Outdoor Unit Installation Drawings

*

**

**

*

(F

oot bolt-hole 

centres)

311

574

(Foot b

olt-hole centres)

(From unit’

s side)

105.5

CAUTION

**Set the piping length 

from 1.5m to 20m.

Wrap the insulation pipe with 
the finishing tape from bottom 
to top.

In sites with poor drainage, use 
block bases for outdoor unit. 
Adjust foot height until the unit 
is leveled.  Otherwise, water 
leakage or pooling of water may 
occur.

Where there is a danger of the unit 
falling, use foot bolts, or wires.

250mm from

 wall

unit: mm

O.D. 9.5mm

Gas pipe

Liquid pipe

O.D. 6.4mm

20g/m

15m

20m

Max. allowable length

Max. allowable height

Additional refrigerant 
required for refrigerant 
pipe exceeding 
10m in length.

Be sure to add the proper amount of additional refrigerant. 

Failure to do so may result in reduced performance.

The suggested shortest pipe length is 1.5m, in order to avoid 

noise from the outdoor unit and vibration. 

(Mechanical noise and vibration may occur depending on how 

the unit is installed and the environment in which it is used.) 

When connecting the FVXS indoor unit, the shortest piping 

length should be no less than around 2.5m.

How to remove the stop 
valve cover

Remove the screw on the 
stop valve cover.
Slide the lid downward 
to remove it.

How to attach the stop 
valve cover

Insert the upper part of 
the stop valve cover into the 
outdoor unit to install.
Tighten the screws.

Stop valve cover

1.5m

Min. allowable length

Allow space for piping 
and electrical servicing.

Allow 300mm of 
work space below 
the ceiling surface.

3PEN360062-3G.book  Page 3  Wednesday, May 27, 2015  9:14 AM

Summary of Contents for RXS42L2V1B

Page 1: ...rie split R410A Fran ais Montagehandleiding R410A Split systeem Nederlands Manual de instalaci n Serie Split R410A Espa ol Manuale d installazione Serie Multiambienti R410A Italiano R410A Manual de I...

Page 2: ...r B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo...

Page 3: ...When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control...

Page 4: ...N When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side...

Page 5: ...th Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced performance The suggested shortest pipe length is 1 5m in order to avoid noise from the outdoor uni...

Page 6: ...Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary f...

Page 7: ...ng the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches...

Page 8: ...m gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no opera...

Page 9: ...d piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insul...

Page 10: ...trial operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 Press ON OFF button to turn on the system 3 Pre...

Page 11: ...the heat exchanger of the unit is exposed to direct wind provide a windbreak wall Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility...

Page 12: ...uced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase Observe the notes mentioned below when wiring to the power supply terminal block Precautions to be...

Page 13: ...r DISCHARGE Discharge C7 C8 Capacitor DB1 DB3 Diode bridge FU1 FU2 FU3 Fuse FU4 Field fuse IPM Intelligent power module L Live L803 L804 Reactor M1C Compressor motor M1F Fan motor MRCW MRM10 MRM20 MR3...

Page 14: ...ion in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode...

Page 15: ...3P360062 3G 2015 05 Copyright 2013 Daikin 3PEN360062 3G book Page 1 Wednesday May 27 2015 9 14 AM...

Reviews: