background image

English

5

Outdoor Unit Installation

3.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

 WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a dryer to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

4.

Refrigerant piping work

 CAUTION

• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

• Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully with the torque 

wrenches. 

A

A

(Cut exactly at 
right angles.)

Remove burrs.

Set exactly at the position shown below.

Flaring

Die

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

Torque wrench

Piping union

Flare nut

Flare nut

Spanner

Flare nut tightening torque

Liquid side

1/4 inch

14.2-17.2N • m

(144-175kgf • cm)

Gas side

3/8 inch

32.7-39.9N • m

(333-407kgf • cm)

Valve cap tightening torque

Liquid side

1/4 inch

21.6-27.4N • m

(220-280kgf • cm)

Gas side

3/8 inch

21.6-27.4N • m

(220-280kgf • cm)

Service port cap tightening torque

10.8-14.7N • m (110-150kgf • cm)

Do not apply refrigeration 
oil to the outer surface.

Apply refrigeration oil to 
the inner surface of the 
flare.

Do not apply refrigeration oil to 
the flare nut to avoid tightening 
with excessive torque.

[Apply oil]

[Tighten]

Summary of Contents for RXS25L3V1B

Page 1: ...ion S rie split R410A Fran ais Montagehandleiding R410A Split systeem Nederlands Manual de instalaci n Serie Split R410A Espa ol Manuale d installazione Serie Multiambienti R410A Italiano R410A Manual...

Page 2: ...lorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer p...

Page 3: ...ormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper...

Page 4: ...m ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor...

Page 5: ...the stop valve cover Remove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor uni...

Page 6: ...foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2...

Page 7: ...orque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them ful...

Page 8: ...hes 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate th...

Page 9: ...of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valv...

Page 10: ...valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn on the main power supply CAUTION Before connecting or disconnecting the selective connector for standby electrici...

Page 11: ...e liquid stop valve close the gas stop valve within 3 minutes then stop the forced cooling operation Facility Setting cooling at low outdoor temperature This function is designed for facilities such a...

Page 12: ...block Observe the notes mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal blo...

Page 13: ...B1 Diode bridge E1 E2 HL1 HN1 HR1 HR2 MR30_A MR30_B Connection E1H Heater FU1 FU2 FU3 Fuse IPM1 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor M1F Fan motor MR30 MRCW MRM10 M...

Page 14: ...a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit brea...

Page 15: ......

Page 16: ...3P381941 1 2014 06 Copyright 2014 Daikin...

Reviews: