Accessories

Accessories supplied with the outdoor unit:

Precautions for Selecting the Location

1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of 

the user.

3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit cables at least 3 meter away from television and radio sets.  This is to prevent interference 

to images and sounds.  (Noises may be heard even if they are more than 3 meter away depending on radio wave conditions.)

8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.

NOTE

Cannot be installed hanging from ceiling or stacked.

CAUTION

When operating the air conditioner in a low outdoor ambient tempera-
ture, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its suction 

side facing the wall.

2) Never install the outdoor unit at a site where the suction side may 

be exposed directly to wind.

3) To prevent exposure to wind, it is recommended to install a baffle 

plate on the air discharge side of the outdoor unit.

4) In heavy snowfall areas, select an installation site where the snow will not affect the unit.

(A) Installation Manual

1

(B) Drain plug (Heat pump-Models)

There is on the bottom packing case.

1

Construct a large canopy.
Construct a pedestal.

Install the unit high enough off the 
ground to prevent burying in snow.

01_EN_3P159684-2F.fm  Page 2  Wednesday, December 7, 2005  3:18 PM

Summary of Contents for RXS50E2V1B

Page 1: ...rlands Espa ol Italiano Portugues T rk e English Montaj k lavuzlar R410A Split serisi Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie spl...

Page 2: ...n TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951...

Page 3: ...cause terminal overheating electrical shock or fire If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames After al...

Page 4: ...n if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9...

Page 5: ...centres 330m m Allow space for piping and electrical servicing 250mm from wall CAUTION Set the piping length from 1 5m to 30m Wrap the insulation pipe with the finishing tape from bottom to top Stop...

Page 6: ...om the foundation surface Outdoor Unit Installation 1 Installing Outdoor Unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawi...

Page 7: ...enches Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces...

Page 8: ...gauge manifold to gas shut off valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no ope...

Page 9: ...aterial Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstan...

Page 10: ...residence or office the space where there is a human 1 You can expand the operation range to 15 C by turning on switch B SW4 on the PCB If the outdoor temperature falls to 20 C or lower the operation...

Page 11: ...rews Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power s...

Page 12: ...el 26 C to 28 C 3 For protection the unit disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the Operation Manual to ensure that all fu...

Page 13: ...0601 HT 3P159684 2F M05B071A...

Reviews: