•  When piping work is complete, it is necessary to perform a pressure test 

and evacuate system with a vacuum pump.

•  If using additional refrigerant, purge the air from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant.

• 

Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.

•  All refrigerant pipe joints should be tightened with a torque wrench to the 

specified tightening torque.

Compound 

pressure gauge

Pressure 
meter

High-pressure 

valve

Gauge 
manifold

Low-pressure 

valve

Charging 

hoses

Vacuum pump

Service port

Valve caps

Liquid 
stop 
valve

Gas stop valve

1) Pressurize the liquid pipe and gas pipe from the service ports of each stop valve to 604psi (4.17MPa) (do not pressurize 

more than 604psi (4.17MPa)) for 1 hour minimum, 24 hours recommended. If there is a pressure drop, check for leaks, 

make repairs and perform the pressure test again.

2) Connect the gauge manifold’s charging hose to the gas stop valve’s service port.
3) Fully open the low-pressure valve (Lo) on the gauge manifold and fully close the high-pressure valve (Hi).

 

(High-pressure valve will require no further operation.)

4) Evacuate system using vacuum pump to below 500 microns for 1 hour minimum.
5) Close the low-pressure valve (Lo) on the gauge manifold and stop vacuum pumping.

 

(Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing 

back.)*

1

6) 

Remove the valve caps from the liquid stop valve and gas stop valve.

7) To open the liquid stop valve, turn the rod of the valve 90° counter-clockwise using a hexagonal wrench.

 

Close it after 5 seconds, and check for gas leakage.

 

Using soapy water, check for gas leakage from the indoor unit’s flare and outdoor unit’s flare and valve rods.

 

After the check is complete, wipe all soapy water off.*

2

8) 

Disconnect the charging hoses from the service port for the gas stop valve, then fully open the liquid and gas stop valves. 

(Do not attempt to turn the valve rods further than they can go.)

9) Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench to the specified 

torques. 
Refer to 

“4. Refrigerant piping” on page 6 for details.

*

1

  If the compound pressure gauge pointer swings back, the refrigerant may have water content or there may be a loose 

pipe joint. 

Check all pipe joints and retighten nuts as needed, then repeat steps 3) through 5).

*

2

 

 Under no circumstances shall potential sources of ignition be used in the searching for or detection of 
refrigerant leaks.  

A halide torch (or any other detector using a naked flame) shall not be used.

 

Do not use substances containing chlorine and electronic leak detection for gas leak detection.

English

01_EN_3P686865-1.indd   8

2022/04/20   9:18:29

Summary of Contents for RXM18WVJU9

Page 1: ...l MODELS RXM18WVJU9 RXM24WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel dinstallation 00_CV_3P686865 1 ind...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...ensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage...

Page 4: ...Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6...

Page 5: ...CAUTION Keep the piping length between 10ft 3m and 98 1 2ft 30m Refrigerant piping must be protected from physical damage Install a plastic cover or equivalent If strong wind blows into the air disch...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is to prevent the flare nut from cracking as a...

Page 8: ...0mm Min O D 5 8 inch 15 9mm 1 15 16 inch 50mm or more 0 039 inch 1 0mm C1220T O I D 5 8 13 16 inch 16 20mm Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...r connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer...

Page 11: ...outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might c...

Page 12: ...alve and gas stop valve 2 Begin forced cooling operation 3 After 5 to 10 minutes close the liquid stop valve with a hexagonal wrench 4 After 2 to 3 minutes close the gas stop valve and stop forced coo...

Page 13: ...ks Incomplete cooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated Water leakage Draining line is properly installed Water leakage System i...

Page 14: ...The two dimensional bar code is a manufacturing code 3P686865 1 M21B537 2205 HT 00_CV_3P686865 1 indd 2 2022 02 10 16 42 47...

Reviews: