6

5.

Purging air and checking gas leakage.

When piping work is completed, it is necessary to purge the air and check for gas leakage.

WARNING

1) Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.

2) When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.

3) R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.

4) Use a vacuum pump for R410A exclusively. Using the same vacuum pump for different refrigerants may damage the vacuum

pump or the unit.

If using additional refrigerant, perform air purging from the refrigerant pipes and

indoor unit using a vacuum pump, then charge additional refrigerant.

Use a hexagonal wrench (4mm) to operate the stop valve rod.

All refrigerant pipe joints should be tightened with a torque wrench at the specified

tightening torque.

*1. Pipe length vs. vacuum pump run time.

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.

Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve

s service port.

2) Fully open gauge manifold

s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).

(High-pressure valve subsequently requires no operation.)

3) Do vacuum pumping and make sure that the compound pressure gauge reads

0.1MPa (

76cmHg)*1.

4) Close gauge manifold

s low-pressure valve (Lo) and stop vacuum pump.

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2.

5) Remove caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve

s rod 90 degrees counterclockwise with a hexagonal wrench to open valve.

Close it after 5 seconds, and check for gas leakage.

Using soapy water, check for gas leakage from indoor unit

s flare and outdoor unit

s flare and valve rods.

After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve

s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

Pipe length

Up to 15 metres

Run time

Not less than 10 min.

Compound

pressure gauge

Pressure

meter

High-

pressure

valve

Low-pressure

valve

Vacuum pump Service port

Liquid

stop

valve

Valve caps

Gas stop valve

Charging

hoses

Gauge

manifold

Summary of Contents for RXB25B5V1

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RXB25B5V1 RXB35B5V1 English Installation manual R410A Split series Montaj K lavuzu T rk e R410A Split serisi...

Page 2: ...shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or...

Page 3: ...heard even if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air cond...

Page 4: ...onal refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shorte...

Page 5: ...oundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Draw ings 2 I...

Page 6: ...torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them f...

Page 7: ...hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequen...

Page 8: ...owing 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation material...

Page 9: ...force a test run to stop press the indoor unit operation stop button Using the main unit s remote controller 1 Press the operation stop button Operation will start 2 Press the temperature button and t...

Page 10: ...that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal board Observe the notes...

Page 11: ...G N R G Notes Refer to the nameplate of the unit for power requirements t i n u r o o d n i o T T I N U R O O D N I O T y l p p u s r e w o P Y L P P U S R E W O P e p y t y l n o g n i l o o c f o e...

Page 12: ...operation in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its stand...

Page 13: ...English 12...

Page 14: ...olu turmayacak ekilde bi imlendiriniz Kablolar n zerine kapaklar monte ediniz Eksik kapak montaj kutuplar n a r s nmas elektrik arpmas veya yang na neden olabilir So utucu montaj i i s ras nda s z nt...

Page 15: ...larda g r nt ve ses bozulmalar n nlemek i indir Radyo dalgalar n n durumuna ba l olarak 3 metreden uzakta olduklar nda da g r lt duyulabilir 8 K y b lgelerinde veya s lfat gaz i eren tuzlu atmosfer ol...

Page 16: ...PI 4I6 7 G 87 85 F2 O B 1B O 1 2 F2 O B 1B VK2 B21 2 O 1 8 RV FHF E B B21 B2 D I B 1 21B VB B 1 2 F CF 1F B D FO B21BV I S VF F F2 B CKH B B BCB 1FE 1 I PJH K BCB B1B K K1 KVK B BH 1B B2 B 1B B 2J F E...

Page 17: ...lay haz rlay n Temel c vatalar n uzunluklar temel y zeyinden 20mm olana kadar vidalaman z en iyisidir D nite Montaj 1 D nitenin Monte Edilmesi 1 D niteyi monte ederken Yer Se iminde nlemler ve D nite...

Page 18: ...i y zeylerine uygulay n R410A i in so utma ya kullan n 3 Geni letme somunlar n n zarar g rmesini ve gaz ka a olu umunu engellemek i in geni letme somunlar n s k t r rken tork anahtarlar n kullan n Her...

Page 19: ...r ld koruma taraf n gaz kapatma vana servis portuna ba lay n 2 Manometre manifoldunun d k bas n vanas n Lo t m yle a n ve y ksek bas n vanas n Hi tamamen kapat n Y ksek bas n l vanada daha sonra i le...

Page 20: ...se imi Ticari bak r boru ve fitingler kullan rken a a dakilere dikkat edin 1 zolasyon malzemesi Polietilen k p k Is iletkenlik oran 0 041 ila 0 052W mK 0 035 ila 0 045kcal mh C So utma gaz borusunun...

Page 21: ...k olarak durur Test al t rmas n durdurmak i in i nite al t rma durdurma d mesine bas n Cihaz n uzaktan kumandas n kullanarak 1 al t rma durdurma d mesine bas n al t rma ba lar 2 S cakl k d mesine bas...

Page 22: ...n 20mm 2 nite ve d niteler aras nda ba lant kablolar n terminal numaralar birbirine uyacak ekilde ba lay n Terminal vidalar n iyice s k n Vidalar s kmak i in d z ba l bir tor navida kullan lmas tavsi...

Page 23: ...Beyaz GRN Ye il YLW Sar Notlar G gereksinimleri i in nite etiketine bak n TO INDOOR UNIT niteye POWER SUPPLY G beslemesi IN CASE OF COOLING ONLY TYPE yaln zca so utma tipi kullan l yorsa OUTDOOR D CON...

Page 24: ...areketi gibi t m i lev ve par alar n d zg n al t ndan emin olmak i in test i letimini Kullan c K lavuzuna uygun olarak ger ekle tirin Klima cihaz bekleme modunda iken az miktarda enerjiye ihtiya duyar...

Page 25: ...12 T rk e...

Page 26: ...1 R410A O p p p p p p p p p p p p p p p...

Page 27: ...2 1 2 3 4 5 6 7 3 3 8 9 1 2 3 4 B 1 99 2 1 51 4 99 2 1 692 5 4 5 5 1 7 9 97 9 8 97 139 1 696 2 134...

Page 28: ...GI KUK 4N611 20g 1 121 151 I3 K D 1IH D2 I I3 K D 1IH FO I T 2 C2M O 2IDIEC N CG C1O D2H GO 2IDIEC I D2 G 2CC 8 1K R 9 3 2 C D GIF2C C CG C1 E 3 2 C FI D 2 C2M E 2IDIEC IK CFO 2 C C DI E CG FI H CFI...

Page 29: ...0 20 1 1 2 2 1 2 30 3 7 1 4 2 11 01 2 11 01 4 8 1 1 14 3 7 1 49 6 7 1 16 2 11 01 2 11 01 2 11 01 4 91 6 2 11 01 4 91 6 2 11 01 2 11 01 5 2 11 01 20 7 27 8 8 7 A5 9 8 25 21 A A 2 A A 0 A 23 6 A 2 7 A 7...

Page 30: ...L 7 2 1 F C2 BF 2 F DF DP 8 E DA BE D AE80 E CE E AE E E 0 4F G8 E 6F3 G8 E 45K H4 K 9 63K5H6 K5 9 T444H37 0A R T633H6 2 0A R DP 8 E DA BE D 0 EU0E 0 E E E E AE E E 0 4F G8 E 6F3 G8 E 56K1H5 K3 9 56K1...

Page 31: ...6 5 1 R410A 2 3 R410A 4 R410A 4 1 2 2 4 1 2 Lo Hi 3 0 1 76 1 4 Lo 2 5 6 90 5 7 8 15 10 8 278 21 8 3 8 2 8 9 8 2 9 8 2 23 9 8 2 6 1 8 2 1 0 1 529 1 8 4 2 0 1 3 1 0 3 7 8 4 2 8 8...

Page 32: ...10 30 0 8 C1220T O 0B 2A9 959 B 4 2 9 2 9 2 B 2 5B 9 22 9 98 A9 9 A2 B 9 69 29 959 B B 7 A 2 2 99A 2 B A B A 9 9 B82 B 29 959 B B 9 91 A 1 25 5B 9 2 62 A 9 A 9 9A 0B 9 29 2 959 B 3 5B 9 2 9 9 9 2A9 9...

Page 33: ...8 1 2 3 4 15 1 2 3 4 30 1 2 KF 1J7 BF CJ7 54F F1 JP5F 54F F1F C 7 54GR KF5 J 9 KF 1J7 9 5 1J7 54F F1...

Page 34: ...L K D J LC 71 5K E CL 1 E7 K E2 1 L L G 25 H 1 LK 25 H 1 LC 71 5K E CL 1 E7 K E2 1 L 3 09G5K E C C7L K D J 1 2 3 1 2 3 I IDL D AI I7N R FO 1 1 H D DI5 5 1 3 I7 O J 7 OQ7 I 1 B 75I I1IK 5 331IH 7 5 A7I...

Page 35: ...U RED BRN WHT GRN YLW TO INDOOR UNIT POWER SUPPLY IN CASE OF COOLING ONLY TYPE OUTDOOR CONDENSER DISCHARGE C5 C6 C119 DB1 DB2 DB3 FU1 FU2 FU3 IPM1 IPM2 L L1 L1R M1C M1F MR4 MR30 MRM10 MRM20 N Q1L PCB1...

Page 36: ...11 1 1 1 1 2 1 2 26 C 28 C 20 C 24 C 3 1 2 26 C 28 C 3 1 3 2 RC...

Page 37: ...emmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw...

Page 38: ...ikineurope com 3P341265 4E 2014 01 Copyright 2014 Daikin DAIKIN ISITMA VE SO UTMA S STEMLER SAN T C A H rriyet Mah D 100 Kuzey Yanyol No 49 1 2 Kartal ISTANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671...

Reviews: