![background image](http://html1.mh-extra.com/html/daikin/rxq35amv1b/rxq35amv1b_installers-reference-manual_4205177048.webp)
9
|
Electrical installation
Installer reference guide
48
RXQ-A_ARXQ-A
R32 split series
4P513661-11P – 2021.11
DC+
DC-
h
g
f
e
b
a
c
d
a
DB1 - diode bridge
b
Multimeter (DC voltage range)
c
S80 – reversing solenoid valve lead wire
d
S71 – fan motor lead wire
e
S30 – compressor motor lead wire
f
S40 – thermal overload relay lead wire
g
S20 – electronic expansion valve lead wire
h
S90 – thermistor lead wire
9.1.2 Guidelines when connecting the electrical wiring
Keep the following in mind:
▪
If stranded conductor wires are used, install a round crimp-style terminal on the
end of the wire. Place the round crimp-style terminal on the wire up to the
covered part and fasten the terminal with the appropriate tool.
b
a
a
Stranded conductor wire
b
Round crimp-style terminal
▪
Use the following methods for installing wires:
Wire type
Installation method
Single-core wire
c b
c
a
a
A
AA´
A´
a
Curled single-core wire
b
Screw
c
Flat washer
Stranded conductor wire
with round crimp-style
terminal
c b
b
a
c
a
B
B
a
Terminal
b
Screw
c
Flat washer
Allowed