background image

INSTALLATION 
MANUAL

R410A Split Series

Models 
RXS50E2V1B RKS50E2V1B
RXS60E2V1B RKS60E2V1B
RXS71E2V1B RKS71E2V1B
RYN50E2V1B RYN60E2V1B
RN50E2V1B

RN60E2V1B

ARXS50E2V1B

Deutsch

Français

Nederlands

Español

Italiano

Ελληνικ

Ü

Portugues

Р

ó

сс

ê

ий

Türkçe

English

Montaj kýlavuzlarý

     R410A Split serisi

Installation manual

R410A Split series

Installationsanleitung

Split-Baureihe R410A

Manuel d’installation

Série split R410A

Montagehandleiding

R410A Split-systeem

Manual de instalación

Serie Split R410A

Manuale d’installazione

Serie Multiambienti R410A

Εγχειρ

ß

διο

 

εγκατ

Ü

σταση

ò

διαιρο

ýì

ενη

ò 

σειρ

Üò R4

1

0A

Manual de Instalação

     Série split R410A

Р

óê

оводство

 

по

 

монтаж

ó

Серия

 R4

1

0A 

с

 

раздельной

 ó

станов

ê

ой

00_CV_3P159684-2F.fm  Page 1  Wednesday, November 30, 2005  9:20 AM

Summary of Contents for RXS50E2V1B

Page 1: ...rlands Espa ol Italiano Portugues T rk e English Montaj k lavuzlar R410A Split serisi Installation manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie spl...

Page 2: ...n TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951 KRQ ECMC99 4476 Daikin TCF 020 95951...

Page 3: ...cause terminal overheating electrical shock or fire If any refrigerant has leaked out during the installation work ventilate the room The refrigerant produces a toxic gas if exposed to flames After al...

Page 4: ...n if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9...

Page 5: ...centres 330m m Allow space for piping and electrical servicing 250mm from wall CAUTION Set the piping length from 1 5m to 30m Wrap the insulation pipe with the finishing tape from bottom to top Stop...

Page 6: ...om the foundation surface Outdoor Unit Installation 1 Installing Outdoor Unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawi...

Page 7: ...enches Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces...

Page 8: ...gauge manifold to gas shut off valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no ope...

Page 9: ...aterial Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstan...

Page 10: ...residence or office the space where there is a human 1 You can expand the operation range to 15 C by turning on switch B SW4 on the PCB If the outdoor temperature falls to 20 C or lower the operation...

Page 11: ...rews Observe the notes mentioned following when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power s...

Page 12: ...el 26 C to 28 C 3 For protection the unit disables restart operation for 3 minutes after it is turned off 1 3 Carry out the test operation in accordance with the Operation Manual to ensure that all fu...

Page 13: ...0601 HT 3P159684 2F M05B071A...

Reviews: