3 About the box

Installation manual

5

RXF20~42C5V1B
Daikin room air conditioner
3P519299-10S – 2020.08

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

WARNING

If the supply cord is damaged, it MUST be replaced by the
manufacturer,  its  service  agent  or  similarly  qualified
persons in order to avoid a hazard.

WARNING

Do NOT connect the power supply to the indoor unit. This
could result in electrical shock or fire.

WARNING

▪ Do  NOT  use  locally  purchased  electrical  parts  inside

the product.

▪ Do  NOT  branch  the  power  supply  for  the  drain  pump,

etc.  from  the  terminal  block.  This  could  result  in
electrical shock or fire.

WARNING

Keep  the  interconnection  wiring  away  from  copper  pipes
without thermal insulation as such pipes will be very hot.

DANGER: RISK OF ELECTROCUTION

All  electrical  parts  (including  thermistors)  are  powered  by
the power supply. Do not touch them with bare hands.

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

Finishing indoor unit installation (see 

"8 Finishing the outdoor

unit installation" 

[

4

 11])

DANGER: RISK OF ELECTROCUTION

▪ Make sure that the system is earthed properly.

▪ Turn off the power supply before servicing.

▪ Install the switch box cover before turning on the power

supply.

Commissioning (see 

"9 Commissioning" 

[

4

 11])

DANGER: RISK OF ELECTROCUTION

DANGER: RISK OF BURNING/SCALDING

CAUTION

Do  NOT  perform  the  test  operation  while  working  on
the indoor units.

When performing the test operation, NOT only the outdoor
unit,  but  the  connected  indoor  unit  will  operate  as  well.
Working on an indoor unit while performing a test operation
is dangerous.

CAUTION

Do  NOT  insert  fingers,  rods  or  other  objects  into  the  air
inlet  or  outlet.  Do  NOT  remove  the  fan  guard.  When  the
fan is rotating at high speed, it will cause injury.

3

About the box

3.1

Outdoor unit

3.1.1

To unpack the outdoor unit

1

2

WARNING

Make  sure  installation,  servicing,  maintenance  and  repair
comply  with  instructions  from  Daikin  and  with  applicable
legislation  (for  example  national  gas  regulation)  and  are
executed only by authorised persons.

3.1.2

To remove the accessories from the
outdoor unit

1

Lift the outdoor unit.

2

Remove the accessories at the bottom of the package.

b

e

c

d

a

Summary of Contents for RXF20C5V1B

Page 1: ...Installation manual Daikin room air conditioner English Installation manual Daikin room air conditioner RXF20C5V1B RXF25C5V1B RXF35C5V1B RXF42C5V1B...

Page 2: ...jem da se uporabljajo v skladu z na imi navodili on vastavuses j rgmis t e standardi te ga v i teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele atitinka emiau nurodyt...

Page 3: ...2 11 Disposal 12 12 Technical data 13 12 1 Wiring diagram 13 12 1 1 Unified wiring diagram legend 13 12 2 Piping diagram 15 12 2 1 Piping diagram Outdoor unit 15 1 About the documentation 1 1 About th...

Page 4: ...kage CAUTION Do NOT open the valves before flaring is complete This would cause refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT start the unit if it is vacuumed Charging refrigerant see 6 Char...

Page 5: ...al components before servicing The voltage MUST be less than 50 V DC before you can touch electrical components For the location of the terminals see the wiring diagram Finishing indoor unit installat...

Page 6: ...install the outdoor unit with the air inlet facing the wall and NOT directly exposed to the wind b a b c a Baffle plate b Prevailing wind direction c Air outlet 4 1 2 Additional installation site requ...

Page 7: ...bles and the outdoor unit to prevent the cables from scratching the paint field supply 4 Attach the ends of the cables 5 Tighten the cables 5 Piping installation 5 1 Preparing refrigerant piping 5 1 1...

Page 8: ...iping length Keep field piping as short as possible Piping protection Protect the field piping against physical damage 1 Connect the liquid refrigerant connection from the indoor unit to the liquid st...

Page 9: ...ch refrigerant to charge 2 Charging refrigerant 3 Filling in the fluorinated greenhouse gases label and fixing it to the inside of the outdoor unit 6 2 About the refrigerant This product contains fluo...

Page 10: ...e outdoor unit near the gas and liquid stop valves 7 Electrical installation DANGER RISK OF ELECTROCUTION WARNING All wiring MUST be performed by an authorised electrician and MUST comply with the app...

Page 11: ...NO damaged components or squeezed pipes on the inside of the indoor and outdoor units There are NO refrigerant leaks The refrigerant pipes gas and liquid are thermally insulated The correct pipe size...

Page 12: ...n the unit is not operating the LEDs on the PCB are turned off in order to save power Even when the LEDs are off the terminal block and the PCB may be powered 11 Disposal NOTICE Do NOT try to dismantl...

Page 13: ...D V D Diode DB Diode bridge DS DIP switch E H Heater FU F U for characteristics refer to PCB inside your unit Fuse FG Connector frame ground H Harness H P LED V L Pilot lamp light emitting diode Symbo...

Page 14: ...ion manual 14 RXF20 42C5V1B Daikin room air conditioner 3P519299 10S 2020 08 Symbol Meaning X M Terminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferri...

Page 15: ...T 9 5CuT M 6 4CuT 6 4CuT 4 8CuT 6 4CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 9 5CuT 7 9CuT Propeller fan 9 5CuT 9 5CuT HPS 7 0CuT g2 g1 f f c a b d j l k g3 i e RXF20C RXF25C RXF35C ARXF20C ARXF25C ARXF35C h 7...

Page 16: ...ield piping i 4 way valve ON heating c Liquid stop valve j Muffler d Gas stop valve k Compressor e Electronic expansion valve l Accumulator f Muffler with filter HPS High pressure switch automatic res...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P519299 10S 2020 08 Copyright 2...

Reviews: