19 Maintenance and service

Installer and user reference guide

47

RXYSCQ4~6TMV1B
VRV IV-S system air conditioner
4P404224-1C – 2019.07

CAUTION: Pay attention to the fan!

It is dangerous to inspect the unit while the fan is running.

Be  sure  to  turn  off  the  main  switch  before  executing  any
maintenance task.

CAUTION

After  a  long  use,  check  the  unit  stand  and  fitting  for
damage. If damaged, the unit may fall and result in injury.

NOTICE

Do  NOT  wipe  the  controller  operation  panel  with  benzine,
thinner,  chemical  dust  cloth,  etc.  The  panel  may  get
discoloured  or  the  coating  peeled  off.  If  it  is  heavily  dirty,
soak  a  cloth  in  water-diluted  neutral  detergent,  squeeze  it
well  and  wipe  the  panel  clean.  Wipe  it  with  another  dry
cloth.

19.1

Maintenance after a long stop
period

E.g., at the beginning of the season.

▪ Check  and  remove  everything  that  might  be  blocking  inlet  and

outlet vents of indoor units and outdoor units.

▪ Clean air filters and casings of indoor units. Contact your installer

or  maintenance  person  to  clean  air  filters  and  casings  of  the
indoor  unit.  Maintenance  tips  and  procedures  for  cleaning  are
provided in the installation/operation manuals of dedicated indoor
units.  Make  sure  to  install  cleaned  air  filters  back  in  the  same
position.

▪ Turn  on  the  power  at  least  6  hours  before  operating  the  unit  in

order  to  ensure  smoother  operation.  As  soon  as  the  power  is
turned on, the user interface display appears.

19.2

Maintenance before a long stop
period

E.g., at the end of the season.

▪ Let the indoor units run in fan only operation for about half a day in

order  to  dry  the  interior  of  the  units.  Refer  to 

"17.2.2  About

cooling,  heating,  fan  only,  and  automatic  operation"  on  page  44

for details on fan only operation.

▪ Turn off the power. The user interface display disappears.

▪ Clean air filters and casings of indoor units. Contact your installer

or  maintenance  person  to  clean  air  filters  and  casings  of  the
indoor  unit.  Maintenance  tips  and  procedures  for  cleaning  are
provided in the installation/operation manuals of dedicated indoor
units.  Make  sure  to  install  cleaned  air  filters  back  in  the  same
position.

19.3

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R410A

Global warming potential (GWP) value: 2087.5

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO2  equivalent
tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

Please contact your installer for more information.

WARNING

The refrigerant in the system is safe and normally does not
leak. If the refrigerant leaks in the room, contact with a fire
of  a  burner,  a  heater  or  a  cooker  may  result  in  a  harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room and contact the dealer where you purchased the unit.

Do not use the system until a service person confirms that
the portion where the refrigerant leaks is repaired.

19.4

After-sales service and warranty

19.4.1

Warranty period

▪ This  product  includes  a  warranty  card  that  was  filled  in  by  the

dealer  at  the  time  of  installation.  The  completed  card  has  to  be
checked by the customer and stored carefully.

▪ If repairs to the product are necessary within the warranty period,

contact your dealer and keep the warranty card at hand.

19.4.2

Recommended maintenance and
inspection

Since  dust  collects  when  using  the  unit  for  several  years,
performance  of  the  unit  will  deteriorate  to  some  extent.  As  taking
apart and cleaning interiors of units requires technical expertise and
in  order  to  ensure  the  best  possible  maintenance  of  your  units,  we
recommend to enter into a maintenance and inspection contract on
top  of  normal  maintenance  activities.  Our  network  of  dealers  has
access  to  a  permanent  stock  of  essential  components  in  order  to
keep your unit in operation as long as possible. Contact your dealer
for more information.

When asking your dealer for an intervention, always state:

▪ The complete model name of the unit.

▪ The manufacturing number (stated on the nameplate of the unit).

▪ The installation date.

▪ The symptoms or malfunction, and details of the defect.

WARNING

▪ Do not modify, disassemble, remove, reinstall or repair

the unit yourself as incorrect dismantling or installation
may  cause  an  electric  shock  or  fire.  Contact  your
dealer.

▪ In case of accidental refrigerant leaks, make sure there

are  no  naked  flames.  The  refrigerant  itself  is  entirely
safe,  non-toxic  and  non-combustible,  but  it  will
generate  toxic  gas  when  it  accidentally  leaks  into  a
room  where  combustible  air  from  fan  heaters,  gas
cookers,  etc.  is  present.  Always  have  qualified  service
personnel  confirm  that  the  point  of  leakage  has  been
repaired or corrected before resuming operation.

19.4.3

Recommended maintenance and
inspection cycles

Be  aware  that  the  mentioned  maintenance  and  replacement  cycles
do not relate to the warranty period of the components.

Summary of Contents for RXYSCQ6TMV1B

Page 1: ...Installer and user reference guide VRV IV S system air conditioner English Installer and user reference guide VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B RXYSCQ6TMV1B...

Page 2: ...5 To flare the pipe end 17 6 4 6 To braze the pipe end 18 6 4 7 Using the stop valve and service port 18 6 4 8 To connect the refrigerant piping to the outdoor unit 19 6 4 9 To connect the refrigerant...

Page 3: ...om The fan speed does not correspond to the setting 50 20 2 4 Symptom The fan direction does not correspond to the setting 50 20 2 5 Symptom White mist comes out of a unit Indoor unit 50 20 2 6 Sympto...

Page 4: ...symbols are Pb lead 0 004 Waste batteries must be treated at a specialized treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential negativ...

Page 5: ...consequence Self combustion and explosion of the compressor because of air going into the operating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate WA...

Page 6: ...arth leakage protector Failure to do so may cause electric shock or fire When installing the earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric n...

Page 7: ...ngineering data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal a...

Page 8: ...mpact S series Q Refrigerant R410A 4 6 Capacity class TM VRV IV series V1 Power supply B European market Minor model change indication 4 3 About the outdoor unit This installation manual concerns the...

Page 9: ...tion and power consumption limitation operation The external control adapter has to be installed in the indoor unit PC configurator cable EKPCCAB You can make several commissioning field settings thro...

Page 10: ...vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds This is to prevent corrosion caused by high levels of salt in t...

Page 11: ...of the refrigerant gas in 1 m3 volume of the occupied space Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required According to the appr...

Page 12: ...3 4 Half hard 1 2H 0 80 mm a Depending on the applicable legislation and the unit s maximum working pressure see PS High on the unit name plate larger piping thickness might be required 5 3 3 To selec...

Page 13: ...on page 12 Refnet joint at first branch counting from outdoor unit When using refnet joints at the first branch counted from the outdoor unit side choose from the following table in accordance with t...

Page 14: ...Limit 30 m 30 m Outdoor lower than indoor Maximum height difference indoor indoor Examples H2 Limit 15 m 15 m Maximum height difference outdoor BP Example 2 H3 Limit N A 30 m Maximum height differenc...

Page 15: ...units Connecting the refrigerant piping Checking the refrigerant piping Charging refrigerant Connecting the electrical wiring Finishing the outdoor installation Finishing the indoor installation INFO...

Page 16: ...he unit to provide a free space of more than 150 mm under the outdoor unit 150 mm Drain holes dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 6 3 6 To prevent the outdoor unit...

Page 17: ...g guidelines into account when connecting pipes Coat the flare inner surface with ether oil or ester oil when connecting a flare nut Tighten 3 or 4 turns by hand before tightening firmly ALWAYS use 2...

Page 18: ...e corrosion or in particular if the flux contains fluorine it will deteriorate the refrigerant oil Always protect the surrounding surfaces e g insulation foam from heat when brazing 6 4 7 Using the st...

Page 19: ...flat head screwdriver and a hammer Optionally cut out the slits b with a metal saw NOTICE Precautions when making knockout holes Avoid damaging the casing and underlying piping After making the knock...

Page 20: ...l the outdoor unit has finished the initialisation Leak test and vacuum drying Checking the refrigerant piping involves Checking for any leakages in the refrigerant piping Performing vacuum drying to...

Page 21: ...ant charge port or first pre charge a portion of refrigerant through the liquid line either open the outdoor unit stop valves or keep them closed See 6 7 4 To charge refrigerant on page 22 for more in...

Page 22: ...ht factor Piping Weight factor 6 4 mm 0 022 6 mm 0 018 9 5 mm 0 059 10 mm 0 065 Connection ratio requirements When selecting indoor units the connection ratio must comply with the following requiremen...

Page 23: ...g with the stop valves closed will damage the compressor NOTICE After adding the refrigerant do not forget to close the lid of the refrigerant charging port The tightening torque for the lid is 11 5 t...

Page 24: ...error No branching is allowed after branching A B C b2 b3 c1 c2 b1 a A Outdoor unit B Indoor unit C Central user interface etc a Main line b1 b2 b3 Branch lines c1 c2 No branch is allowed after branc...

Page 25: ...knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 6 8 4 Guidelines when connecting the electrical wiring Keep the following in mind If st...

Page 26: ...n sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting...

Page 27: ...l Mode 2 field settings Mode 2 is used to change the field settings of the system Consulting the current field setting value and changing the current field setting value is possible In general normal...

Page 28: ...least 5 s INFORMATION If you get confused in the middle of the process press BS1 to return to the default situation 7 2 5 To use mode 1 In mode 1 and in default situation you can read out some informa...

Page 29: ...consumption limitation of the outdoor unit system The first method is to enable a forced power consumption limitation by field setting The unit will always operate at the selected power consumption li...

Page 30: ...ion was not aborted by pushing BS3 the unit will stop its operation after 30 minutes If 30 minutes was not sufficient to add the needed refrigerant amount the function can be reactivated by changing t...

Page 31: ...an external signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 2 The level is according to the table 30 default 40 50 2 32 Forced all...

Page 32: ...temperatures e g 15 C as under low outdoor ambient temperatures e g 5 C Using this idea the system automatically starts decreasing its refrigerant temperature automatically reducing the delivered capa...

Page 33: ...In case of cooling operation the evaporating temperature is allowed to go down to 6 C on temporary base depending on the situation In case of heating operation the condense temperature is allowed to...

Page 34: ...working on the indoor units When performing the test operation NOT only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation...

Page 35: ...ttached to the rear side of the front cover Installation date and field setting Be sure to keep a record of the installation date on the sticker on the rear of the front panel according to EN60335 2 4...

Page 36: ...ant charge in kg 1000 10 1 Overview Maintenance and service This chapter contains information about Preventing electrical hazards when maintaining and servicing the system The refrigerant recovery ope...

Page 37: ...oose connections or defective wiring 11 2 Precautions when troubleshooting WARNING When carrying out an inspection on the switch box of the unit ALWAYS make sure that the unit is disconnected from the...

Page 38: ...unction S1NPL open circuit short circuit A1P X18A Check connection on PCB or actuator Transmission outdoor unit inverter INV1 FAN1 transmission trouble Check connection INV1 unbalanced power supply vo...

Page 39: ...00 500 B D E 1 2 1 HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB HU HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000...

Page 40: ...A2 A1 If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lowe...

Page 41: ...er h Service port high pressure i Muffler j Check valve k Compressor accumulator l Capillary tube m Service port refrigerant charge n Accumulator M1C Compressor M1F Fan motor R1T Thermistor air R2T Th...

Page 42: ...d main A2P Printed circuit board BS1 BS5 Push button switch C1 Capacitor DS1 DIP switch E1HC Crankcase heater F1U Fuse F3U F4U Fuse T 6 3 A 250 V F6U Fuse T 5 0 A 250 V H1P H8P Light emitting diode se...

Page 43: ...y Air SA direct expansion DX indoor units f Residential Air RA direct expansion DX indoor units g User interface wireless dedicated depending on indoor unit type 15 User interface CAUTION NEVER touch...

Page 44: ...st operation the heating capacity on the indoor unit side will temporarily drop until defrosting is completed After defrosting the unit will regain its full heating capacity The indoor unit will stop...

Page 45: ...er interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air RA direct expansion DX indoor unit...

Page 46: ...equipped with advanced energy saving functionality Depending on the priority emphasises can be put on energy saving or comfort level Several parameters can be selected resulting in the optimal balanc...

Page 47: ...it is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Please contact your instal...

Page 48: ...le indicates main components Refer to your maintenance and inspection contract for more details The table indicates recommended intervals of replacement cycles However in order to keep the unit operat...

Page 49: ...or Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activated Low pressure malfunction out...

Page 50: ...arts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication between the units causing the...

Page 51: ...n the selection is done the LOT 21 datasheet can be viewed as a PDF or a HTML webpage INFORMATION Other documents e g manuals can also be consulted from the resulting webpage 24 Glossary Dealer Sales...

Page 52: ...4P404224 1C 2019 07 Copyright 2015 Daikin...

Reviews: