Installation Space Requirements

•  Position the unit on a horizontal surface. Any tilt in the unit should be 3° or less to the horizontal.
• 

Where a wall or other obstacle is in the path of the outdoor unit’s intake or exhaust airflow, follow the installation space requirements 

below.

• 

For any of the below installation patterns, the wall height on the outlet side should be 47-1/4 inch (1200mm) or less.

• 

Secure as much installation space around the unit as the location allows, as more space will result in more efficient operation.

Wall facing one side

Walls facing three sides

Walls facing two sides

More than 

3-15/16 (100)

More than 

13-3/4 (350)

More than 

1-15/16 (50)

Side view

Top view

Top view

unit: inch (mm)

More than 3-15/16 (100)

More than 13-3/4 (350)

47-1/4
(1200)

or less

More than

3-15/16 (100)

More than 

13-3/4 

(350)

More than 

1-15/16 (50)

More 
than 

3-15/16 
(100)

More than 

1-15/16 (50)

More than

13-3/4 (350)

When installed as in the figure on the left, it is recommended to either 

change the orientation of the outdoor unit outlet side or use the air direction 

adjustment grille (sold separately).

Outdoor Unit Installation

1. 

Installing the outdoor unit

•  When installing the outdoor unit, refer to “

Precautions for Selecting a Location” on page 3 and the “Outdoor Unit 

Installation Diagram” on page 4.

•  If drain work is necessary, follow the procedures below.

2. 

Drain work

CAUTION

• 

In cold areas, do not use a drain socket, drain caps (1, 2) and a drain hose with the outdoor unit. (Drain water may freeze, 
impairing heating performance.)

• 

If the drain port is covered by a mounting base or floor 
surface, place additional foot bases of at least 1-1/4 
inch (30mm) in height under the outdoor unit’s feet.

1) 

Attach 

B

 drain cap (1) and 

C

 drain cap (2).

2) 

Attach 

A

 drain socket.

•  When attaching 

A

 drain socket to the bottom 

frame, make sure to connect the drain hose to the 

drain socket first.

A  Drain socket

A  Drain socket

Bottom frame

Hose (available commercially, 

inner dia. 5/8” (16mm))

Bottom frame

Drain cap

Pinch the bottom 
frame in.

C  Drain cap (2)

C  Drain cap (2)

B

 Drain cap (1)

Air outlet side

01_EN_3P686865-1.indd   5

2022/04/20   9:18:27

Summary of Contents for RXM18WVJU9

Page 1: ...l MODELS RXM18WVJU9 RXM24WVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel dinstallation 00_CV_3P686865 1 ind...

Page 2: ...lly in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can ca...

Page 3: ...ensation Be careful when transporting the product Do not turn off the power immediately after stopping operation Always wait for at least 5 minutes before turning off the power Otherwise water leakage...

Page 4: ...Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away from moisture 9 A location where flammable gas does not leak Position at least 6...

Page 5: ...CAUTION Keep the piping length between 10ft 3m and 98 1 2ft 30m Refrigerant piping must be protected from physical damage Install a plastic cover or equivalent If strong wind blows into the air disch...

Page 6: ...t is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit Whe...

Page 7: ...020 inch 0 0 5mm 0 039 0 059 inch 1 0 1 5mm 0 059 0 079 inch 1 5 2 0mm Flaring 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is to prevent the flare nut from cracking as a...

Page 8: ...0mm Min O D 5 8 inch 15 9mm 1 15 16 inch 50mm or more 0 039 inch 1 0mm C1220T O I D 5 8 13 16 inch 16 20mm Liquid side O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O I D 5 16 13...

Page 9: ...ifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from the liquid stop valve a...

Page 10: ...r connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place Round crimp style terminal Stranded wire Screw Flat washer...

Page 11: ...outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might c...

Page 12: ...alve and gas stop valve 2 Begin forced cooling operation 3 After 5 to 10 minutes close the liquid stop valve with a hexagonal wrench 4 After 2 to 3 minutes close the gas stop valve and stop forced coo...

Page 13: ...ks Incomplete cooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated Water leakage Draining line is properly installed Water leakage System i...

Page 14: ...The two dimensional bar code is a manufacturing code 3P686865 1 M21B537 2205 HT 00_CV_3P686865 1 indd 2 2022 02 10 16 42 47...

Reviews: