9 Technical data

Installation and operation manual

25

RXYSQ4~6TAY1B
VRV IV-S system air conditioner
4P482256-1 – 2017.03

Main code

Cause

Solution

▪ The stop valve of an outdoor unit is left closed.

▪ Insufficient refrigerant

▪ Open the stop valve on both the gas and liquid side.

▪ Check  if  the  additional  refrigerant  charge  has  been

finished  correctly.  Recalculate  the  required  amount  of
refrigerant  from  the  piping  length  and  add  an  adequate
amount of refrigerant.

Refrigerant overcharge

Recalculate the required amount of refrigerant from the
piping length and correct the refrigerant charge level by
recovering any excessive refrigerant with a refrigerant
recovery machine.

Ambient temperature sensor malfunction (R1T) - A1P
(X18A)

Check connection on PCB or actuator.

Discharge temperature sensor malfunction (R3T): open
circuit / short circuit - A1P (X29A)

Check connection on PCB or actuator.

Suction temperature sensor malfunction

(R2T) - A1P (X30A)

(R7T) - A1P (X30A)

Check connection on PCB or actuator.

Liquid temperature sensor (after subcool HE) malfunction
(R6T) - A1P (X30A)

Check connection on PCB or actuator.

Liquid temperature sensor (coil) malfunction (R4T) - A1P
(X30A)

Check connection on PCB or actuator.

Gas temperature sensor (after subcool HE) malfunction
(R5T) - A1P (X30A)

Check connection on PCB or actuator.

High pressure sensor malfunction (S1NPH): open circuit /
short circuit - A1P (X32A)

Check connection on PCB or actuator.

Low pressure sensor malfunction (S1NPL): open circuit /
short circuit - A1P (X31A)

Check connection on PCB or actuator.

Transmission outdoor unit - inverter: INV1 / FAN1 / FAN2
transmission trouble - A1P (X20A, X28A)

Check connection.

INV1 unbalanced power supply voltage

Check if power supply is within range.

Reversed power supply phase malfunction

Correct phase order.

Insufficient supply voltage

Check if the supply voltage is supplied properly.

Malfunction code: System test run not yet executed (system
operation not possible)

Execute system test run.

No power is supplied to the outdoor unit.

Check if the power wiring for the outdoor unit is connected
correctly.

Faulty wiring to Q1/Q2

Check Q1/Q2 wiring.

System mismatch. Wrong type of indoor units combined
(R410A, R407C, RA, etc)

Indoor unit malfunction

Check if other indoor units have malfunction and confirm
indoor unit mix is allowed.

Improper type of indoor units are connected.

Check the type of indoor units that are currently connected.
If they are not proper, replace them with proper ones.

Incorrect interconnections between units.

Connect interconnections F1 and F2 of the connected BP
unit correctly to the outdoor unit's PCB (TO BP UNIT). Make
sure that the communication with the BP unit is enabled.

▪ The stop valve of an outdoor unit is left closed.

▪ The  piping  and  wiring  of  the  specified  indoor  unit  are  not

connected correctly to the outdoor unit.

▪ Open the stop valve on both the gas and liquid side.

▪ Confirm  that  the  piping  and  wiring  of  the  specified  indoor

unit are connected correctly to the outdoor unit.

9

Technical data

subset

  of  the  latest  technical  data  is  available  on  the  regional  Daikin  website  (publicly  accessible).  The 

full  set

  of  latest  technical  data  is

available on the Daikin extranet (authentication required).

9.1

Service space: Outdoor unit

Outdoor unit:
• When mounting units side by side, the piping route must be to the front, to the back or downwards. In this case the piping route to the side is

not possible.

• When mounting the units side by side and routing the piping to the back, you must keep a distance of ≥250 mm between the units (instead of

≥100 mm as shown on the figures below).

Summary of Contents for RXYSQ4TAY1B

Page 1: ...Installation and operation manual VRV IV S system air conditioner English Installation and operation manual VRV IV S system air conditioner RXYSQ4TAY1B RXYSQ5TAY1B RXYSQ6TAY1B...

Page 2: ...0 1700 1000 500 HU a b 100 100 c d e eB eD A B C D E HB HD A B C 200 300 1000 A B C E 200 300 1000 1000 500 D 1000 D E 1000 1000 500 B D HD HU 300 1000 HD HU 250 1500 HU HD HU 300 1500 B D E HB HD HB...

Page 3: ...3 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Direktyvose su papildymais Direkt v s un to papildin jumos Smernice v platnom znen De i tir...

Page 4: ...la M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin Minim ln teplota...

Page 5: ...8 6 Configuration 18 6 1 Making field settings 18 6 1 1 About making field settings 18 6 1 2 To access the field setting components 18 6 1 3 Field setting components 18 6 1 4 To access mode 1 or 2 19...

Page 6: ...nstructions Format Paper in the box of the outdoor unit Installer and user reference guide Preparation of the installation reference data Detailed step by step instructions and background information...

Page 7: ...io interference in which case the user may be required to take adequate measures 4 1 2 Additional installation site requirements of the outdoor unit in cold climates NOTICE When operating the unit in...

Page 8: ...e pipe size nearest to the required size Use the suitable adapters for the change over from inch to mm pipes field supply The additional refrigerant calculation has to be adjusted as mentioned in 5 6...

Page 9: ...header Indoor unit capacity index Refrigerant branch kit 182 KHRQ22M29H INFORMATION Maximum 8 branches can be connected to a header 4 3 Preparing electrical wiring 4 3 1 Safety device requirements Th...

Page 10: ...he invasion of water in the unit and to avoid the drain water dripping see the following illustration NOTICE If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise...

Page 11: ...aks after tightening the service port cover Tightening torques Stop valve size mm Tightening torque N m turn clockwise to close Shaft Valve body Hexagonal wrench Cap valve lid Service port 9 5 5 4 6 6...

Page 12: ...with screw b a b 2 Choose a piping route a b c or d a b c d 3 If you have chosen the downwards piping route Drill a 4 and remove the knockout hole b Cut out the slits c with a metal saw c c b a 4 6 m...

Page 13: ...the outdoor unit are powered on NOTICE Wait until the outdoor unit has finished the initialisation to apply setting 2 21 Leak test and vacuum drying Checking the refrigerant piping involves Checking f...

Page 14: ...il all moisture has been removed 4 Depending on whether you want to immediately charge refrigerant through the refrigerant charge port or first pre charge a portion of refrigerant through the liquid l...

Page 15: ...valve b Nitrogen c Weighing scales d Refrigerant R410A tank siphon system e Vacuum pump f Liquid line stop valve g Gas line stop valve A Valve A B Valve B C Valve C 2 Open valves C and B 3 Pre charge...

Page 16: ...Contains fluorinated greenhouse gases 2 1 1 1 2 2 kg tCO2 eq GWP kg 1000 kg kg GWP XXX RXXX a f c d e a If a multilingual fluorinated greenhouse gases label is delivered with the unit see accessories...

Page 17: ...ard field supply 3 Connect the power supply as follows 3N 50 Hz 380 415 V L1 L2 L3 L1 L2 L3 N X1M a b c a Earth leakage circuit breaker b Fuse c Power supply cable 4 Fix the cables power supply and tr...

Page 18: ...ervention after changing field settings Some field settings are used for special operation e g 1 time operation recovery vacuuming setting manual adding refrigerant setting etc In such a case it is re...

Page 19: ...S 1 B S 1 B S 1 a c b a Default situation H1P OFF b Mode 1 H1P flashing c Mode 2 H1P ON BS1 Press BS1 BS1 5 s Press BS1 for at least 5 s INFORMATION If you get confused in the middle of the process p...

Page 20: ...power consumption limitation Power consumption limitation reduces the power consumption of the unit compared to nominal operating conditions Power consumption limitation can be set in mode 2 There are...

Page 21: ...ut automatic refrigerant charging functionality following setting should be applied binary 1 default Deactivated binary 2 Activated To stop the manual additional refrigerant charge operation when the...

Page 22: ...daptor DTA104A61 62 If the system needs to be running under power consumption limitation conditions when an external signal is sent to the unit this setting defines the level power consumption limitat...

Page 23: ...e unit on loose connections or damaged electrical components Pipe size and pipe insulation Be sure that correct pipe sizes are installed and that the insulation work is properly executed Stop valves B...

Page 24: ...malfunction code perform correcting actions as explained in the malfunction code table Carry out the test operation again and confirm that the abnormality is properly corrected INFORMATION If a malfun...

Page 25: ...s within range Reversed power supply phase malfunction Correct phase order Insufficient supply voltage Check if the supply voltage is supplied properly Malfunction code System test run not yet execute...

Page 26: ...reezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lower unit to prevent ice buildup at the upper unit s bo...

Page 27: ...an 1 A5P Printed circuit board fan 2 BS1 BS5 Push button switch C32 C67 Capacitor DS1 DIP switch E1HC Crankcase heater F1U F2U Fuse T 3 15 A 250 V A1P F101U Fuse 5 A DC650 V A4P A5P F400U Fuse T 6 3 A...

Page 28: ...manual of the indoor unit Refer to the operation manual of the installed user interface 12 Operation 12 1 Operation range Use the system in the following temperature and humidity ranges for safe and e...

Page 29: ...12 4 Adjusting the air flow direction on page 29 for details To stop 4 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the system stops operating NOTIC...

Page 30: ...njury CAUTION After a long use check the unit stand and fitting for damage If damaged the unit may fall and result in injury NOTICE Do not wipe the controller operation panel with benzine thinner chem...

Page 31: ...s Remove any obstacle and make it well ventilated Check if the user interface display shows time to clean the air filter Refer to 13 Maintenance and service on page 30 and Maintenance in the indoor un...

Page 32: ...nt overloading of the compressor motor the air conditioner starts 5 minutes after it is turned ON again in case it was turned OFF just before The same starting delay occurs after the operation mode se...

Page 33: ...nt caused by flow stop or flow change 14 2 10 Symptom Noise of air conditioners Outdoor unit When the tone of operating noise changes This noise is caused by the change of frequency 14 2 11 Symptom Du...

Page 34: ......

Page 35: ......

Page 36: ...4P482256 1 0000000P 4P482256 1 2017 03 Copyright 2017 Daikin...

Reviews: