Disruption of operation due to rise of high pressure When a strong wind blows continuously on the face of the unit t...

Page 7: ...pe disposal If drain pipe disposal from the outdoor unit causes trouble for example if the drain water may splash on people provide the drain piping using a drain socket optional Make sure the drain w...

Page 8: ...e sizes must have the same size as the connected indoor units pipe sizes Branch see marking on figures 3 4 and 5 Selection of branch pipe L A L H 0 L 1 2H 150 250 1 2H L 200 300 H L Installation impos...

Page 9: ...nch pipe to the indoor unit should be as short as possible Try to keep lengths of both branch pipes to the indoor unit equal REFRIGERANT PIPING Field pipes can be installed in four directions Figure F...

Page 10: ...r to the figure Take care not to damage it After operating the valve be sure to tighten the valve cover properly Check for refrigerant leakage after tightening the cap Cautions for handling service po...

Page 11: ...f oxidised film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preventing normal operation When brazing pipes however do not use oxidation preven...

Page 12: ...0 m G1 G2 30 m Based on this decide R2 in the table R1 0 3 Total additional charge amount R R1 R2 kg Table 2 Length unit m additional charging of refrigerant unit kg Example 1 1 G1 L1 35 m G2 L2 L3 7...

Page 13: ...e bundled cables into a unit Fix cables so that cables do not make contact with the pipes especially on high pressure side Secure the electrical wiring with clamping material as shown in the figure be...

Page 14: ...wiring works Form the wires and fix the cover firmly so that the cover may be fit in properly Precautions on wiring of power supply and inter unit wiring Use a round crimp style terminal for connectio...

Page 15: ...pt displaying the heating symbol all the time and the unit will switch to heating operation automatically after elapse of that time 2 In case you cannot operate the unit in test run mode for any unusu...

Page 16: ...r code U4 or UF is displayed on the remote controller check the inter unit branch wiring connection The reversed phase protection detector of this product only works during the initialisation stage af...

Page 17: ...r air R2T Thermistor coil R3T Thermistor discharge pipe R4T Thermistor suction pipe R5T Thermistor power module RC Signal receiver circuit S1NPL Pressure sensor low S1PH Pressure switch high S1PL Pres...

Page 18: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW32097 1...

Reviews: