Outdoor Unit Installation

3.

Flaring the Pipe End

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing down-

ward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

WARNING

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

4.

Refrigerant Piping

1) Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque 

wrenches.
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas.

2) To prevent gas leakage, apply refrigeration oil on both inner and outer surfaces of the flare. (Use refrigeration oil for 

R410A.)

(Cut exactly at 

right angles.)

 Remove burrs

Set exactly at the position shown below.

A

Flaring

Die

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

A

0 ~ 0.5mm

Clutch-type

Flare tool for R410A

1.0 ~ 1.5mm

Clutch-type (Rigid-type)

1.5 ~ 2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

Coat here with refrigeration oil 

Torque wrench

Piping union

Flare nut

Spanner

Flare nut tightening torque

 

Gas side

Liquid side

 

1/2 inch

5/8 inch

1/4 inch

 

49.5~60.3N • m

61.8~75.4N • m

14.2~17.2N • m

 

(505~615kgf • cm)

(630~770kgf • cm)

(144~175kgf • cm)

Valve cap tightening torque

 

Gas side

Liquid side

 

1/2 inch

5/8 inch

1/4 inch

 

48.1~59.7N • m

44.1~53.9N • m

21.6~27.4N • m

 

(490~610kgf • cm)

(450~550kgf • cm)

(220~280kgf • cm)

Service port cap tightening torque

10.8~14.7N • m

(110~150kgf • cm)

01_EN_3P188821-1C.fm  Page 5  Friday, March 9, 2007  10:52 AM

Summary of Contents for RXS71E3V1B

Page 1: ...Espa ol Italiano Portugues T rk e English Montaj k lavuzlar R410A Split serisi Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410...

Page 2: ...kin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KR...

Page 3: ...y do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has l...

Page 4: ...ing on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit d...

Page 5: ...er of the unit falling use foot bolts or wires In sites with poor drainage use block bases for outdoor unit Adjust foot height until the unit is leveled Otherwise water leakage or pooling of water may...

Page 6: ...tdoor Unit Installation 1 Installing Outdoor Unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is neces...

Page 7: ...enches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration oil on both inner and outer surfaces of the flare Use refrigerat...

Page 8: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 9: ...0 class 71 class 50 60 71 class 50 60 class 71 class 50 60 71 class O D 12 7mm O D 15 9mm O D 6 4mm I D 14 16mm I D 16 20mm I D 8 10mm Thickness 0 8mm Thickness 1 0mm Thickness 0 8mm Thickness 10mm Mi...

Page 10: ...pace where there is a human 1 You can expand the operation range to 15 C by turning on switch B SW4 on the PCB If the outdoor temperature falls to 20 C or lower the operation will stop If the outdoor...

Page 11: ...ioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board In cas...

Page 12: ...ction the unit disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts such as l...

Page 13: ...0704 HT 3P188821 1C M06B069C Two dimensional bar code is a code for manufacturing 00_CV_3P188821 1C fm Page 2 Friday March 9 2007 10 41 AM...

Reviews: