Outdoor Unit Installation

3.

Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing 

downward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

 WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Never install a drier to this R32 unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.
• Protect or enclose refrigerant tubing to avoid mechanical damage.

4.

Refrigerant piping

 CAUTION

• Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
• To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R410A or R32.)
• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.
• After the piping work is finished (after checking for gas leaks), open the stop valves or the compressor might break down.

Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque wrenches. 

A

A

(Cut exactly at 
right angles.)

Remove burrs.

Set exactly at the position shown below.

Flaring

Die

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

0-0.5mm

Clutch-type

Flare tool for R410A/R32

1.0-1.5mm

Clutch-type (Ridgid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

Torque wrench

Piping union

Flare nut

Flare nut

Spanner

Flare nut tightening torque

Liquid side

1/4 inch

14.2-17.2N • m

(144-175kgf • cm)

Gas side

1/2 inch

49.5-60.3N • m

(505-615kgf • cm)

Valve cap tightening torque

Liquid side

1/4 inch

21.6-27.4N • m

(220-280kgf • cm)

Gas side

1/2 inch

48.1-59.7N • m

(490-610kgf • cm)

Service port cap tightening torque

10.8-14.7N • m (110-150kgf • cm)

Do not apply refrigeration 
oil to the outer surface.

Apply refrigeration oil to 
the inner surface of the 
flare.

Do not apply refrigeration oil to 
the flare nut to avoid tightening 
with excessive torque.

[Apply oil]

[Tighten]

3PEN386698-4L.book  Page 6  Thursday, April 27, 2017  8:43 AM

Summary of Contents for RXM42M3V1B9

Page 1: ...INSTALLATION MANUAL R32 Split Series Models RXM42M3V1B9 RXM50M3V1B9 RXM60M3V1B9 ARXM50M3V1B9 3PEN386698 4L book Page 1 Thursday April 27 2017 8 43 AM...

Page 2: ...ente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de...

Page 3: ...ivt intygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkom...

Page 4: ...astunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas s...

Page 5: ...nections or wires Improper connections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units pos...

Page 6: ...erant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended to be used by expert or trained users in shops in light in...

Page 7: ...ages and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten...

Page 8: ...t Failure to do so may result in reduced performance The suggested shortest pipe length is 1 5m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur dep...

Page 9: ...Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary...

Page 10: ...mage to the flare nuts and gas leakage After the piping work is finished after checking for gas leaks open the stop valves or the compressor might break down Align the centres of both flares and tight...

Page 11: ...oint may exists Check all pipe joints and retighten nuts as needed then repeat steps 2 through 4 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service...

Page 12: ...product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type GWP value factory refrigerant charge of the product see unit name plate additional refrigerant amo...

Page 13: ...liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes NOTE Piping and other pressure containing parts shall comply with the...

Page 14: ...unit ON OFF switch for at least 5 seconds The operation will start Forced cooling operation will stop automatically after around 15 minutes To stop the operation press the indoor unit ON OFF switch Us...

Page 15: ...ses may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where faci...

Page 16: ...oor unit Doing so may cause electric shock or fire Do not turn ON the safety breaker until all work is completed 1 Strip the insulation from the wire 20mm 2 Connect the inter unit wire between the ind...

Page 17: ...ace with a wire stop 1 Safe handling of high voltage part Turn the circuit breaker off and wait for 10 minutes before servicing 1 1 To prevent electrical shock Check the voltage of max DC50V between D...

Page 18: ...OR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT L...

Page 19: ...e connector for standby electricity saving 5 Turn on the main power supply CAUTION Before connecting or disconnecting the selective connector for standby electricity saving make sure that the main pow...

Page 20: ...the circuit breaker is opened again 2 Fault diagnosis by LED on outdoor unit PCB NOTE Error detection should be done using the remote control fault diagnosis 3 Test items Diagnosis LED is flashing No...

Page 21: ...3PEN386698 4L book Page 1 Thursday April 27 2017 8 43 AM...

Page 22: ...3PEN386698 4L book Page 2 Thursday April 27 2017 8 43 AM...

Page 23: ...3PEN386698 4L book Page 3 Thursday April 27 2017 8 43 AM...

Page 24: ...3P386698 4L 2017 04 Copyright 2017 Daikin 3PEN386698 4L book Page 1 Thursday April 27 2017 8 43 AM...

Reviews: