background image

4

English

Precautions on Installation

• 

Check the strength and level of the installation surface so that the unit does not cause 

any operating vibrations or noise after installation.

• 

Fix the unit in place securely using foundation bolts, as in the figure. (Prepare 4 
sets of 5/16 inch (M8) or 3/8 inch (M10) foundation bolts, nuts and washers; all sold 
separately.)

• 

It is best to screw in the foundation bolts until their ends are 3/4 inch (20mm) from the 

foundation surface.

3/4”

(20mm)

Outdoor Unit Installation Diagram

RXM18

RXM24

Max. allowable piping length

98-1/2ft (30m)

** Min. allowable piping length

10ft (3m)

Max. allowable piping height

82-1/64ft (25m)

* Additional refrigerant required for refrigerant 

pipe exceeding 49.2ft (15m) in length.

0.22oz/ft (20g/m)

Gas pipe

O.D. 1/2 inch 

(12.7mm)

O.D. 5/8 inch 

(15.9mm)

Liquid pipe

O.D. 1/4 inch (6.4mm)

Refrigerant piping must be kept to a minimum.
  *  Be sure to add the proper amount of additional refrigerant. 

Failure to do so may result in reduced performance. 

**  The suggested shortest pipe length is 10ft (3m), in order to avoid 

noise from the outdoor unit and vibration. 
(Mechanical noise and vibration may occur depending on how 

the unit is installed and the environment in which it is used.)

Allow 11-13/16 (300) 

of work space below 
the ceiling surface.

4-15/16 (125)

(From unit’

s side)

23-5/8 (600)

(Foot bolt-hole centers)

13-5/8

(346)

(Foot bolt-hole 

 

centers)

unit : inch (mm)

If there is a danger of the unit falling or overturning, 

fix the unit with foundation bolts, or with wire or 

other means.

 

CAUTION

Keep the piping length between 

10ft (3m) and 98-1/2ft (30m). 

Refrigerant piping must be protected from 
physical damage.
Install a plastic cover or equivalent.

If strong wind blows into the air 
discharge side from the front and 
there is a danger that the fan may be 
damaged, change the orientation of 
the air discharge side of the outdoor 
unit or use an air direction adjustment 

grille (sold separately).

Wrap the insulation pipe with 

finishing tape from bottom to top.

9-13/16 (250) from w

all

Allow space for piping and 
electrical servicing.

 

„

How to remove the stop 

valve cover

1)  Remove the screw on the 

stop valve cover.

2)  Slide the stop valve cover 

downward to remove it.

 

„

How to attach the stop valve 

cover

1)  Insert the upper part of the 

stop valve cover into the 
outdoor unit.

2)  Tighten the screw.

Stop valve cover

In sites with poor drainage, use 
block bases for the outdoor unit.  
Adjust foot height until the unit is 
level. Otherwise, water leakage or 
pooling of water may occur.

Refrigerant charge label

Please fill in with indelible ink, 

 

„

1

 the factory refrigerant charge of the product, 

 

„

2

 the additional refrigerant amount charged in the field and

 

„

1

 + 

2

 the total refrigerant charge 

on the refrigerant charge label supplied with the product.

Affix the refrigerant charge label near the manufacturer’s label 
after filling it out.

The filled out label must be adhered in the 
proximity of the product charging port.

1

1

2

2

lb

+ =

2

lb

=

1

lb

kg

kg

kg

=

4

5

3

2

1

1

   factory refrigerant charge of the 

product: see unit name plate 

2

   additional refrigerant amount 

charged in the field 

3

   total refrigerant charge 

4

   outdoor  unit

5

   refrigerant cylinder and manifold 

for charging

English

01_EN_3P628775-3.indd   4

2021/02/09   13:40:05

Summary of Contents for RXM18VVJU

Page 1: ...English Fran ais Espa ol MODELS RXM18VVJU RXM24VVJU DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R32 Split Series Installation manual Manuel dinstallation Manual de instalaci n Manuel dinstallation...

Page 2: ...A massive leak can lead to oxygen depletion especially in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wi...

Page 3: ...re to wear proper gloves Install drain piping to ensure proper drainage Improper drain piping may result in water leakage and property damage Insulate piping to prevent condensation Be careful when tr...

Page 4: ...one containing sulfate gas corrosion may shorten the life of the air conditioner 8 Since water will flow from the drain of the outdoor unit do not place anything under the unit which must be kept away...

Page 5: ...or other means CAUTION Keep the piping length between 10ft 3m and 98 1 2ft 30m Refrigerant piping must be protected from physical damage Install a plastic cover or equivalent If strong wind blows into...

Page 6: ...orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately Outdoor Unit Installation 1 Installing the outdoor unit When installing the outdoor unit refer t...

Page 7: ...the flare nut is fitted When flaring do not over tighten and crack Check Set exactly at the position shown below A Die Flare tool for R32 or R410A Conventional flare tool Clutch type Clutch type Rigid...

Page 8: ...e to keep dirt and water out Piping size Minimum bend radius Piping thickness Thermal insulation size Thermal insulation thickness Gas side O D 1 2 inch 12 7mm 1 9 16 inch 40mm or more 0 031 inch 0 8m...

Page 9: ...ve Lo on the gauge manifold and stop vacuum pumping Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing back 1 6 Remove the valve caps from t...

Page 10: ...ust be used make sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in pl...

Page 11: ...and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation fr...

Page 12: ...as stop valve 2 Begin forced cooling operation 3 After 5 to 10 minutes close the liquid stop valve with a hexagonal wrench 4 After 2 to 3 minutes close the gas stop valve and stop forced cooling opera...

Page 13: ...vibration noise No refrigerant gas leaks Incomplete cooling heating function Refrigerant gas and liquid pipes and indoor drain hose extension are thermally insulated Water leakage Draining line is pro...

Page 14: ...The two dimensional bar code is a manufacturing code 3P628775 3 M20B075 2102 HT...

Reviews: