Wiring

 WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, 

electrical shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that an earth leak detector capable of handling higher harmonics must be used, in 
order to prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Do not turn ON the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the 

indoor and outdoor units so that the terminal 
numbers match. Tighten the terminal screws 
securely. We recommend a flathead 
screwdriver be used to tighten the screws. 
The screws are packed with the terminal block. 

Observe the notes mentioned below when wiring to the power supply terminal block.
Precautions to be taken for power supply wiring.

 CAUTION

• When connecting the connection wires to the terminal block using a single core wire, be sure to perform curling.

Problems with the work may cause heat and fires.  

• If the stranded wires must be used, make sure to use the round 

crimp-style terminal for connection to the power supply terminal 
block. Place the round crimp-style terminals on the wires up to the 
covered part and secure in place.

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

Safety 
breaker 
16A

Earth leakage 
circuit breaker

Earth

Inter-unit wire 
4-core 1.5mm² or more
H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power supply
50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

Power supply wire 
3-core 2.5mm² or more
H05RN

Use the specified wire type 
and connect it securely.

Firmly secure wire retainer so wire 
terminations will not receive external stress.

Power supply 
terminal block

Shape wires so 
that the service lid 
and stop valve 
cover fit securely.

Strip wire end 
to this point.

Excessive strip length 
may cause electrical 
shock or leakage.

Good

Wrong

Good

Wrong

Stripping wire at terminal block

Stranded wire

Round crimp-style 
terminal

Summary of Contents for RXS25L3V1B

Page 1: ...ion S rie split R410A Fran ais Montagehandleiding R410A Split systeem Nederlands Manual de instalaci n Serie Split R410A Espa ol Manuale d installazione Serie Multiambienti R410A Italiano R410A Manual...

Page 2: ...lorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer p...

Page 3: ...ormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper...

Page 4: ...m ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor...

Page 5: ...the stop valve cover Remove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor uni...

Page 6: ...foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2...

Page 7: ...orque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them ful...

Page 8: ...hes 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate th...

Page 9: ...of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valv...

Page 10: ...valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn on the main power supply CAUTION Before connecting or disconnecting the selective connector for standby electrici...

Page 11: ...e liquid stop valve close the gas stop valve within 3 minutes then stop the forced cooling operation Facility Setting cooling at low outdoor temperature This function is designed for facilities such a...

Page 12: ...block Observe the notes mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal blo...

Page 13: ...B1 Diode bridge E1 E2 HL1 HN1 HR1 HR2 MR30_A MR30_B Connection E1H Heater FU1 FU2 FU3 Fuse IPM1 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor M1F Fan motor MR30 MRCW MRM10 M...

Page 14: ...a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit brea...

Page 15: ......

Page 16: ...3P381941 1 2014 06 Copyright 2014 Daikin...

Reviews: