Installation

Outdoor unit installation drawings

Wrap the installation pipe with the finishing

tape from bottom to top

Model

20 / 25 / 35 class

Max. allowable length

Heat pump: 15m

Max. allowable height

15m

Additional refrigerant required

for refrigerant pipe exceeding

10 m in length.

20 g/m

Gas pipe

O.D. 9.5 mm

Liquid pipe

O.D. 6.4 mm

* Be sure to add the proper amount of additional refrigerant.

Failure to do so may result in reduced performance.

In sites with poor drainage, use block bases for

outdoor unit. Adjust foot height until the unit is

leveled. Otherwise, water leakage or pooling of

water may occur.

Where there is a danger of the unit falling, use foot

bolts, or wires.

Allow space for piping and electrical

servicing.

Service lid

How to remove the service lid.

+

This service lid is an open/close type.

+

Slide the lid downward to remove it.

How to attach the service lid.

+

Insert the upper part of the service lid into the

outdoor unit to install.

+

Tighten the screws.

Foot bolt-hole

centres

Foot bolt-hole

centres

From unit’s side

470

115

288

250 mm from wall

RXH20,25,35C

Pair Application, Inverter Controlled Unit

R-410A

RXH20-25-35CVMB

1

11

15

Split - Sky Air

Outdoor Units

Summary of Contents for RXH20CVMB

Page 1: ...RXH C Pair Application Inverter Controlled Unit technical data Split Sky Air air conditioning systems...

Page 2: ...products and services and to assist in maintaining and improving the quality of the environment Daikin Europe N V is approved by LRQA for its Quality Management System in accordance with the ISO9001...

Page 3: ...sional drawings 7 5 Operation range 8 6 Piping diagrams 9 7 Wiring diagrams 10 8 Sound level 11 Sound level data Sound pressure spectrum 9 Accessories 13 Standard accessories Optional accessories 10 C...

Page 4: ...e mounted easily on a roof or terrace or simply placed against an outside wall They are fitted with a swing compressor renowned for its low noise and high energy efficiency Pair Application Inverter C...

Page 5: ...ally sealed swing type Model 1YC23NXD A Motor output 600 Oil type FVC50K Oil charge volume 0 375 PIPING CONNECTIONS liquid mm 6 4 gas mm 9 5 drain mm 18 0 INSULATION MATERIAL Heat insulation Both liqu...

Page 6: ...D044325 SYMBOLS MCA Min Circuit Amps A MFA Max Fuse Amps A RHz Rated operating frequency Hz RLA Rated Load Amps A OFM Outdoor Fan Motor IFM Indoor Fan Motor FLA Full Load Amps W Rated motor output W N...

Page 7: ...66 2 08 1 76 0 67 2 02 1 72 0 68 1 94 1 65 0 74 18 0 25 2 43 2 06 0 54 2 35 2 00 0 61 2 27 1 93 0 67 2 23 1 89 0 68 2 17 1 85 0 69 2 08 1 77 0 75 19 0 27 2 52 2 14 0 55 2 43 2 06 0 61 2 35 1 99 0 67 2...

Page 8: ...87 3 03 0 94 3 62 1 02 4 01 1 07 20 0 2 03 0 84 2 52 0 91 3 01 0 98 3 60 1 06 3 99 1 11 21 0 2 02 0 86 2 51 0 93 3 00 0 99 3 59 1 07 3 98 1 13 22 0 2 01 0 88 2 50 0 95 2 99 1 01 3 58 1 09 3 98 1 15 2...

Page 9: ...hose for connection 4 x holes for anchor bolts M8 or M10 Name plate Terminal strip with earth terminal Wiring inlet Gas stop valve J B CuT Liquid stop valve J A CuT Service port Outdoor air thermistor...

Page 10: ...WB Notes The graph is based on the following conditions 1 Equivalent piping length 7 5 m 2 Level difference 0 m 3 Air flow rate high Indoor temp CDB 10 CDB Outdoor temp CWB Cooling Heating Pair Applic...

Page 11: ...s stop valve Muffler with filter Muffler with filter Muffler 3D042769A RXH35C Outdoor temperature thermistor Heat exchanger Propeller fan Liquid stop valve Field piping Field piping Accumulator Compre...

Page 12: ...d circuit board MRCW MRL MRM10 MRM20 Magnetic relay N Neutral Q1L Overload protector R1T R2T R3T Thermistor S20 S75 S80 S90 Connector SA1 Surge arrester Z1C Z2C Z3C Ferrite core IC11 Solid state relay...

Page 13: ...r level cooling heating 230V 50Hz Measuring location Cooling heating H L RXH20C 46 47 61 62 RXH25C 46 47 61 62 RXH35C 48 48 63 63 This information was not available at the time of publication Pair App...

Page 14: ...and sound pressure level Octave band sound pressure level approximate threshold hearing for continuous noise approximate threshold hearing for continuous noise 3D044291 3D044291 Octave band center fre...

Page 15: ...upplied with the outdoor unit 1 9 2 Optional accessories RXH C RXH20CVMB RXH25CVMB RXH35CVMB Air direction adjustment grille KPW937A4 Installation manual Pair Application Inverter Controlled Unit R 41...

Page 16: ...10 Center of gravity RXH20 25C 4D044156 RXH35C 4D044157 Pair Application Inverter Controlled Unit R 410A RXH20 25 35CVMB 1 10 14 Split Sky Air Outdoor Units...

Page 17: ...es for outdoor unit Adjust foot height until the unit is leveled Otherwise water leakage or pooling of water may occur Where there is a danger of the unit falling use foot bolts or wires Allow space f...

Reviews: