Outdoor Unit Installation

5. 

Purging air and checking gas leakage

WARNING

• Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the 

vacuum pump or the unit.

• When piping work is completed, it is necessary to purge the air and check for gas 

leakage.

• If using additional refrigerant, perform air purging from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant.

• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified 

tightening torque.

Compound 
pressure gauge

Pressure 
metre

High-
pressure 
valve

Low-pressure 
valve

Vacuum pump Service port

Liquid 
stop 
valve

Valve caps

Gas stop valve

Charging 
hoses

Gauge 
manifold

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi). 

(High-pressure valve subsequently requires no operation.)

3) Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg).*1

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump. 

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2

5) Remove caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve. 

Close it after 5 seconds, and check for gas leakage. 
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods. 
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves. 

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

*1.  Pipe length vs. vacuum pump run time.

Pipe length

Up to 15m

More than 15m

Run time

Not less than 10 min.

Not less than 15 min.

*2.  If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists. 

Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

01_EN_3P297037-2D.indd   7

11/1/2012   11:04:42 AM

Summary of Contents for RXS20K2V1B

Page 1: ...ation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie Split R410A Manuale dinstallazione Serie Multiambienti R410A R410A Manual de Instala o S rie split R410A R410...

Page 2: ...e 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB64564 12E Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N4 09 2010 RXS20J2V1B RXS25J2V1B RXS35J2V1B RKS20J2V1B RKS25J2V1B RKS3...

Page 3: ...ES LTD Low Voltage 2006 95 EC Electromagnetic Compatibility 2004 108 EC 3SB65451 3 RXS20K2V1B RXS25K2V1B Shinri Sada Manager Quality Control Department DAIKIN TCF 015 N20 09 2011 DEKRA Certification B...

Page 4: ...meda Center Bldg 2 4 12 Nakazaki Nishi Kita ku Osaka 530 8323 Japan RXS20K2V1B RXS25K2V1B 3SB65451 4 Shinri Sada Manager Quality Control Department 3SB65451 4 fm Page 1 Thursday October 27 2011 4 49 P...

Page 5: ...AIKIN TCF 015 P7 07 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 14D Shinri Sada Manager Quality Control Department RXS20K3V1B RXS25K3V1B Machinery 2006 42 EC Electromagnetic Comp...

Page 6: ...5 2 40 DAIKIN TCF 015 P9 09 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 18F Shinri Sada Manager Quality Control Department RXS35K2V1B Machinery 2006 42 EC Electromagnetic Compati...

Page 7: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM...

Page 8: ...terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for...

Page 9: ...m television and radio sets This is to prevent interference to images and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other p...

Page 10: ...ove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor unit to install Tighten the...

Page 11: ...the unit securely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts unt...

Page 12: ...lifetime The drying material may dissolve and damage the system Incomplete flaring may cause refrigerant gas leakage 4 Refrigerant piping work CAUTION Use the flare nut fixed to the main unit To preve...

Page 13: ...52W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and...

Page 14: ...nifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge...

Page 15: ...nd manifold for charging The lled out label must be adhered in the proximity of the product charging port e g onto the inside of the stop valve cover NOTE National implementation of EU regulation on c...

Page 16: ...peration press the switch SW1 1 2 3 The selective connector for standby electricity saving in use with standby electricity saving function turned off Push Screwdriver Power supply terminal block Force...

Page 17: ...Earth leakage circuit breaker Earth Inter unit wire 4 core 1 5mm or more H05RN Firmly x the wires with the terminal screws Outdoor unit Indoor unit Power supply 50Hz 220 240V Firmly x the wires with t...

Page 18: ...r in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off...

Page 19: ...Two dimensional bar code is a code for manufacturing 3P297037 2D M12B067A 1210 HT 00_CV_3P297037 2D indd 2 11 1 2012 11 01 11 AM...

Reviews: