ELECTRICAL DATA
RXH20CVMB
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTXS20CVMB
RXH20CVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
14.0
15
42
2.81
25
0.35
18
0.20
3D044323
RXH25CVMB
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTXS25CVMB
RXH25CVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
14.0
15
47
3.21
25
0.35
18
0.20
3D044324
RXH35CVMB
Indoor unit
Outdoor unit
Power supply
Compressor
OFM
IFM
Hz-Volts
Voltage range
MCA
MFA
RHz
RLA
W
FLA
W
FLA
FTXS35CVMB
RXH35CVMB
50-230
MAX. 50Hz 253V
MIN. 50Hz 207V
14.0
15
70
4.41
25
0.35
18
0.20
3D044325
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency(Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select ’’Daikin
Documentation’’ and select ’’conditional connection’’, ’’the
requested product type’’ and ’’English’’ from the drop down
lists, click the search button.
Finally, click on the document title of your choice.
•
Pair Application, Inverter Controlled Unit
•
R-410A
•
RXH20-25-35CVMB
2
Specifications
1
2
4
•
Split - Sky Air
•
Outdoor Units