5 Installation

Installation and operation manual

12

RXYSQ6T7Y1B9

VRV IV-S system air conditioner

4P397285-1B – 2016.03

b

a

a

Insulation material

b

Caulking etc.

5.6

Charging refrigerant

5.6.1

Precautions when charging refrigerant

WARNING

▪ Only use R410A as refrigerant. Other substances may

cause explosions and accidents.

▪ R410A  contains  fluorinated  greenhouse  gases.  Its

global  warming  potential  (GWP)  value  is  2087.5.  Do
NOT vent these gases into the atmosphere.

▪ When  charging  refrigerant,  always  use  protective

gloves and safety glasses.

NOTICE

If  the  power  of  some  units  is  turned  off,  the  charging
procedure cannot be finished properly.

NOTICE

Be  sure  to  turn  on  the  power  6  hours  before  operation  in
order  to  have  power  running  to  the  crankcase  heater  and
to protect the compressor.

NOTICE

If operation is performed within 12 minutes after the indoor
and  outdoor  units  are  turned  on,  the  compressor  will  not
operate  before  the  communication  is  established  in  a
correct way between outdoor unit(s) and indoor units.

NOTICE

Before  starting  charging  procedures,  check  if  the  7‑LEDs
display is as normal (see 

"6.1.4 To access mode 1 or 2" on

page  16

),  and  there  is  no  malfunction  code  on  the  user

interface  of  the  indoor  unit.  If  a  malfunction  code  is
present,  see 

"8.1  Solving  problems  based  on  error

codes" on page 22

.

NOTICE

Make  sure  all  connected  indoor  units  are  recognised
(setting [1‑5]).

NOTICE

Close  the  front  panel  before  any  refrigerant  charge
operation is executed. Without the front panel attached the
unit cannot judge correctly whether it is operating properly
or not.

NOTICE

In case of maintenance and the system (outdoor unit+field
indoor  units)  does  not  contain  any  refrigerant  any
more (e.g., after refrigerant reclaim operation), the unit has
to  be  charged  with  its  original  amount  of  refrigerant  (refer
to the nameplate on the unit) and the determined additional
refrigerant amount.

5.6.2

To determine the additional refrigerant
amount

INFORMATION

For  final  charge  adjustment  in  a  test  laboratory,  contact
your dealer.

Additional refrigerant to be charged=R (kg). R should be rounded off
in units of 0.1 kg.

R=[(X

1

×

Ø9.5

)×0.059+(X

2

×

Ø6.4

)×0.022]

X

1...2

=Total length (m) of liquid piping size at 

Øa

INFORMATION

Piping  length  is  considered  the  distance  from  the  outdoor
unit to the farthest indoor unit.

When  using  metric  piping,  please  take  into  account  following  table
concerning the weight factor to be allocated. It should be substituted
in the formula for R.

Inch piping

Metric piping

Size (Ø) (mm)

Weight factor

Size (Ø) (mm)

Weight factor

6.4

0.022

6

0.018

9.5

0.059

10

0.065

5.6.3

To charge refrigerant

To speed up the refrigerant charging process, it is in case of larger
systems  recommended  to  first  pre-charge  a  portion  of  refrigerant
through the liquid line before proceeding with the manual charging. It
can be skipped, but charging will take longer then.

Pre-charging refrigerant

Pre-charging  can  be  done  without  compressor  operation,  by
connecting the refrigerant bottle to the service port of the liquid stop
valve.

1

Connect as shown. Make sure that all outdoor unit stop valves,
as well as valve A are closed.

p< p>

N2

C

b

c

e

a

g

f

d

A

B

a

Pressure reducing valve

b

Nitrogen

c

Weighing scales

d

Refrigerant R410A tank (siphon system)

e

Vacuum pump

f

Liquid line stop valve

g

Gas line stop valve

A

Valve A

B

Valve B

C

Valve C

2

Open valves C and B.

3

Pre‑charge refrigerant until the determined additional refrigerant
amount is reached or pre‑charging is not possible anymore, and
then close valves C and B.

4

Do one of the following:

If

Then

The determined additional
refrigerant amount is 

reached

Disconnect the manifold from
the liquid line.

You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.

Summary of Contents for RXYSQ6T7Y1B9

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ6T7Y1B9...

Page 2: ...1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB H...

Page 3: ...em da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodytu...

Page 4: ...king field settings 16 6 1 2 To access the field setting components 16 6 1 3 Field setting components 16 6 1 4 To access mode 1 or 2 16 6 1 5 To use mode 1 17 6 1 6 To use mode 2 17 6 1 7 Mode 1 and d...

Page 5: ...aper in the box of the outdoor unit Outdoor unit installation and operation manual Installation and operation instructions Format Paper in the box of the outdoor unit Installer and user reference guid...

Page 6: ...cid deoxidised seamless copper for refrigerant Foreign materials inside pipes including oils for fabrication must be 30 mg 10 m 4 2 2 Refrigerant piping material Piping material Phosphoric acid deoxid...

Page 7: ...r unit capacity type HP Refrigerant branch kit 6 KHRQ22M20T Refnet joints at other branches For refnet joints other than the first branch select the proper branch kit model based on the total capacity...

Page 8: ...the foundation to drain waste water surrounding the unit Avoid drain water flowing over the footpath so that it does not become slippery in case of ambient freezing temperatures If you install the un...

Page 9: ...rader type valve After handling the service port make sure to tighten the service port cover securely For the tightening torque refer to the table below Check for refrigerant leaks after tightening th...

Page 10: ...This means that they will close Leak test and vacuum drying of field piping and indoor units is impossible when this happens Therefore there will be explained 2 methods for initial installation leak...

Page 11: ...mum operation pressure of the unit i e 4 0 MPa 40 bar 2 Test for leaks by applying a bubble test solution to all piping connections 3 Discharge all nitrogen gas NOTICE Make sure to use a recommended b...

Page 12: ...s original amount of refrigerant refer to the nameplate on the unit and the determined additional refrigerant amount 5 6 2 To determine the additional refrigerant amount INFORMATION For final charge a...

Page 13: ...e will be displayed In that case refer to 5 6 4 Error codes when charging refrigerant on page 13 and solve the malfunction accordingly Resetting the malfunction can be done by pushing BS3 You can rest...

Page 14: ...ut holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 5 7 3 Guidelines when connecting the electrical wiring Tightening torques Wiring Screw size T...

Page 15: ...he edge of the knockout hole from cutting the wires a b c d e A B A Inside of the outdoor unit B Outside of the outdoor unit a Wire b Bush c Nut d Frame e Hose 6 Reattach the service cover 7 Connect a...

Page 16: ...setting components The components to make field settings are as follows BS2 SET BS1 MODE BS3 RETURN BS4 TEST BS5 RESET H1P H2P H3P H4P H5P H6P H7P H8P A1P A2P X1M X2M 1 2 OFF ON DS1 MULTI DEMAND L N O...

Page 17: ...P ON Unit is currently operating under low noise restrictions Example 7 LEDs display Mode 1 You can read out setting 1 5 the total number of connected indoor units as follows Action Button display 1 S...

Page 18: ...e at the selected power consumption limitation The second method is to enable power consumption limitation based on an external input For this operation an optional accessory is required 7 LEDs displa...

Page 19: ...ing the field setting again 2 21 Refrigerant recovery vacuuming mode In order to achieve a free pathway to reclaim refrigerant out of the system or to remove residual substances or to vacuum the syste...

Page 20: ...s setting is used in conjunction with setting 2 8 Eco default Mild Quick Powerful 2 42 Heating comfort setting This setting is used in conjunction with setting 2 9 Eco default Mild Quick Powerful 6 1...

Page 21: ...or any other material Additional refrigerant charge The amount of refrigerant to be added to the unit shall be written on the included Added refrigerant plate and attached to the rear side of the fron...

Page 22: ...erform correcting actions as explained in the malfunction code table After correcting the abnormality press BS3 to reset the malfunction code and retry operation INFORMATION If a malfunction occurs th...

Page 23: ...the specified indoor unit are not connected correctly to the outdoor unit Open the stop valve on both the gas and liquid side Confirm that the piping and wiring of the specified indoor unit are connec...

Page 24: ...refer to the installation manual of the option 3 Refer to the installation or service manual on how to use BS1 BS4 push buttons and DS1 1 and DS1 2 DIP switches 4 Do not operate the unit by short cir...

Page 25: ...Detailed information on required actions to achieve certain functions can be found in the dedicated installation and operation manual of the indoor unit Refer to the operation manual of the installed...

Page 26: ...ating or cooling operation b COOL HEAT CHANGEOVER SWITCH Set the switch to for cooling or to for heating To start 1 Select operation mode with the cool heat changeover switch as follows Cooling operat...

Page 27: ...The air flow flap itself adjusts its position The air flow direction can be fixed by the user Automatic and desired position WARNING Never touch the air outlet or the horizontal blades while the swin...

Page 28: ...ontact your dealer and keep the warranty card at hand 13 2 2 Recommended maintenance and inspection Since dust collects when using the unit for several years performance of the unit will deteriorate t...

Page 29: ...malfunction code reset the code by pushing the ON OFF button If not ask your installer for advice Main code Contents External protection device was activated EEPROM failure indoor Drain system malfun...

Page 30: ...display The fan direction does not swing This is because the unit is being controlled by the micro computer 14 2 6 Symptom White mist comes out of a unit Indoor unit When humidity is high during cooli...

Page 31: ...operation This is to prevent refrigerant from remaining in the compressor The unit will stop after 5 to 10 minutes 14 2 17 Symptom The inside of an outdoor unit is warm even when the unit has stopped...

Page 32: ...4P397285 1 B 00000005 4P397285 1B 2016 03 Copyright 2015 Daikin...

Reviews: