background image

Installation manual

14

RXYSQ4~Y1B

VRVIII-S System air conditioner

4PW68122-1 – 02.2011

9.9.

Leak test and vacuum drying

The units were checked for leaks by the manufacturer.

See 

figure 6

  or 

figure 7

  and refer to 

"9.10. Additional  refrigerant

charge" on page 14

  for nomenclature of the parts in 

figure 6

  or

figure 7

.

Confirm that the gas and liquid line stop valves are firmly closed
before pressure test or vacuuming.

Make sure that valve A is completely open.

Air tight test and vacuum drying

Air tight test: Make sure to use nitrogen gas. (For the service
port position, refer to 

"9.2. Cautions for handling stop valve" on

page 9

.

Pressurize the liquid and gas pipes to 4.0 MPa (40 bar) (do not
pressurize more than 4.0 MPa (40 bar)). If the pressure does not
drop within 24 hours, the system passes the test. If the pressure
drops, check where the nitrogen leaks from.

Vacuum drying: Use a vacuum pump which can evacuate to
–100.7 kPa (5 Torr, –755 mm Hg)

1.

Evacuate the system from the liquid and gas pipes by using a
vacuum pump for more than 2 hours and bring the system to
–100.7 kPa. After keeping the system under that condition for
more than 1 hour, check if the vacuum gauge rises or not. If it
rises, the system may either contain moisture inside or have
leaks.

2.

Following should be executed if there is a possibility of moisture
remaining inside the pipe (if piping work is carried out during the
raining season or over a long period of time, rainwater may enter
the pipe during work).
After evacuating the system for 2 hours, pressurize the system
to 0.05 MPa (vacuum break) with nitrogen gas and evacuate the
system again using the vacuum pump for 1 hour to –100.7 kPa
(vacuum dr ying). If the system cannot be evacuated to
–100.7 kPa within 2 hours, repeat the operation of vacuum
break and vacuum drying.
Then, after leaving the system in vacuum for 1 hour, confirm that
the vacuum gauge does not rise.

9.10. Additional refrigerant charge

See 

figure 6

  for Sky Air or room air conditioner applications or

figure 7

 for VRV applications.

To avoid compressor breakdown. Do not charge the refrigerant
more than the specified amount.

This outdoor unit is factory charged with refrigerant and
depending on pipe sizes and pipe lengths some systems require
additional charging of refrigerant. See 

"How to calculate the

additional refrigerant to be charged" on page 12

  for Sky Air or

room air conditioner applications or 

"How to calculate the

additional refrigerant to be charged" on page 13

 for VRV indoor

units.

In case re-charge is required, refer to the nameplate of the unit.
The nameplate states the type of refrigerant and necessary
amount.

Precautions when adding R410A

Be sure to charge the specified amount of refrigerant in liquid state to
the liquid pipe.

Since this refrigerant is a mixed refrigerant, adding it in gas form may
cause the refrigerant composition to change, preventing normal
operation.

Before charging, check whether the refrigerant cylinder is
equipped with a siphon tube or not.

9.11. Important information regarding the 

refrigerant used

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol. Do not vent gases into the atmosphere.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Please fill in with indelible ink,

 the factory refrigerant charge of the product,

 the additional refrigerant amount charged in the field and

+

➁ 

the total refrigerant charge

on the fluorinated greenhouse gases label supplied with the product.

Refrigerant cannot be charged until field wiring has
been completed.

Refrigerant may only be charged after performing the
leak test and the vacuum drying (see above).

When charging a system, care shall be taken that its
maximum permissible charge is never exceeded, in
view of the danger of liquid hammer.

Charging with an unsuitable substance may cause
explosions and accidents, so always ensure that the
appropriate refrigerant (R410A) is charged.

Refrigerant containers shall be opened slowly.

Always use protective gloves and protect your eyes
when charging refrigerant.

When performing service on the unit requiring the
refrigerant system to be opened, refrigerant must be
evacuated according to local regulations.

Do not use the automatic refrigerant charging function
while working on the indoor units.
When using the automatic refrigerant charging
function, the indoor units operate automatically as
well as the outdoor unit.

When the power is on, please close the front
panel when leaving the unit.

1

Pressure reducing valve

2

Nitrogen

3

Tank

4

Siphon system

5

Measuring instrument

6

Vacuum pump

7

Valve A

8

Gas line stop valve

9

Outdoor unit

10

Liquid line stop valve

11

Indoor unit

12

Stop valve service port

13

Charge hose

14

BP unit (for Sky Air or room air conditioner indoor units only)

Charge the liquid 
refrigerant with the cylinder 
in upright position.

Charge the liquid 
refrigerant with the cylinder 
in up-side-down position.

Summary of Contents for RXYSQ4P8V1B

Page 1: ...INSTALLATION MANUAL RXYSQ4P8V1B RXYSQ5P8V1B RXYSQ6P8V1B RXYSQ4P8Y1B RXYSQ5P8Y1B RXYSQ6P8Y1B System air conditioner ...

Page 2: ... 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 1000 1000 1000 1000 500 500 1000 500 1000 1000 300 300 300 250 300 300 500 200 1000 1000 1000 1000 1000 1250 1500 1500 1000 1000 100 5 4 4 3 2 1 7 8 9 10 A D C B 5 6 11 3000 1 3 5 4 2 2 mm 6 3 7 1 0 0 0 1 0 0 0 1000...

Page 3: ...0 V 2 3 1 4 5 9 16 V 230 V 1 2 3 4 1 2 3 4 380 415 V V1 Y1 10 16 V 230 V 230 V 16 V 16 V 16 V 1 2 3 2 3 4 1 2 3 4 1 4 5 5 5 380 415 V V1 Y1 11 2 1 1 1 2 3 4 4 V1 1 50 Hz Y1 3N 50 Hz 1 50 Hz 1 8 11 9 8 10 ...

Page 4: ...abelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godkänts av B enligt Certifikatet C 12 Merk som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat ...

Page 5: ...isposal requirements 27 The English text is the original instruction Other languages are translations of the original instructions 1 SAFETY CONSIDERATIONS The precautions listed here are divided into the following two types Both cover very important topics so be sure to follow them carefully Warning Ask your dealer or qualified personnel to carry out installation work Do not install the machine by...

Page 6: ...as leaks Water pipe Hard vinyl tubes are not effective grounds Lightning conductor or telephone ground wire Electric potential may rise abnormally if struck by a lightning bolt Be sure to install an earth leakage breaker Failure to install an earth leakage breaker may cause electric shocks and fire Install drain piping according to this installation manual to ensure good drainage and insulate the ...

Page 7: ...icated for your system To select an optimum refrigerant branching kit refer to Refrigerant branch kit selection on page 11 2 5 Technical and electrical specifications Refer to the Engineering Data Book for the complete list of specifications 1 BP unit branch provider Choose the BP unit type 2 or 3 rooms in function of the installation pattern For 2 rooms BPMKS967B2B For 3 rooms BPMKS967B3B 2 Refne...

Page 8: ...ere the following conditions are satisfied and that meets with your customer s approval Places which are well ventilated Places where the unit does not bother next door neighbours Safe places which can withstand the unit s weight and vibration and where the unit can be installed level Places where there is no possibility of flammable gas or product leak Places where servicing space can be well ens...

Page 9: ... 5 1 Installation method for prevention of falling over If it is necessary to prevent the unit from falling over install as shown in the figure prepare all 4 wires as indicated in the drawing unscrew the top plate at the 4 locations indicated A and B put the screws through the nooses and screw them back tight 5 2 Method for removing transportation stay The yellow transportation stay installed over...

Page 10: ... case of non stacked installation See figure 4 B In case of stacked installation 1 In case obstacles exist in front of the outlet side 2 In case obstacles exist in front of the air inlet A Drain socket B Drain cap C Drain receiver D Insulation tape E Drain stop NOTE If drain holes of the outdoor unit are covered by a mounting base or by floor surface raise the unit in order to provide a free space...

Page 11: ... sizes are not available it is also allowed to use other diameters mm sizes taken the following into account select the pipe size nearest to the required size use the suitable adapters for the change over from inch to mm pipes field supply L A L H 0 L 1 2H 250 1 2H L H 300 H L Installation impossible 1000 200 2000 100 1500 600 3000 A H L All field piping must be installed by a licensed refrigerati...

Page 12: ...gerating system and preventing normal operation When brazing while inserting nitrogen into the piping nitrogen must be set to 0 02 MPa with a pressure reducing valve just enough so that it can be felt on the skin 8 2 Cautions for flare connection See the following table for flare part machining dimensions When connecting the flare nuts apply refrigerant ether or ester oil to the inside and outside...

Page 13: ...ts always lock the stop valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply force on the valve cover this may result in a refrigerant leak For cooling operation under low ambient temperature or any other operation under low pressure apply silicon pad or similar to prevent freezing of the gas stop valve flare nut see figure Freezing of the flare nu...

Page 14: ...not to let the indoor and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as shown in the figure below Also make sure the field piping does not touch the bolts or outer panels of the compressor For VRV indoor units only When the outdoor unit is installed above the indoor unit the follo...

Page 15: ...Between outdoor and indoor units Difference in height Difference in height between outdoor and indoor units H1 30 m Between outdoor and BP units Difference in height Difference in height between outdoor and BP units H2 30 m Between BP and BP units Difference in height Difference in height between BP and BP units H3 15 m Between indoor and indoor units Difference in height Difference in height betw...

Page 16: ...branch kit and BP unit c d e Total indoor capacity Q Gas pipe Liquid pipe Qc Qd Qe 5 0 kW Ø12 7x0 8 Ø6 4x0 8 Qc Qd Qe 5 0 kW Ø15 9x1 0 Ø9 5x0 8 NOTE Qc Qd Qe is total connected indoor capacity c d e indicates the symbols in the figure Example Indoor 4 2 5 kW Indoor 5 3 5 kW Qe 11 0 kW Indoor 6 5 0 kW Gas pipe Ø15 9x1 0 and liquid pipe Ø9 5x0 8 R Total length m of liquid piping size at Ø9 5 x0 054 ...

Page 17: ...side main piping If the recommended pipe size is not available stick to the original pipe diameter which may result in a small capacity decrease Gas side RXYSQ4 5 Ø15 9 Ø19 1 RXYSQ6 Ø19 1 Ø22 2 A Piping between outdoor unit and refrigerant branch kit Match to the size of the connection piping on the outdoor unit Outdoor unit connection piping size B Piping between refrigerant branch kits Use the p...

Page 18: ... Air or room air conditioner applications or How to calculate the additional refrigerant to be charged on page 13 for VRV indoor units In case re charge is required refer to the nameplate of the unit The nameplate states the type of refrigerant and necessary amount Precautions when adding R410A Be sure to charge the specified amount of refrigerant in liquid state to the liquid pipe Since this refr...

Page 19: ...ual fluorinated greenhouse gases label is supplied with the unit Sticking instructions are illustrated on the backside of that label x OFF w ON c blinking ON or OFF H1P H2P H3P H4P H5P H6P H7P w x x x x x x H1P H2P H3P H4P H5P H6P H7P w w w x x w w H1P H2P H3P H4P H5P H6P H7P w x x x x x c This setting is for VRV applications default setting H1P H2P H3P H4P H5P H6P H7P w x x x x c x This setting i...

Page 20: ...k and valve A open Check if the button was pressed within 10 minutes after the valves were opened Is the indoor unit air intake vent or outlet vent blocked After correcting the problem press button once and perform automatic refrigerant charging again starting from step 4 2 x OFF w ON c blinking ON or OFF WARNING Do not touch anything else than the push buttons BS1 5 on the PCB A2P when making the...

Page 21: ...valve and liquid side stop valve Valve A must be left fully closed 3 Open valve A immediately after starting of the compressor 4 Charge the additional refrigerant in its liquid state through the service port of the liquid line stop valve 5 While the unit is at a standstill and under setting mode 2 refer to 11 2 Checks before initial start up on page 22 Setting the mode on page 22 set the required ...

Page 22: ...2F Motor fan lower PS Switching power supply Q1DI Field earth leakage breaker 300 mA R1 Resistor current limiting R1 A1P Resistor R1 A2P Resistor R2 Resistor current sensor R2 A2P Resistor R1T Thermistor air R2T Thermistor discharge R2T Thermistor M1C discharge R3T Thermistor suction 1 R4T Thermistor heat exchanger R4T Thermistor subcool R5T Thermistor suction 2 R6T Thermistor subcooling heat exch...

Page 23: ... remote controller of the indoor unit indicates U1 and the equipment cannot operate Change any two of the three power supply cables L1 L2 L3 to correct phase 10 3 Connection example of total system wiring For Sky Air or room air conditioner indoor units only see figure 9 For VRV indoor units only see figure 10 10 4 Connecting power wire and transmission wires Let the power wire including ground wi...

Page 24: ...27 13 5 Transmission line section 0 75 1 25 mm2 Wire type Only in protected pipes use H07RN F when protected pipes are not used H05VV NOTE Select the power supply cable in accordance with relevant local and national regulations Wire size must comply with the applicable local and national code Specifications for local wiring power cord and branch wiring are in compliance with IEC60245 2 3 1 After f...

Page 25: ... extremely hot In order to prevent damage to the PCB first eliminate static electricity by touching a metal part e g stop valve with your hand Then pull out the connector After measuring the residual voltage pull out the outdoor fan connector Make sure you do not touch a conductive section The outdoor fan may rotate due to strong backblow wind causing the capacitor to charge This may result in an ...

Page 26: ...ate the switches with an insulated stick such as a ball point pen to avoid touching of live parts Location of the DIP switches leds and buttons Led state Throughout the manual the state of the leds is indicated as follows Setting the push button switch BS1 5 Function of the push button switch which is located on the outdoor unit PCB The figure shows state of the led indications when the unit is sh...

Page 27: ...OOL HEAT setting by the slave unit when outdoor units are connected in multiple system combination H1P H2P H3P H4P H5P H6P H7P 1 x x c x x x x 2 x x x c x x x 3 x x x x c x x Possible functions A additional refrigerant charging operation B refrigerant recovery operation vacuuming operation C automatic low noise operation setting at nighttime D low noise operation level setting via the external con...

Page 28: ...NOTE When you want to terminate the test operation press the button The unit will keep running for 30 seconds and then stops During test operation it is impossible to stop the unit with the remote controller H1P H2P H3P H4P H5P H6P H7P normal x x w x x x x abnormal x w x x x x x Indoor units cannot be checked individually After the test operation is finished check the indoor units individually via...

Page 29: ...ss the fan direction and fan strength buttons on the indoor unit to see if they operate properly 12 SERVICE MODE OPERATION After turning on the power supply the unit can not be started until the H2P initialisation led indicating that the unit is still under preparation goes off maximum 12 minutes Vacuuming method At the first installation this vacuuming is not required It is required only for repa...

Page 30: ...VRV indoor units only Pay special attention to places such as a basements etc where refrigerant can stay since refrigerant is heavier than air 13 3 Procedure for checking maximum concentration Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply 1 Calculate the amount of refrigerant kg charged to each system separately 2 Calcul...

Page 31: ...oncentration level then it will be necessary to revise the system Please consult your supplier 14 DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation A Where there are no smaller room divisions B Where there is a room division but there is an opening between the rooms sufficient...

Page 32: ......

Page 33: ......

Page 34: ......

Page 35: ...2 5 B 1 2 4 3 5 C 1 2 3 4 D E E E E E 12 A B C 2 2 3 2 4 7 2 9 3 2 3 5 6 1 4 8 3 2 4 3 2 1 6 8 9 7 2 V1 Y1 3 14 A1P A2P A4P X2M X2M F1 F1 F2 F2 TO IN D UNIT C H SELECTOR X2M A C B A4P TO OUT D UNIT F1 F1 F2 A C B F2 TO IN D UNIT C H SELECTOR X2M TO OUT D UNIT X1M A1P A B C F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 4 5 1 3 A B C 1 3 2 2 V1 Y1 16 TO IN D UNIT F1 F2 TO OUT D UNIT F1 F2 DS...

Page 36: ...4PW68122 1 02 2011 Copyright 2011 Daikin ...

Reviews: