Safety Precautions

Read these Safety Precautions carefully to ensure correct installation.

This manual classifies the precautions into WARNING and CAUTION.

Be sure to follow all the precautions below: they are all important for ensuring safety.

WARNING...............Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury.

CAUTION...............Failure to follow any of CAUTION may result in grave consequences in some cases.

The following safety symbols are used throughout this manual:

After completing installation, test the unit to check for installation errors. Give the user adequate instructions concerning the use

and cleaning of the unit according to the Operation Manual.

Be sure to observe this instruction.

Be sure to establish an earth connection.

Never attempt.

WARNING

Installation should be left to the dealer or another professional.

Improper installation may cause water leakage, electrical shock, or fire.

Install the air conditioner according to the instructions given in this manual.

Incomplete installation may cause water leakage, electrical shock, or fire.

Be sure to use the supplied or specified installation parts.

Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire.

Install the air conditioner on a solid base that can support the weight of the unit.

An inadequate base or incomplete installation may cause injury in the event the unit falls off the base.

Electrical work should be carried out in accordance with the installation manual and the national electrical wiring

rules or code of practice.

Insufficient capacity or incomplete electrical work may cause electrical shock or fire.

Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance.

For wiring, use a cable length enough to cover the entire distance with no connection.

Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit.

(Failure to do so may cause abnormal heat, electric shock or fire.)

Use the specified types of wires for electrical connections between the indoor and outdoor units.

Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause termi-

nal overheating or fire.

After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force

on the electrical covers or panels.

Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.

If any refrigerant has leaked out during the installation work, ventilate the room.

(The refrigerant produces a toxic gas if exposed to flames.)

After all installation is complete, check to make sure that no refrigerant is leaking out.

(The refrigerant produces a toxic gas if exposed to flames.)

When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the

specified refrigerant (R410A), such as air.

(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)

During pump-down, stop the compressor before removing the refrigerant piping.

If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed,

causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

During installation, attach the refrigerant piping securely before running the compressor.

If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing

abnormal pressure in the freezer cycle which will lead to breakage and even injury.

Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth.

Incomplete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the

air conditioner.

Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in electric shocks, or fire.

CAUTION

Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.

If the gas leaks and builds up around the unit, it may catch fire.

Establish drain piping according to the instructions of this manual.

Inadequate piping may cause flooding.

Tighten the flare nut according to the specified method such as with a torque wrench.

If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage.

Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small

animals.

Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around

the unit clean.

Summary of Contents for RXB25B5V1

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RXB25B5V1 RXB35B5V1 English Installation manual R410A Split series Montaj K lavuzu T rk e R410A Split serisi...

Page 2: ...shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or...

Page 3: ...heard even if they are more than 3 meter away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air cond...

Page 4: ...onal refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shorte...

Page 5: ...oundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Draw ings 2 I...

Page 6: ...torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them f...

Page 7: ...hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequen...

Page 8: ...owing 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 035 to 0 045kcal mh C Refrigerant gas pipe s surface temperature reaches 110 C max Choose heat insulation material...

Page 9: ...force a test run to stop press the indoor unit operation stop button Using the main unit s remote controller 1 Press the operation stop button Operation will start 2 Press the temperature button and t...

Page 10: ...that the termi nal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal board Observe the notes...

Page 11: ...G N R G Notes Refer to the nameplate of the unit for power requirements t i n u r o o d n i o T T I N U R O O D N I O T y l p p u s r e w o P Y L P P U S R E W O P e p y t y l n o g n i l o o c f o e...

Page 12: ...operation in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its stand...

Page 13: ...English 12...

Page 14: ...olu turmayacak ekilde bi imlendiriniz Kablolar n zerine kapaklar monte ediniz Eksik kapak montaj kutuplar n a r s nmas elektrik arpmas veya yang na neden olabilir So utucu montaj i i s ras nda s z nt...

Page 15: ...larda g r nt ve ses bozulmalar n nlemek i indir Radyo dalgalar n n durumuna ba l olarak 3 metreden uzakta olduklar nda da g r lt duyulabilir 8 K y b lgelerinde veya s lfat gaz i eren tuzlu atmosfer ol...

Page 16: ...PI 4I6 7 G 87 85 F2 O B 1B O 1 2 F2 O B 1B VK2 B21 2 O 1 8 RV FHF E B B21 B2 D I B 1 21B VB B 1 2 F CF 1F B D FO B21BV I S VF F F2 B CKH B B BCB 1FE 1 I PJH K BCB B1B K K1 KVK B BH 1B B2 B 1B B 2J F E...

Page 17: ...lay haz rlay n Temel c vatalar n uzunluklar temel y zeyinden 20mm olana kadar vidalaman z en iyisidir D nite Montaj 1 D nitenin Monte Edilmesi 1 D niteyi monte ederken Yer Se iminde nlemler ve D nite...

Page 18: ...i y zeylerine uygulay n R410A i in so utma ya kullan n 3 Geni letme somunlar n n zarar g rmesini ve gaz ka a olu umunu engellemek i in geni letme somunlar n s k t r rken tork anahtarlar n kullan n Her...

Page 19: ...r ld koruma taraf n gaz kapatma vana servis portuna ba lay n 2 Manometre manifoldunun d k bas n vanas n Lo t m yle a n ve y ksek bas n vanas n Hi tamamen kapat n Y ksek bas n l vanada daha sonra i le...

Page 20: ...se imi Ticari bak r boru ve fitingler kullan rken a a dakilere dikkat edin 1 zolasyon malzemesi Polietilen k p k Is iletkenlik oran 0 041 ila 0 052W mK 0 035 ila 0 045kcal mh C So utma gaz borusunun...

Page 21: ...k olarak durur Test al t rmas n durdurmak i in i nite al t rma durdurma d mesine bas n Cihaz n uzaktan kumandas n kullanarak 1 al t rma durdurma d mesine bas n al t rma ba lar 2 S cakl k d mesine bas...

Page 22: ...n 20mm 2 nite ve d niteler aras nda ba lant kablolar n terminal numaralar birbirine uyacak ekilde ba lay n Terminal vidalar n iyice s k n Vidalar s kmak i in d z ba l bir tor navida kullan lmas tavsi...

Page 23: ...Beyaz GRN Ye il YLW Sar Notlar G gereksinimleri i in nite etiketine bak n TO INDOOR UNIT niteye POWER SUPPLY G beslemesi IN CASE OF COOLING ONLY TYPE yaln zca so utma tipi kullan l yorsa OUTDOOR D CON...

Page 24: ...areketi gibi t m i lev ve par alar n d zg n al t ndan emin olmak i in test i letimini Kullan c K lavuzuna uygun olarak ger ekle tirin Klima cihaz bekleme modunda iken az miktarda enerjiye ihtiya duyar...

Page 25: ...12 T rk e...

Page 26: ...1 R410A O p p p p p p p p p p p p p p p...

Page 27: ...2 1 2 3 4 5 6 7 3 3 8 9 1 2 3 4 B 1 99 2 1 51 4 99 2 1 692 5 4 5 5 1 7 9 97 9 8 97 139 1 696 2 134...

Page 28: ...GI KUK 4N611 20g 1 121 151 I3 K D 1IH D2 I I3 K D 1IH FO I T 2 C2M O 2IDIEC N CG C1O D2H GO 2IDIEC I D2 G 2CC 8 1K R 9 3 2 C D GIF2C C CG C1 E 3 2 C FI D 2 C2M E 2IDIEC IK CFO 2 C C DI E CG FI H CFI...

Page 29: ...0 20 1 1 2 2 1 2 30 3 7 1 4 2 11 01 2 11 01 4 8 1 1 14 3 7 1 49 6 7 1 16 2 11 01 2 11 01 2 11 01 4 91 6 2 11 01 4 91 6 2 11 01 2 11 01 5 2 11 01 20 7 27 8 8 7 A5 9 8 25 21 A A 2 A A 0 A 23 6 A 2 7 A 7...

Page 30: ...L 7 2 1 F C2 BF 2 F DF DP 8 E DA BE D AE80 E CE E AE E E 0 4F G8 E 6F3 G8 E 45K H4 K 9 63K5H6 K5 9 T444H37 0A R T633H6 2 0A R DP 8 E DA BE D 0 EU0E 0 E E E E AE E E 0 4F G8 E 6F3 G8 E 56K1H5 K3 9 56K1...

Page 31: ...6 5 1 R410A 2 3 R410A 4 R410A 4 1 2 2 4 1 2 Lo Hi 3 0 1 76 1 4 Lo 2 5 6 90 5 7 8 15 10 8 278 21 8 3 8 2 8 9 8 2 9 8 2 23 9 8 2 6 1 8 2 1 0 1 529 1 8 4 2 0 1 3 1 0 3 7 8 4 2 8 8...

Page 32: ...10 30 0 8 C1220T O 0B 2A9 959 B 4 2 9 2 9 2 B 2 5B 9 22 9 98 A9 9 A2 B 9 69 29 959 B B 7 A 2 2 99A 2 B A B A 9 9 B82 B 29 959 B B 9 91 A 1 25 5B 9 2 62 A 9 A 9 9A 0B 9 29 2 959 B 3 5B 9 2 9 9 9 2A9 9...

Page 33: ...8 1 2 3 4 15 1 2 3 4 30 1 2 KF 1J7 BF CJ7 54F F1 JP5F 54F F1F C 7 54GR KF5 J 9 KF 1J7 9 5 1J7 54F F1...

Page 34: ...L K D J LC 71 5K E CL 1 E7 K E2 1 L L G 25 H 1 LK 25 H 1 LC 71 5K E CL 1 E7 K E2 1 L 3 09G5K E C C7L K D J 1 2 3 1 2 3 I IDL D AI I7N R FO 1 1 H D DI5 5 1 3 I7 O J 7 OQ7 I 1 B 75I I1IK 5 331IH 7 5 A7I...

Page 35: ...U RED BRN WHT GRN YLW TO INDOOR UNIT POWER SUPPLY IN CASE OF COOLING ONLY TYPE OUTDOOR CONDENSER DISCHARGE C5 C6 C119 DB1 DB2 DB3 FU1 FU2 FU3 IPM1 IPM2 L L1 L1R M1C M1F MR4 MR30 MRM10 MRM20 N Q1L PCB1...

Page 36: ...11 1 1 1 1 2 1 2 26 C 28 C 20 C 24 C 3 1 2 26 C 28 C 3 1 3 2 RC...

Page 37: ...emmelserne i 11 enligt villkoren i 12 gitt i henhold til bestemmelsene i 13 noudattaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw...

Page 38: ...ikineurope com 3P341265 4E 2014 01 Copyright 2014 Daikin DAIKIN ISITMA VE SO UTMA S STEMLER SAN T C A H rriyet Mah D 100 Kuzey Yanyol No 49 1 2 Kartal ISTANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671...

Reviews: