
4 Installation
Installation manual
12
RZAG71~Y1
Sky Air Alpha-series
4P485927-1 – 2017.04
NOTICE
In Europe, the
greenhouse gas emissions
of the total
refrigerant charge in the system (expressed as tonnes
CO
2
-equivalent) is used to determine the maintenance
intervals. Follow the applicable legislation.
Formula to calculate the greenhouse gas emissions:
GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000
2
Fix the label on the inside of the outdoor unit. There is a
dedicated place for it on the wiring diagram label.
4.5
Connecting the electrical wiring
DANGER: RISK OF ELECTROCUTION
WARNING
ALWAYS use multicore cable for power supply cables.
CAUTION
For use of units in applications with temperature alarm
settings it is recommended to foresee a delay of 10
minutes for signalling the alarm in case the alarm
temperature is exceeded. The unit may stop for several
minutes during normal operation for "defrosting the unit", or
when in "thermostat stop" operation.
4.5.1
About electrical compliance
RZAG71~140M7V1B
Equipment complying with EN/IEC 61000‑3‑12 (European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current >16 A and ≤75 A per phase.).
RZAG71~140M7Y1B
Equipment
complying
with
EN/IEC
61000‑3‑2
(European/
International Technical Standard setting the limits for harmonic
currents produced by equipment connected to public low-voltage
systems with input current ≤16 A per phase.).
4.5.2
Guidelines when connecting the electrical
wiring
Tightening torques
Item
Tightening torque (N•m)
M4 (X1M)
1.2~1.8
M4 (earth)
1.2~1.4
M5 (X1M)
2.0~3.0
M5 (earth)
2.4~2.9
If limited space is available at the wire terminal, use bended crimp-
style ring terminals.
4.5.3
Specifications of standard wiring components
Component
V1
Y1
71
100~140
71
100
125
140
Power supply cable MCA
(a)
20.2 A
30.5 A
13.3 A
17.1 A
16.9 A
16.6
Voltage range
220~240 V
380~415 V
Phase
1~
3N~
Frequency
50 Hz
Wire sizes
Must comply with applicable legislation
Interconnection cables
Minimum cable section of 2.5 mm² and applicable for 230 V
Recommended field fuse
25 A
32 A
16 A
20 A
Earth leakage circuit breaker
Must comply with applicable legislation
(a)
MCA=Minimum circuit ampacity. Stated values are maximum values (see electrical data of combination with indoor units for exact values).
4.5.4
To connect the electrical wiring on the
outdoor unit
NOTICE
▪ Follow the wiring diagram (delivered with the unit,
located at the inside of the service cover).
▪ Make sure the electrical wiring does NOT obstruct
proper reattachment of the service cover.
1
Remove the service cover.
2
Connect the interconnection cables and power supply as
follows:
Summary of Contents for RZAG100M7Y1B
Page 19: ......
Page 20: ...4P485927 1 2017 04 Copyright 2017 Daikin 4P485927 1 0000000X ...