4 35 35
3 RXTA30N2V1B
R32 split series
4P518023-7H – 2020.08
▪
Mind the service space requirements when installing the windbreaker.
a
b
c
d
c
d
a
Sea wind
b
Building
c
Outdoor unit
d
Windbreaker
The outdoor unit is designed for outdoor installation only, and for ambient
temperatures within the following ranges:
Cooling mode
Heating mode
–10~46°C DB
–25~24°C DB
6.1.2 Additional installation site requirements of the outdoor unit in cold climates
Protect the outdoor unit against direct snowfall and take care that the outdoor unit
is NEVER snowed up.
a
b
c
c
d
a
Snow cover or shed
b
Pedestal
c
Prevailing wind direction
d
Air outlet
It is recommended to provide at least 150 mm of free space below the unit
(300 mm for heavy snowfall areas). Additionally, make sure the unit is positioned at
least 100 mm above the maximum expected level of snow. If necessary, construct
a pedestal. See
"6.3 Mounting the outdoor unit"
In heavy snowfall areas it is very important to select an installation site where the
snow will NOT affect the unit. If lateral snowfall is possible, make sure that the heat
exchanger coil is NOT affected by the snow. If necessary, install a snow cover or
shed and a pedestal.