6 Charging refrigerant

Installation manual

9

(A)RXP20~35M5V1B
R32 split series
3P650253-6E – 2022.04

NOTICE

ALWAYS  use  a  recommended  bubble  test  solution  from
your wholesaler.

NEVER use soap water:

▪ Soap  water  may  cause  cracking  of  components,  such

as flare nuts or stop valve caps.

▪ Soap  water  may  contain  salt,  which  absorbs  moisture

that will freeze when the piping gets cold.

▪ Soap  water  contains  ammonia  which  may  lead  to

corrosion  of  flared  joints  (between  the  brass  flare  nut
and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

5.3.2

To perform vacuum drying

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

Increases

There is moisture in the
system. Go to the next step.

3

Vacuum the system for at least 2 hours to a manifold pressure
of −0.1 MPa (−1 bar).

4

After  turning  the  pump  OFF,  check  the  pressure  for  at  least
1 hour.

5

If  you  do  NOT  reach  the  target  vacuum  or  CANNOT  maintain
the vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

6

Charging refrigerant

6.1

About charging refrigerant

The  outdoor  unit  is  factory  charged  with  refrigerant,  but  in  some
cases the following might be necessary:

What

When

Charging additional refrigerant

When the total liquid piping
length is more than specified
(see later).

Completely recharging refrigerant

Example: 

▪ When relocating the system.

▪ After a leak.

Charging additional refrigerant

Before  charging  additional  refrigerant,  make  sure  the  outdoor  unit's

external

 refrigerant piping is checked (leak test, vacuum drying).

INFORMATION

Depending on the units and/or the installation conditions, it
might be necessary to connect electrical wiring before you
can charge refrigerant.

Typical  workflow  –  Charging  additional  refrigerant  typically  consists
of the following stages:

1 Determining if and how much you have to charge additionally.

2 If necessary, charging additional refrigerant.

3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

Completely recharging refrigerant

Before completely recharging refrigerant, make sure the following is
done:

1 All refrigerant is recovered from the system.

2 The outdoor unit's 

external

 refrigerant piping is checked (leak

test, vacuum drying).

3 Vacuum drying on the outdoor unit's 

internal

 refrigerant piping is

performed.

NOTICE

Before  completely  recharging,  perform  vacuum  drying  on
the outdoor unit's 

internal

 refrigerant piping as well.

Typical  workflow  –  Completely  recharging  refrigerant  typically
consists of the following stages:

1 Determining how much refrigerant to charge.

2 Charging refrigerant.

3 Filling in the fluorinated greenhouse gases label, and fixing it to

the inside of the outdoor unit.

6.2

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

Periodical  inspections  for  refrigerant  leaks  may  be  required
depending  on  the  applicable  legislation.  Contact  your  installer  for
more information.

WARNING: FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

▪ The  refrigerant  inside  the  unit  is  mildly  flammable,  but

normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater,  or  a  cooker,  this  may  result  in  fire,  or  the
formation of a harmful gas.

▪ Turn  OFF  any  combustible  heating  devices,  ventilate

the room, and contact the dealer where you purchased
the unit.

▪ Do  NOT  use  the  unit  until  a  service  person  confirms

that the part from which the refrigerant leaked has been
repaired.

Summary of Contents for RXP20M5V1B

Page 1: ...Installation manual R32 split series English Installation manual R32 split series RXP20M5V1B RXP25M5V1B RXP35M5V1B ARXP20M5V1B ARXP25M5V1B ARXP35M5V1B...

Page 2: ...nka emiau nurodytus standartus ir arba kitus norminius dokumentus su s lyga kad yra naudojami pagal m s nurodymus tad ja lietoti atbilsto i ra ot ja nor d jumiem atbilst sekojo iem standartiem un citi...

Page 3: ...un 12 10 4 Starting up the outdoor unit 12 11 Disposal 12 11 1 Overview Disposal 12 11 2 To pump down 12 11 3 To start and stop forced cooling 13 11 3 1 To start and stop forced cooling using the indo...

Page 4: ...NGER RISK OF ELECTROCUTION WARNING ALWAYS use multicore cable for power supply cables WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the applicable legislation...

Page 5: ...r intrinsically safe Prior to and during work the area MUST be checked with an appropriate refrigerant detector capable of detecting R32 refrigerant to ensure a work environment free of refrigerant WA...

Page 6: ...ed to wind It is recommended to install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet 4 1 2 A...

Page 7: ...lable options contact your dealer 1 Use a drain plug for drainage 2 Use a 16 mm hose field supply b c d a a Drain port b Bottom frame c Drain plug accessory d Hose field supply NOTICE Provide at least...

Page 8: ...Make sure the outdoor and indoor unit are mounted Typical workflow Connecting the refrigerant piping involves Connecting the refrigerant piping to the indoor unit Connecting the refrigerant piping to...

Page 9: ...e charging additional refrigerant make sure the outdoor unit s external refrigerant piping is checked leak test vacuum drying INFORMATION Depending on the units and or the installation conditions it m...

Page 10: ...um drying 1 Connect the refrigerant cylinder to the service port 2 Charge the additional refrigerant amount 3 Open the gas stop valve 6 6 To fix the fluorinated greenhouse gases label 1 Fill in the la...

Page 11: ...or unit installation 1 Insulate and fix the refrigerant piping and cables as follows g b a f e c d a Gas pipe b Gas pipe insulation c Interconnection cable d Field wiring if applicable e Liquid pipe f...

Page 12: ...turned OFF INFORMATION Even if the unit is turned OFF it consumes electricity When the power turns back on after a power break the previously selected mode will be resumed 10 4 Starting up the outdoor...

Page 13: ...nt on the indoor unit Method 2 Using the indoor unit user interface 11 3 1 To start and stop forced cooling using the indoor unit ON OFF switch 1 Press the ON OFF switch for at least 5 seconds Result...

Page 14: ...HN HR MR _A MR _B S U V W X A K R_ NE Connection connector D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground...

Page 15: ...0253 6E 2022 04 Symbol Meaning V R Diode bridge Insulated gate bipolar transistor IGBT power module WRC Wireless remote controller X Terminal X M Terminal strip block Y E Electronic expansion valve co...

Page 16: ...f c a b d j l k g3 i e RXP20M RXP25M RXP35M ARXP20M ARXP25M ARXP35M h a Liquid field piping h Heat exchanger thermistor b Gas field piping i 4 way valve ON heating c Liquid stop valve j Muffler d Gas...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P650253 6E 2022 04 Copyright 20...

Reviews: