10

English

Wiring

 WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, 

electrical shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that an earth leak detector capable of handling higher harmonics must be used, in 
order to prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Equipment complying with EN61000-3-12

(1)

• Do not turn ON the safety breaker until all work is 

completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the 

indoor and outdoor units so that the terminal 
numbers match. Tighten the terminal screws 
securely. We recommend a flathead 
screwdriver be used to tighten the screws. The 
screws are packed with the terminal block.

NOTE

(1)

European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to public 
low-voltage systems with input current >16 A and 

75 A per phase.

Observe the notes mentioned below when wiring to the power supply terminal block.
Precautions to be taken for power supply wiring.

 CAUTION

• When connecting the wires to the terminal block using a single core 

wire, be sure to perform curling.
Problems with the work may cause heat and fires.  

• If the stranded wires must be used, make sure to use the round 

crimp-style terminal for connection to the power supply terminal 
block. Place the round crimp-style terminals on the wires up to the 
covered part and secure in place.

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

Safety 
breaker 
20A

Earth leakage 
circuit breaker

Earth

Inter-unit wire 
4-core 1.5mm² or more
H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power supply
50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

Power supply wire 
3-core 2.5mm² or more
H05RN

Use the specified wire type and 
connect it securely.

Firmly secure wire retainer so wire 
terminations will not receive 
external stress.

Shape wires so 
that the service 
lid and stop 
valve cover fit 
securely.

Power supply 
terminal block

Good

Stripping wire at terminal block

Stranded wire

Round crimp-style
terminal

Wrong

Good

Strip wire end 
to this point.

Excessive strip length 
may cause electrical 
shock or leakage.

Wrong

3PEN360062-3G.book  Page 10  Wednesday, May 27, 2015  9:14 AM

Summary of Contents for RXS42L2V1B

Page 1: ...rie split R410A Fran ais Montagehandleiding R410A Split systeem Nederlands Manual de instalaci n Serie Split R410A Espa ol Manuale d installazione Serie Multiambienti R410A Italiano R410A Manual de I...

Page 2: ...r B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo...

Page 3: ...When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control...

Page 4: ...N When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side...

Page 5: ...th Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced performance The suggested shortest pipe length is 1 5m in order to avoid noise from the outdoor uni...

Page 6: ...Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary f...

Page 7: ...ng the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches...

Page 8: ...m gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no opera...

Page 9: ...d piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insul...

Page 10: ...trial operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 Press ON OFF button to turn on the system 3 Pre...

Page 11: ...the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility...

Page 12: ...uced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase Observe the notes mentioned below when wiring to the power supply terminal block Precautions to be...

Page 13: ...r DISCHARGE Discharge C7 C8 Capacitor DB1 DB3 Diode bridge FU1 FU2 FU3 Fuse FU4 Field fuse IPM Intelligent power module L Live L803 L804 Reactor M1C Compressor motor M1F Fan motor MRCW MRM10 MRM20 MR3...

Page 14: ...ion in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode...

Page 15: ...3P360062 3G 2015 05 Copyright 2013 Daikin 3PEN360062 3G book Page 1 Wednesday May 27 2015 9 14 AM...

Reviews: