Wiring

WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, 

electrical shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leak detector. (One that can handle higher harmonics.) 

(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to 
prevent malfunctioning of the earth leak detector itself.)

• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• Do not turn on the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the 

indoor and outdoor units so that the terminal 
numbers match. Tighten the terminal screws 
securely. We recommend a flathead screwdriver 
be used to tighten the screws. The screws are 
packed with the terminal board.

1

2

3

1 2 3

L N

Safety 
breaker 
16A

Earth leakage 

circuit breaker

Earth

Inter-unit wire
4-core 1.5mm² or more
H05RN

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power supply

50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

Power supply wire

3-core 2.5mm² or more
H05RN

1

2

3

Use the specified wire type 
and connect it securely.

Firmly secure wire retainer so wire 
terminations will not receive external stress.

1

2

3

L

N

Power supply
terminal block

Shape wires so 
that the service lid 
and stop valve 
cover fit securely.

Observe the notes mentioned following when wiring to the power supply terminal board.
Precautions to be taken for power supply wiring. 

CAUTION

• When connecting the connection wires to the terminal board using a single core wire, be sure to perform curling. 

Problems with the work may cause heat and fires.

Strip wire end
to this point.

Excessive strip length

may cause electrical

shock or leakage.

Good

Wrong

Good

Wrong

Stripping wire at terminal block

• If the stranded wires must be used, make sure to use the round 

crimp-style terminal for connection to the power supply terminal block. 
Place the round crimp-style terminals on the wires up to the covered 
part and secure in place. 

Stranded wire

Round crimp-style
terminal

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

01_EN_3P297037-2D.indd   10

11/1/2012   11:04:44 AM

Summary of Contents for RXS20K2V1B

Page 1: ...ation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie Split R410A Manuale dinstallazione Serie Multiambienti R410A R410A Manual de Instala o S rie split R410A R410...

Page 2: ...e 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 12E Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 RXS20J2V1B RXS25J2V1B RXS35J2V1B RKS20J2V1B RKS25J2V1B RKS3...

Page 3: ...ES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB65451 3 RXS20K2V1B RXS25K2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N20 09 2011 DEKRA Certification B...

Page 4: ...meda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan RXS20K2V1B RXS25K2V1B 3SB65451 4 Shinri Sada Manager Quality Control Department 3SB65451 4 fm Page 1 Thursday October 27 2011 4 49 P...

Page 5: ...AIKIN TCF 015 P7 07 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 14D Shinri Sada Manager Quality Control Department RXS20K3V1B RXS25K3V1B Machinery 2006 42 EC Electromagnetic Comp...

Page 6: ...5 2 40 DAIKIN TCF 015 P9 09 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 18F Shinri Sada Manager Quality Control Department RXS35K2V1B Machinery 2006 42 EC Electromagnetic Compati...

Page 7: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM...

Page 8: ...terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for...

Page 9: ...m television and radio sets This is to prevent interference to images and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other p...

Page 10: ...ove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor unit to install Tighten the...

Page 11: ...the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts unt...

Page 12: ...lifetime The drying material may dissolve and damage the system Incomplete flaring may cause refrigerant gas leakage 4 Refrigerant piping work CAUTION Use the flare nut fixed to the main unit To preve...

Page 13: ...52W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and...

Page 14: ...nifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge...

Page 15: ...nd manifold for charging The lled out label must be adhered in the proximity of the product charging port e g onto the inside of the stop valve cover NOTE National implementation of EU regulation on c...

Page 16: ...peration press the switch SW1 1 2 3 The selective connector for standby electricity saving in use with standby electricity saving function turned off Push Screwdriver Power supply terminal block Force...

Page 17: ...Earth leakage circuit breaker Earth Inter unit wire 4 core 1 5mm or more H05RN Firmly x the wires with the terminal screws Outdoor unit Indoor unit Power supply 50Hz 220 240V Firmly x the wires with t...

Page 18: ...r in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off...

Page 19: ...Two dimensional bar code is a code for manufacturing 3P297037 2D M12B067A 1210 HT 00_CV_3P297037 2D indd 2 11 1 2012 11 01 11 AM...

Reviews: