background image

8

English

Outdoor Unit Installation

6.

Charging refrigerant

Check the type of refrigerant to be used (on the machine nameplate).

Fill from the gas pipe in liquid form.

1-1. Charging additional refrigerant

• If the total length of refrigerant piping exceeds 10m, add refrigerant.
• Subtract 10m from the overall length and write the result in column.

1-2. Completely recharging refrigerant

The total amount that must be added is the amount listed on the machine nameplate and the amount of the additional refrigerant.

Precautions for compressor

WARNING

Electric shock hazard 

• Use this compressor on a grounded system only.
• Turn power OFF before servicing.
• Replace terminal cover before applying power.

Injury hazard

• Wear protective goggles.

Explosion or fire hazard

• Use tubing cutter to remove compressor.
• Do NOT use torch. System contains refrigerant under pressure.
• Do NOT drive under air or vacuum condition.
• Use only approved refrigerants and lubricants.

Burn hazard 

• Do NOT touch with bare hands during or immediately following operation.

20g x

m=

g

6

5

Please fill in with indelible ink, 

  the factory refrigerant charge of the product, 

tCO

2

eq calculation according to the formula (rounded up 

to 2 decimal places)

  the additional refrigerant amount charged in the field and

  the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Important information regarding the refrigerant used

This product contains fluorinated greenhouse gases. 
Do not vent gases into the atmosphere.

Refrigerant type:
GWP

 value:

factory refrigerant charge of the 
product: 
see unit name plate 

additional refrigerant amount 
charged in the field 

total refrigerant charge 

greenhouse gas emissions

 of the 

total refrigerant charge expressed 
as tonnes CO

2

-equivalent 

outdoor unit

refrigerant cylinder and manifold 
for charging

The filled out label must be adhered in the 
proximity of the product charging port 
(e.g. onto the inside of the stop valve cover).

GWP = global warming potential 

(1)

(1)

Contains fluorinated greenhouse gases

2

1

1

1

2

2

kg

tCO

2

eq

1000

GWP × kg

=

=

+

kg

=

kg

=

GWP: 675

675

R32

R32

NOTE

National implementation of EU regulation on certain fluorinated greenhouse gases may require to provide the appropriate official national language on the unit. 
Therefore an additional multilingual fluorinated greenhouse gases label is supplied with the unit. Sticking instructions are illustrated on the backside of that label.

NOTICE

In Europe, the 

greenhouse gas emissions 

of the total refrigerant charge in the system (expressed as tonnes CO

-equivalent) 

is  used  to  determine  the  maintenance intervals. Follow the applicable legislation.

Formula to calculate the greenhouse gas emissions:

GWP value of the refrigerant × Total refrigerant charge [in kg] / 1000

Use the GWP value mentioned on the refrigerant charge label. This GWP value is based on the 4th IPCC 

Assessment 

Report.  The  GWP  value  mentioned  in  the manual might be outdated (i.e., based on the 3rd IPCC Assessment Report).

3PEN386698-4L.book  Page 8  Thursday, April 27, 2017  8:43 AM

Summary of Contents for RXM42M3V1B9

Page 1: ...INSTALLATION MANUAL R32 Split Series Models RXM42M3V1B9 RXM50M3V1B9 RXM60M3V1B9 ARXM50M3V1B9 3PEN386698 4L book Page 1 Thursday April 27 2017 8 43 AM...

Page 2: ...ente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de...

Page 3: ...ivt intygats av E Fastsatt modul F vilket ocks framg r av Certifikat G Riskkategori H Se ven n sta sida 12 som det fremkommer i A og gjennom positiv bed mmelse av B if lge Sertifikat C som det fremkom...

Page 4: ...astunud temperatuur M C Jahutusaine N Surve turvaseadme seadistus P bar Tootmisnumber ja tootmisaasta vaadake mudeli andmeplaati 21 PS K bar TS TSmin L C TSmax PS M C N P bar 22 Maksimalus leistinas s...

Page 5: ...nections or wires Improper connections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units pos...

Page 6: ...erant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended to be used by expert or trained users in shops in light in...

Page 7: ...ages and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten...

Page 8: ...t Failure to do so may result in reduced performance The suggested shortest pipe length is 1 5m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur dep...

Page 9: ...Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary...

Page 10: ...mage to the flare nuts and gas leakage After the piping work is finished after checking for gas leaks open the stop valves or the compressor might break down Align the centres of both flares and tight...

Page 11: ...oint may exists Check all pipe joints and retighten nuts as needed then repeat steps 2 through 4 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service...

Page 12: ...product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type GWP value factory refrigerant charge of the product see unit name plate additional refrigerant amo...

Page 13: ...liquid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes NOTE Piping and other pressure containing parts shall comply with the...

Page 14: ...unit ON OFF switch for at least 5 seconds The operation will start Forced cooling operation will stop automatically after around 15 minutes To stop the operation press the indoor unit ON OFF switch Us...

Page 15: ...ses may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where faci...

Page 16: ...oor unit Doing so may cause electric shock or fire Do not turn ON the safety breaker until all work is completed 1 Strip the insulation from the wire 20mm 2 Connect the inter unit wire between the ind...

Page 17: ...ace with a wire stop 1 Safe handling of high voltage part Turn the circuit breaker off and wait for 10 minutes before servicing 1 1 To prevent electrical shock Check the voltage of max DC50V between D...

Page 18: ...OR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOT L...

Page 19: ...e connector for standby electricity saving 5 Turn on the main power supply CAUTION Before connecting or disconnecting the selective connector for standby electricity saving make sure that the main pow...

Page 20: ...the circuit breaker is opened again 2 Fault diagnosis by LED on outdoor unit PCB NOTE Error detection should be done using the remote control fault diagnosis 3 Test items Diagnosis LED is flashing No...

Page 21: ...3PEN386698 4L book Page 1 Thursday April 27 2017 8 43 AM...

Page 22: ...3PEN386698 4L book Page 2 Thursday April 27 2017 8 43 AM...

Page 23: ...3PEN386698 4L book Page 3 Thursday April 27 2017 8 43 AM...

Page 24: ...3P386698 4L 2017 04 Copyright 2017 Daikin 3PEN386698 4L book Page 1 Thursday April 27 2017 8 43 AM...

Reviews: