Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After five to ten minutes, close the liquid stop valve with a hexagonal wrench.
4) After two to three minutes, close the gas stop valve and stop forced cooling operation.

How to force cooling operation mode

Using the indoor unit operation/stop button 

Press the indoor unit operation/stop button for at least five seconds. 
(Operation will start.)

• Forced cooling operation will stop automatically after around 15 minutes. 

To force a test run to stop, press the indoor unit operation/stop button.

Using the main unit’s remote control

1) Press the “operation/stop” button. 

(Operation will start.)

2) Press the temperature

 

 

button and the “operation select” button at the same time.

3) Press the “operation select” button twice.

(

 

 

will be displayed and the unit will enter test run mode.)

4) Press the “operation select” button to return the operation mode to cooling.

• Test run mode will stop automatically after around 30 minutes. To force a test run to stop, press the operation/stop button.

Using the outdoor unit forced cooling operation switch (with standby electricity saving function turned OFF)

1) Push on “ ” with a screwdriver. The unit will start operating.
2) The forced cooling mode is selected, and terminates in approx. 15 minutes.

 CAUTION

1) When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
2) After closing the liquid stop valve, close the gas stop valve within three minutes, then stop the forced operation.

Facility Setting 
(cooling at low outdoor temperature)

This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). Never use it in 
a residence or office (the space where there is a human).

1) Cutting jumper 4 (J4) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor 

temperature drops below –20°C and start back up once the temperature rises again.

 CAUTION

1) If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
2) Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
3) Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used. 

A humidifier might cause dew jumping from the indoor unit outlet vent.

4) Cutting jumper 4 (J4) sets the indoor fan tap to the highest position. Notify the user about this.

Gas 
stop valve

Valve cap

Hexagonal 
wrench

Close

Liquid 
stop valve

The selective connector for standby electricity saving in 
use (with standby electricity saving function turned OFF)

Push
here

1

2

3

Screwdriver

Power supply
terminal block

1

2

3

S90

PCB

S50

S20

S10

S1

J4

J8

J9

Cut J4 with nippers 
or a similar tools.

01_EN_3P203824-5A.fm  Page 9  Wednesday, September 26, 2007  3:33 PM

Summary of Contents for RXS20G2V1B

Page 1: ...a ol Italiano Portugues T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montageha...

Page 2: ...015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97...

Page 3: ...not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has leake...

Page 4: ...on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do no...

Page 5: ...part of the stop valve cover into the outdoor unit to install Tighten the screws Stop valve cover O D 9 5mm Gas pipe Liquid pipe O D 6 4mm 20g m 15m 20m Max allowable length Max allowable height Addit...

Page 6: ...nstallation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Draw ings 2 If drain work is necessary follow...

Page 7: ...the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cu...

Page 8: ...lve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and ma...

Page 9: ...s pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Thickness 0 8mm Thickness 10mm Min Filling a cylinder with an attached siphon Stand the cylinder upr...

Page 10: ...if has not been turned OFF 2 Remove the stop valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn ON the main power supply CAUTION 1 Before connecting or disconnectin...

Page 11: ...15 minutes CAUTION 1 When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock 2 After closing the liquid stop valve close the gas stop valve...

Page 12: ...r supply wiring Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be used due to unavoidable reasons be sure to observe the follow ing instruction Pl...

Page 13: ...dance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode If the syst...

Page 14: ...0711 HT 3P203824 5A M07B117 Two dimensional bar code is a code for manufacturing 00_CV_3P203824 5A fm Page 2 Thursday September 6 2007 10 20 AM...