7

English

Outdoor Unit Installation

Cautions on pipe handling

•  Protect the open end of the pipe from dust and moisture.
•  All pipe bends should be as gentle as possible. Use a pipe bender for bending.

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:

•  Insulation material: Polyethylene foam 

Heat transfer rate: 0.041 to 0.052W/mK (0.024 to 0.030Btu/fth°F) (0.035 to 
0.045kcal/mh°C)

 

Be sure to use insulation that is designed for use with HVAC Systems.

• 

ACR Copper only.

•  Be sure to insulate both the gas and liquid piping and observe the insulation 

dimensions as below.

Be sure to 
place a cap.

Wall

Rain

If no flare cap 

is available, 

cover the flare 

mouth with tape 
to keep dirt and 
water out.

Piping size

Minimum bend radius

Piping thickness

Thermal insulation size

Thermal insulation 

thickness

Gas side

O.D. 1/2 inch

(12.7mm)

1-9/16 inch (40mm) 

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 9/16-5/8 inch

(14-16mm)

13/32 inch

(10mm) Min.

O.D. 5/8 inch

(15.9mm)

1-15/16 inch (50mm) 

or more

0.039 inch (1.0mm)

(C1220T-O)

I.D. 5/8-13/16 inch

(16-20mm)

Liquid side

O.D. 1/4 inch

(6.4mm)

1-3/16 inch (30mm) 

or more

0.031 inch (0.8mm)

(C1220T-O)

I.D. 5/16-13/32 inch

(8-10mm)

•  Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
• 

Using finishing tape, bundle and wrap the indoor unit piping and drain hose 

together so that the drain hose is below the other piping.

Finishing tape

Gas pipe

Drain hose

Liquid pipe

Liquid pipe 
insulation

Gas pipe 
insulation

5. 

Pressure test and evacuating system

WARNING

• 

Make sure that air or any matter other than refrigerant (R32) does not get into the refrigeration cycle.

•  If refrigerant gas leaks should occur, ventilate the room as soon and as much as possible.
•  R32, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• 

Use tools for R32 or R410A (such as the gauge manifold, charging hose, or vacuum pump adapter).

CAUTION

• 

It is highly recommended that you do not open/close the stop valves when the outdoor temperature is below −5°F (−21°C) 

as this may result in refrigerant leakage.

01_EN_3P686865-1.indd   7

2022/04/20   9:18:28

Summary of Contents for RXM18WVJU9

Page 1: ...l MODELS RXM18WVJU9 RXM24WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel dinstallation 00_CV_3P686865 1 ind...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...ensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage...

Page 4: ...Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6...

Page 5: ...CAUTION Keep the piping length between 10ft 3m and 98 1 2ft 30m Refrigerant piping must be protected from physical damage Install a plastic cover or equivalent If strong wind blows into the air disch...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is to prevent the flare nut from cracking as a...

Page 8: ...0mm Min O D 5 8 inch 15 9mm 1 15 16 inch 50mm or more 0 039 inch 1 0mm C1220T O I D 5 8 13 16 inch 16 20mm Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...r connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer...

Page 11: ...outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might c...

Page 12: ...alve and gas stop valve 2 Begin forced cooling operation 3 After 5 to 10 minutes close the liquid stop valve with a hexagonal wrench 4 After 2 to 3 minutes close the gas stop valve and stop forced coo...

Page 13: ...ks Incomplete cooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated Water leakage Draining line is properly installed Water leakage System i...

Page 14: ...The two dimensional bar code is a manufacturing code 3P686865 1 M21B537 2205 HT 00_CV_3P686865 1 indd 2 2022 02 10 16 42 47...

Reviews: