Installation Guidelines

• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.

Precautions on Installation

• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare four sets of M8 or M10 

foundation bolts, nuts and washers each which are available on the market.)

• It is best to screw in the foundation bolts until their length are 20mm from the foundation surface. 

Outdoor Unit Installation

1.

Installing outdoor unit.

1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor Unit Installation Draw-

ings.”

2) If drain work is necessary, follow the procedures below.

2.

Drain work. (Heat pump-models.)   

1) Use drain plug for drainage.
2) If the drain port is covered by a mounting base or floor surface, place addi-

tional foot bases of at least 30mm in height under the outdoor unit’s feet.

3) In cold areas, do not use a drain hose with the outdoor unit.  

(Otherwise, drain water may freeze, impairing heating performance.)

More than 50

More than 100

Side view

1200
or less

More than 50

More than 50

Top view

More 
than 100

Top view

Unit: mm

More than 150

More than 300

More than 50

Wall facing one side

Walls facing two sides

Walls facing three sides

More than 150

20

Drain-water hole

Bottom frame

Drain plug

Hose (available commercially,
inner dia. 16mm)

01_EN_3P203824-5A.fm  Page 4  Wednesday, September 26, 2007  3:33 PM

Summary of Contents for RXS20G2V1B

Page 1: ...a ol Italiano Portugues T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montageha...

Page 2: ...015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97...

Page 3: ...not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has leake...

Page 4: ...on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do no...

Page 5: ...part of the stop valve cover into the outdoor unit to install Tighten the screws Stop valve cover O D 9 5mm Gas pipe Liquid pipe O D 6 4mm 20g m 15m 20m Max allowable length Max allowable height Addit...

Page 6: ...nstallation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Draw ings 2 If drain work is necessary follow...

Page 7: ...the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cu...

Page 8: ...lve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and ma...

Page 9: ...s pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Thickness 0 8mm Thickness 10mm Min Filling a cylinder with an attached siphon Stand the cylinder upr...

Page 10: ...if has not been turned OFF 2 Remove the stop valve cover 3 Disconnect the selective connector for standby electricity saving 4 Turn ON the main power supply CAUTION 1 Before connecting or disconnectin...

Page 11: ...15 minutes CAUTION 1 When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock 2 After closing the liquid stop valve close the gas stop valve...

Page 12: ...r supply wiring Use a round crimp style terminal for connection to the power supply terminal board In case it cannot be used due to unavoidable reasons be sure to observe the follow ing instruction Pl...

Page 13: ...dance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode If the syst...

Page 14: ...0711 HT 3P203824 5A M07B117 Two dimensional bar code is a code for manufacturing 00_CV_3P203824 5A fm Page 2 Thursday September 6 2007 10 20 AM...

Reviews: