2 Specific installer safety instructions

Installation manual

4

(A)RXP20~35M5V1B

R32 split series

3P650253-6E – 2022.04

CAUTION

For walls containing a metal frame or a metal board, use a
wall  embedded  pipe  and  wall  cover  in  the  feed-through
hole to prevent possible heat, electrical shock, or fire.

WARNING

Make  sure  installation,  testing  and  applied  materials
comply  with  applicable  legislation  (on  top  of  the
instructions described in the Daikin documentation).

CAUTION

▪ Check  if  the  installation  location  can  support  the  unit's

weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.

▪ Provide sufficient service space.

▪ Do  NOT  install  the  unit  so  that  it  is  in  contact  with  a

ceiling or a wall, as this may cause vibrations.

WARNING

Improper  installation  or  attachment  of  equipment  or
accessories  could  result  in  electrical  shock,  short-circuit,
leaks,  fire  or  other  damage  to  the  equipment.  ONLY  use
accessories,  optional  equipment  and  spare  parts  made  or
approved by Daikin.

Piping installation (see 

"5 Piping installation"

 [

4

 8])

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

DANGER: RISK OF BURNING/SCALDING

NOTICE

▪ Use the flare nut fixed to the unit.

▪ To prevent gas leakage, apply refrigeration oil ONLY to

the  inside  of  the  flare.  Use  refrigeration  oil  for  R32
(FW68DA).

▪ Do NOT reuse joints.

NOTICE

▪ Do NOT use mineral oil on flared part.

▪ NEVER  install  a  drier  to  this  R32  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

Electrical installation (see 

"7 Electrical installation"

 [

4

 10])

DANGER: RISK OF ELECTROCUTION

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

WARNING

Provide adequate measures to prevent that the unit can be
used  as  a  shelter  by  small  animals.  Small  animals  that
make contact with electrical parts can cause malfunctions,
smoke or fire.

INFORMATION

The sound pressure level is less than 70 dBA.

Summary of Contents for RXP20M5V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXP20M5V1B RXP25M5V1B RXP35M5V1B ARXP20M5V1B ARXP25M5V1B ARXP35M5V1B...

Page 2: ...nka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem un citi...

Page 3: ...un 12 10 4 Starting up the outdoor unit 12 11 Disposal 12 11 1 Overview Disposal 12 11 2 To pump down 12 11 3 To start and stop forced cooling 13 11 3 1 To start and stop forced cooling using the indo...

Page 4: ...NGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation...

Page 5: ...r intrinsically safe Prior to and during work the area MUST be checked with an appropriate refrigerant detector capable of detecting R32 refrigerant to ensure a work environment free of refrigerant WA...

Page 6: ...ed to wind It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet 4 1 2 A...

Page 7: ...lable options contact your dealer 1 Use a drain plug for drainage 2 Use a 16 mm hose field supply b c d a a Drain port b Bottom frame c Drain plug accessory d Hose field supply NOTICE Provide at least...

Page 8: ...Make sure the outdoor and indoor unit are mounted Typical workflow Connecting the refrigerant piping involves Connecting the refrigerant piping to the indoor unit Connecting the refrigerant piping to...

Page 9: ...e charging additional refrigerant make sure the outdoor unit s external refrigerant piping is checked leak test vacuum drying INFORMATION Depending on the units and or the installation conditions it m...

Page 10: ...um drying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 6 6 To fix the fluorinated greenhouse gases label 1 Fill in the la...

Page 11: ...or unit installation 1 Insulate and fix the refrigerant piping and cables as follows g b a f e c d a Gas pipe b Gas pipe insulation c Interconnection cable d Field wiring if applicable e Liquid pipe f...

Page 12: ...turned OFF INFORMATION Even if the unit is turned OFF it consumes electricity When the power turns back on after a power break the previously selected mode will be resumed 10 4 Starting up the outdoor...

Page 13: ...nt on the indoor unit Method 2 Using the indoor unit user interface 11 3 1 To start and stop forced cooling using the indoor unit ON OFF switch 1 Press the ON OFF switch for at least 5 seconds Result...

Page 14: ...HN HR MR _A MR _B S U V W X A K R_ NE Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground...

Page 15: ...0253 6E 2022 04 Symbol Meaning V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve co...

Page 16: ...f c a b d j l k g3 i e RXP20M RXP25M RXP35M ARXP20M ARXP25M ARXP35M h a Liquid field piping h Heat exchanger thermistor b Gas field piping i 4 way valve ON heating c Liquid stop valve j Muffler d Gas...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P650253 6E 2022 04 Copyright 20...

Reviews: