6 Installation

Installer and user reference guide

22

RXYSCQ4~6TMV1B

VRV IV-S system air conditioner

4P404224-1C – 2019.07

NOTICE

If  the  power  of  some  units  is  turned  off,  the  charging
procedure cannot be finished properly.

NOTICE

Be  sure  to  turn  on  the  power  6  hours  before  operation  in
order  to  have  power  running  to  the  crankcase  heater  and
to protect the compressor.

NOTICE

If operation is performed within 12 minutes after the indoor
and  outdoor  units  are  turned  on,  the  compressor  will  not
operate  before  the  communication  is  established  in  a
correct way between outdoor unit(s) and indoor units.

NOTICE

Before  starting  charging  procedures,  check  if  the  7‑LEDs
display is as normal (see 

"7.2.4 To access mode 1 or 2" on

page  28

),  and  there  is  no  malfunction  code  on  the  user

interface  of  the  indoor  unit.  If  a  malfunction  code  is
present,  see 

"11.3  Solving  problems  based  on  error

codes" on page 37

.

NOTICE

Make  sure  all  connected  indoor  units  are  recognised
(setting [1‑5]).

NOTICE

Close  the  front  panel  before  any  refrigerant  charge
operation is executed. Without the front panel attached the
unit cannot judge correctly whether it is operating properly
or not.

NOTICE

In case of maintenance and the system (outdoor unit+field
indoor  units)  does  not  contain  any  refrigerant  any
more (e.g., after refrigerant reclaim operation), the unit has
to  be  charged  with  its  original  amount  of  refrigerant  (refer
to the nameplate on the unit) and the determined additional
refrigerant amount.

6.7.3

To determine the additional refrigerant
amount

INFORMATION

For  final  charge  adjustment  in  a  test  laboratory,  contact
your dealer.

Formula:

R=[(X

1

×

Ø9.5

)×0.059+(X

2

×

Ø6.4

)×0.022]

R

Additional refrigerant to be charged [in kg and rounded off
to 1 decimal place]

X

1...2

Total length [m] of liquid piping size at 

Øa

Metric piping.

 When using metric piping, replace the weight factors

in the formula by the ones from the following table:

Inch piping

Metric piping

Piping

Weight factor

Piping

Weight factor

Ø6.4 mm

0.022

Ø6 mm

0.018

Ø9.5 mm

0.059

Ø10 mm

0.065

Connection  ratio  requirements.

  When  selecting  indoor  units,  the

connection  ratio  must  comply  with  the  following  requirements.  For
more information, see the technical engineering data.

Indoor units

Total CR

(a)

CR per type

(b)

VRV DX

RA DX

VRV DX

50~130%

50~130%

Indoor units

Total CR

(a)

CR per type

(b)

VRV DX

RA DX

RA DX

80~130%

80~130%

(a)

Total CR = Total indoor unit capacity connection ratio

(b)

CR per type = Allowable capacity connection ratio per
indoor unit type

6.7.4

To charge refrigerant

To speed up the refrigerant charging process, it is in case of larger
systems  recommended  to  first  pre-charge  a  portion  of  refrigerant
through the liquid line before proceeding with the manual charging. It
can be skipped, but charging will take longer then.

Pre-charging refrigerant

Pre-charging  can  be  done  without  compressor  operation,  by
connecting the refrigerant bottle to the service port of the liquid stop
valve.

1

Connect as shown. Make sure that all outdoor unit stop valves,
as well as valve A are closed.

p< p>

N2

C

b

c

e

a

g

f

d

A

B

a

Pressure reducing valve

b

Nitrogen

c

Weighing scales

d

Refrigerant R410A tank (siphon system)

e

Vacuum pump

f

Liquid line stop valve

g

Gas line stop valve

A

Valve A

B

Valve B

C

Valve C

2

Open valves C and B.

3

Pre‑charge refrigerant until the determined additional refrigerant
amount is reached or pre‑charging is not possible anymore, and
then close valves C and B.

4

Do one of the following:

If

Then

The determined additional
refrigerant amount is 

reached

Disconnect the manifold from
the liquid line.

You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.

Too much

 refrigerant is

charged

Recover refrigerant.

Disconnect the manifold from
the liquid line.

You do not have to perform the
"Charging refrigerant (in
manual additional refrigerant
charge mode)" instructions.

The determined additional
refrigerant amount is 

not

reached

 yet

Disconnect the manifold from
the liquid line.

Continue with the "Charging
refrigerant (in manual
additional refrigerant charge
mode)" instructions.

Summary of Contents for RXYSCQ6TMV1B

Page 1: ...Installer and user reference guide VRV IV S system air conditioner English Installer and user reference guide VRV IV S system air conditioner RXYSCQ4TMV1B RXYSCQ5TMV1B RXYSCQ6TMV1B...

Page 2: ...5 To flare the pipe end 17 6 4 6 To braze the pipe end 18 6 4 7 Using the stop valve and service port 18 6 4 8 To connect the refrigerant piping to the outdoor unit 19 6 4 9 To connect the refrigerant...

Page 3: ...om The fan speed does not correspond to the setting 50 20 2 4 Symptom The fan direction does not correspond to the setting 50 20 2 5 Symptom White mist comes out of a unit Indoor unit 50 20 2 6 Sympto...

Page 4: ...symbols are Pb lead 0 004 Waste batteries must be treated at a specialized treatment facility for reuse By ensuring waste batteries are disposed of correctly you will help to prevent potential negativ...

Page 5: ...consequence Self combustion and explosion of the compressor because of air going into the operating compressor Use a separate recovery system so that the unit s compressor does NOT have to operate WA...

Page 6: ...arth leakage protector Failure to do so may cause electric shock or fire When installing the earth leakage protector make sure it is compatible with the inverter resistant to high frequency electric n...

Page 7: ...ngineering data A subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal a...

Page 8: ...mpact S series Q Refrigerant R410A 4 6 Capacity class TM VRV IV series V1 Power supply B European market Minor model change indication 4 3 About the outdoor unit This installation manual concerns the...

Page 9: ...tion and power consumption limitation operation The external control adapter has to be installed in the indoor unit PC configurator cable EKPCCAB You can make several commissioning field settings thro...

Page 10: ...vessels Where acidic or alkaline vapour is present Seaside installation Make sure the outdoor unit is NOT directly exposed to sea winds This is to prevent corrosion caused by high levels of salt in t...

Page 11: ...of the refrigerant gas in 1 m3 volume of the occupied space Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required According to the appr...

Page 12: ...3 4 Half hard 1 2H 0 80 mm a Depending on the applicable legislation and the unit s maximum working pressure see PS High on the unit name plate larger piping thickness might be required 5 3 3 To selec...

Page 13: ...on page 12 Refnet joint at first branch counting from outdoor unit When using refnet joints at the first branch counted from the outdoor unit side choose from the following table in accordance with t...

Page 14: ...Limit 30 m 30 m Outdoor lower than indoor Maximum height difference indoor indoor Examples H2 Limit 15 m 15 m Maximum height difference outdoor BP Example 2 H3 Limit N A 30 m Maximum height differenc...

Page 15: ...units Connecting the refrigerant piping Checking the refrigerant piping Charging refrigerant Connecting the electrical wiring Finishing the outdoor installation Finishing the indoor installation INFO...

Page 16: ...he unit to provide a free space of more than 150 mm under the outdoor unit 150 mm Drain holes dimensions in mm 52 102 118 59 62 216 130 20 98 21 89 32 a a Drain holes 6 3 6 To prevent the outdoor unit...

Page 17: ...g guidelines into account when connecting pipes Coat the flare inner surface with ether oil or ester oil when connecting a flare nut Tighten 3 or 4 turns by hand before tightening firmly ALWAYS use 2...

Page 18: ...e corrosion or in particular if the flux contains fluorine it will deteriorate the refrigerant oil Always protect the surrounding surfaces e g insulation foam from heat when brazing 6 4 7 Using the st...

Page 19: ...flat head screwdriver and a hammer Optionally cut out the slits b with a metal saw NOTICE Precautions when making knockout holes Avoid damaging the casing and underlying piping After making the knock...

Page 20: ...l the outdoor unit has finished the initialisation Leak test and vacuum drying Checking the refrigerant piping involves Checking for any leakages in the refrigerant piping Performing vacuum drying to...

Page 21: ...ant charge port or first pre charge a portion of refrigerant through the liquid line either open the outdoor unit stop valves or keep them closed See 6 7 4 To charge refrigerant on page 22 for more in...

Page 22: ...ht factor Piping Weight factor 6 4 mm 0 022 6 mm 0 018 9 5 mm 0 059 10 mm 0 065 Connection ratio requirements When selecting indoor units the connection ratio must comply with the following requiremen...

Page 23: ...g with the stop valves closed will damage the compressor NOTICE After adding the refrigerant do not forget to close the lid of the refrigerant charging port The tightening torque for the lid is 11 5 t...

Page 24: ...error No branching is allowed after branching A B C b2 b3 c1 c2 b1 a A Outdoor unit B Indoor unit C Central user interface etc a Main line b1 b2 b3 Branch lines c1 c2 No branch is allowed after branc...

Page 25: ...knockout holes wrap the wiring with protective tape to prevent damage b c a a Knockout hole b Burr c Sealant etc 6 8 4 Guidelines when connecting the electrical wiring Keep the following in mind If st...

Page 26: ...n sleeve for the conduits PG insertions can be inserted at the knockout hole When you do not use a wire conduit protect the wires with vinyl tubes to prevent the edge of the knockout hole from cutting...

Page 27: ...l Mode 2 field settings Mode 2 is used to change the field settings of the system Consulting the current field setting value and changing the current field setting value is possible In general normal...

Page 28: ...least 5 s INFORMATION If you get confused in the middle of the process press BS1 to return to the default situation 7 2 5 To use mode 1 In mode 1 and in default situation you can read out some informa...

Page 29: ...consumption limitation of the outdoor unit system The first method is to enable a forced power consumption limitation by field setting The unit will always operate at the selected power consumption li...

Page 30: ...ion was not aborted by pushing BS3 the unit will stop its operation after 30 minutes If 30 minutes was not sufficient to add the needed refrigerant amount the function can be reactivated by changing t...

Page 31: ...an external signal is sent to the unit this setting defines the level power consumption limitation that will be applied for step 2 The level is according to the table 30 default 40 50 2 32 Forced all...

Page 32: ...temperatures e g 15 C as under low outdoor ambient temperatures e g 5 C Using this idea the system automatically starts decreasing its refrigerant temperature automatically reducing the delivered capa...

Page 33: ...In case of cooling operation the evaporating temperature is allowed to go down to 6 C on temporary base depending on the situation In case of heating operation the condense temperature is allowed to...

Page 34: ...working on the indoor units When performing the test operation NOT only the outdoor unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation...

Page 35: ...ttached to the rear side of the front cover Installation date and field setting Be sure to keep a record of the installation date on the sticker on the rear of the front panel according to EN60335 2 4...

Page 36: ...ant charge in kg 1000 10 1 Overview Maintenance and service This chapter contains information about Preventing electrical hazards when maintaining and servicing the system The refrigerant recovery ope...

Page 37: ...oose connections or defective wiring 11 2 Precautions when troubleshooting WARNING When carrying out an inspection on the switch box of the unit ALWAYS make sure that the unit is disconnected from the...

Page 38: ...unction S1NPL open circuit short circuit A1P X18A Check connection on PCB or actuator Transmission outdoor unit inverter INV1 FAN1 transmission trouble Check connection INV1 unbalanced power supply vo...

Page 39: ...00 500 B D E 1 2 1 HB HD HB HU 250 750 1000 500 HU HB HU 250 1000 1000 500 HB HU HB HD HD HU 100 1000 1000 500 HU HD HU 200 1000 1000 500 HD HU A B C 250 300 1000 A B C E 250 300 1000 1000 500 D 1000...

Page 40: ...A2 A1 If there is danger of drainage dripping and freezing between the upper and lower units A2 Then install a roof between the upper and lower units Install the upper unit high enough above the lowe...

Page 41: ...er h Service port high pressure i Muffler j Check valve k Compressor accumulator l Capillary tube m Service port refrigerant charge n Accumulator M1C Compressor M1F Fan motor R1T Thermistor air R2T Th...

Page 42: ...d main A2P Printed circuit board BS1 BS5 Push button switch C1 Capacitor DS1 DIP switch E1HC Crankcase heater F1U Fuse F3U F4U Fuse T 6 3 A 250 V F6U Fuse T 5 0 A 250 V H1P H8P Light emitting diode se...

Page 43: ...y Air SA direct expansion DX indoor units f Residential Air RA direct expansion DX indoor units g User interface wireless dedicated depending on indoor unit type 15 User interface CAUTION NEVER touch...

Page 44: ...st operation the heating capacity on the indoor unit side will temporarily drop until defrosting is completed After defrosting the unit will regain its full heating capacity The indoor unit will stop...

Page 45: ...er interface dedicated depending on indoor unit type e BP box required to connect Residential Air RA or Sky Air SA direct expansion DX indoor units f Residential Air RA direct expansion DX indoor unit...

Page 46: ...equipped with advanced energy saving functionality Depending on the priority emphasises can be put on energy saving or comfort level Several parameters can be selected resulting in the optimal balanc...

Page 47: ...it is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value of the refrigerant total refrigerant charge in kg 1000 Please contact your instal...

Page 48: ...le indicates main components Refer to your maintenance and inspection contract for more details The table indicates recommended intervals of replacement cycles However in order to keep the unit operat...

Page 49: ...or Movement detector or floor temperature sensor malfunction indoor User interface thermistor malfunction indoor PCB malfunction outdoor High pressure switch was activated Low pressure malfunction out...

Page 50: ...arts after a few minutes This is because the user interface is intercepting noise from electric appliances other than the air conditioner The noise prevents communication between the units causing the...

Page 51: ...n the selection is done the LOT 21 datasheet can be viewed as a PDF or a HTML webpage INFORMATION Other documents e g manuals can also be consulted from the resulting webpage 24 Glossary Dealer Sales...

Page 52: ...4P404224 1C 2019 07 Copyright 2015 Daikin...

Reviews: