Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop 

valve.

2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a 

hexagonal wrench.

4) After two to three minutes, close the gas stop valve and stop 

forced cooling operation.

Forced cooling operation

1) Press the Forced Operation switch (SW1) to begin forced cooling. Press the Forced Operation switch (SW1) again to stop forced cooling.

Facility Setting Switch 

(RKS50/60/71E3V1B, RKS50/60F2V1B only)

 

(cooling at low outdoor temperature)

This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in 
a residence or office (the space where there is a human).

1) You can expand the operation range to -15°C by turning on switch B (SW4) on the PCB. If the outdoor temperature falls 

to -20°C or lower, the operation will stop. If the outdoor temperature rises, the operation will start again.

CAUTION

1) If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
2) Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used. 

A humidifier might cause dew jumping from the indoor unit outlet vent.

4) Use the indoor unit at the highest level of air flow rate.

Gas stop valve

Valve cap

Hexagonal wrench

Close

Liquid stop valve

Service port

LED-A

SW4

ON

AB

C

D

S102

SW1

S2

Forced 
operation 
switch

LED-A

SW4

ON

AB

C

D

S102

SW1

S2

Turn on 
switch B.

01_EN_3P188821-1C.fm  Page 8  Friday, March 9, 2007  10:52 AM

Summary of Contents for RXS71E3V1B

Page 1: ...Espa ol Italiano Portugues T rk e English Montaj k lavuzlar R410A Split serisi Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410...

Page 2: ...kin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KR...

Page 3: ...y do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has l...

Page 4: ...ing on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit d...

Page 5: ...er of the unit falling use foot bolts or wires In sites with poor drainage use block bases for outdoor unit Adjust foot height until the unit is leveled Otherwise water leakage or pooling of water may...

Page 6: ...tdoor Unit Installation 1 Installing Outdoor Unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is neces...

Page 7: ...enches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration oil on both inner and outer surfaces of the flare Use refrigerat...

Page 8: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 9: ...0 class 71 class 50 60 71 class 50 60 class 71 class 50 60 71 class O D 12 7mm O D 15 9mm O D 6 4mm I D 14 16mm I D 16 20mm I D 8 10mm Thickness 0 8mm Thickness 1 0mm Thickness 0 8mm Thickness 10mm Mi...

Page 10: ...pace where there is a human 1 You can expand the operation range to 15 C by turning on switch B SW4 on the PCB If the outdoor temperature falls to 20 C or lower the operation will stop If the outdoor...

Page 11: ...ioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board In cas...

Page 12: ...ction the unit disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the Operation Manual to ensure that all functions and parts such as l...

Page 13: ...0704 HT 3P188821 1C M06B069C Two dimensional bar code is a code for manufacturing 00_CV_3P188821 1C fm Page 2 Friday March 9 2007 10 41 AM...

Reviews: