Operation manual

8

RXYCQ8~20A7Y1B

VRV Classic System air conditioner

4P327539-1 — 2012.08

Recommended inspection and maintenance cycles

Be aware that the mentioned maintenance and replacement cycles
do not relate to the warranty period of the components.

Table 1: 

"Inspection Cycle" and "Maintenance Cycle" list

Table 1 assumes the following conditions of use:

1.

Normal use without frequent starting and stopping of the unit.
Depending on the model, we recommend not starting and
stopping the machine more than 6 times/hour.

2.

Operation of the unit is assumed to be 10 hours/day and 2,500
hours/year.

12.2. Shortening of "maintenance cycle" and 

"replacement cycle" needs to be considered in 
following situations

The unit is used in locations where:

1.

heat and humidity fluctuate out of the ordinary

2.

power fluctuation is high (voltage, frequency, wave distortion,
etc.)
(The unit cannot be used if power fluctuation is outside the
allowable range.)

3.

bumps and vibrations are frequent

4.

dust, salt, harmful gas or oil mist such as sulfurous acid and
hydrogen sulfide may be present in the air

5.

the machine is started and stopped frequently or operation time
is long (sites with 24 hour air-conditioning).

Recommended replacement cycle of wear parts

Table 2: 

"Replacement Cycle" list

Contact your dealer for details.

Moving and discarding the unit

Contact your dealer for removing and reinstalling the total
unit. Moving units requires technical expertise.

This unit uses hydrofluorocarbon.
Contact your dealer when discarding this unit. It is required
by law to collect, transport and discard the refrigerant in
accordance with the "hydrofluorocarbon collection and
destruction" regulations.

WARNING

Do not modify, disassemble, remove, reinstall or
repair the unit yourself as incorrect dismantling or
installation may cause an electric shock or fire.
Contact your dealer.

In case of accidental refrigerant leaks, make sure
there are no naked flames. The refrigerant itself is
entirely safe, non-toxic and non-combustible, but it will
generate toxic gas when it accidentally leaks into a
room where combustible air from fan heaters, gas
cookers, etc. ... is present.
Always have qualified service personnel confirm that
the point of leakage has been repaired or corrected
before resuming operation.

Component

Inspection cycle

Maintenance cycle 

(replacements and/

or repairs)

Electric motor

1 year

20,000 hours

PCB

25,000 hours

Heat exchanger

5 years

Sensor (thermistor, etc.)

5 years

Remote controller and switches

25,000 hours

Drain pan

8 years

Expansion valve

20,000 hours

Electromagnetic valve

20,000 hours

NOTE

1.

Table 1 indicates main components.
Refer to your maintenance and inspection contract
for more details.

2.

Table 

1 indicates recommended intervals of

maintenance cycles. However, in order to keep the
unit operational as long as possible, maintenance
work may be required sooner.
Recommended intervals can be used for
appropriate maintenance design in terms of
budgetting maintenance and inspection fees.
Depending on the content of the maintenance and
inspection contract, inspection and maintenance
cycles may in reality be shorter than listed.

Component

Inspection cycle

Maintenance cycle 

(replacements and/

or repairs)

Air filter

1 year

5 years

High efficiency filter (Optional)

1 year

Fuse

10 years

Crankcase heater

8 years

NOTE

1.

Table 2 indicates main components.
Refer to your maintenance and inspection contract
for more details.

2.

Table 

2 indicates recommended intervals of

replacement cycles. However, in order to keep the
unit operational as long as possible, maintenance
work may be required sooner.
Recommended intervals can be used for
appropriate maintenance design in terms of
budgetting maintenance and inspection fees.

NOTE

Damage due to taking apart or cleaning interiors of
units by anyone other than our authorised dealers may
not be included in the warranty.

Summary of Contents for RXYCQ8A7Y1B

Page 1: ...VRV Classic System air conditioner OPERATION MANUAL RXYCQ8A7Y1B RXYCQ10A7Y1B RXYCQ12A7Y1B RXYCQ14A7Y1B RXYCQ16A7Y1B RXYCQ18A7Y1B RXYCQ20A7Y1B System air conditioner...

Page 2: ...6 1 6 2 6 3 5 1 2 7 9 2 4 1 3 8 UNIT NO 1 2 3 4 2 1 2 3 C D A B 4 1 5 5 3 3 3 4 6 4 1 1 1 1 1 1 1 1 2 4 2 3 2 3 2 3 3 5 2 2 2 1 2 3 4 6 2 6 3 5 6 1 8 9 7...

Page 3: ...n electric shock or a re Never use a ammable spray such as hair spray lacquer or paint near the unit It may cause a re Never touch the air outlet or the horizontal blades while the swing ap is in oper...

Page 4: ...ic shock or re make sure that an earth leak detector is installed Be sure the air conditioner is electrically earthed In order to avoid electric shock make sure that the unit is grounded and that the...

Page 5: ...ay change over under centralized control ashes refer to 7 4 Setting the master remote controller on page 5 The fan may keep on running for about 1 minute after the heating operation stops The air ow r...

Page 6: ...ection adjust button Only for Double ow Multi ow Corner Ceiling suspended and Wall mounted Refer to 7 3 Adjusting the air ow direction on page 4 for details Stopping the system 5 Press the on off butt...

Page 7: ...erly for a comfortable environment Avoid excessive heating or cooling Prevent direct sunlight from entering a room during cooling operation by using curtains or blinds Ventilate often Extended use req...

Page 8: ...the remote control display The fan direction does not swing This is because the unit is being controlled by the micro computer Symptom 6 White mist comes out of a unit Symptom 6 1 Indoor unit When hu...

Page 9: ...clean the air lter Refer to Maintenance in the indoor unit manual 3 The system operates but cooling or heating is insuf cient Check if air inlet or outlet of outdoor or indoor unit is not blocked by o...

Page 10: ...Contact your dealer In case of accidental refrigerant leaks make sure there are no naked ames The refrigerant itself is entirely safe non toxic and non combustible but it will generate toxic gas when...

Page 11: ......

Page 12: ...4P327539 1 2012 08 Copyright 2012 Daikin...

Reviews: