2 Specific installer safety instructions

Installation manual

5

RXA-A8
R32 Split system air conditioners
3P748894-1A – 2023.09

2

Specific installer safety
instructions

Always observe the following safety instructions and regulations.

Unit installation (see 

"4 Unit installation"

 [

4

 7])

WARNING

Installation  shall  be  done  by  an  installer,  the  choice  of
materials  and  installation  shall  comply  with  the  applicable
legislation. In Europe, EN378 is the applicable standard.

Installation site (see 

"4.1 Preparing the installation site"

 [

4

 7])

CAUTION

▪ Check  if  the  installation  location  can  support  the  unit's

weight. Poor installation is hazardous. It can also cause
vibrations or unusual operating noise.

▪ Provide sufficient service space.

▪ Do  NOT  install  the  unit  so  that  it  is  in  contact  with  a

ceiling or a wall, as this may cause vibrations.

WARNING

The appliance shall be stored so as to prevent mechanical
damage and in a well-ventilated room without continuously
operating  ignition  sources  (e.g.  open  flames,  an  operating
gas  appliance,  or  an  operating  electric  heater).  The  room
size shall be as specified in the General safety precaution.

Piping installation (see 

"5 Piping installation"

 [

4

 8])

CAUTION

Piping  and  joints  of  a  split  system  shall  be  made  with
permanent  joints  when  inside  an  occupied  space  except
joints directly connecting the piping to the indoor units.

CAUTION

▪ No  brazing  or  welding  on  site  for  units  with  R32

refrigerant charge during shipment.

▪ During installation of the refrigeration system, joining of

parts with at least one part charged shall be performed
taking  into  account  the  following  requirements:  inside
occupied  spaces  non-permanent  joints  are  NOT
allowed  for  R32  refrigerant  except  for  site  made  joints
directly connecting the indoor unit to piping. Site made
joints directly connecting piping to indoor units shall be
of non-permanent type.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

CAUTION

Do  NOT  open  the  valves  before  flaring  is  complete.  This
would cause refrigerant gas leakage.

DANGER: RISK OF EXPLOSION

Do NOT open the stop valves before the vacuum drying is
finished.

Charging refrigerant (see 

"6 Charging refrigerant"

 [

4

 9])

WARNING

▪ The  refrigerant  inside  the  unit  is  mildly  flammable,  but

normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater,  or  a  cooker,  this  may  result  in  fire,  or  the
formation of a harmful gas.

▪ Turn  OFF  any  combustible  heating  devices,  ventilate

the room, and contact the dealer where you purchased
the unit.

▪ Do  NOT  use  the  unit  until  a  service  person  confirms

that the part from which the refrigerant leaked has been
repaired.

WARNING

▪ Only  use  R32  as  refrigerant.  Other  substances  may

cause explosions and accidents.

▪ R32  contains  fluorinated  greenhouse  gases.  Its  global

warming  potential  (GWP)  value  is  675.  Do  NOT  vent
these gases into the atmosphere.

▪ When  charging  refrigerant,  ALWAYS  use  protective

gloves and safety glasses.

WARNING

NEVER  directly  touch  any  accidental  leaking  refrigerant.
This could result in severe wounds caused by frostbite.

Electrical installation (see 

"7 Electrical installation"

 [

4

 11])

WARNING

The  appliance  MUST  be  installed  in  accordance  with
national wiring regulations.

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  national  wiring
regulation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shocks.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  extension  cords,  or

connections  from  a  star  system.  They  can  cause
overheating, electrical shocks or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

Summary of Contents for RXA20A5V1B8

Page 1: ...Installation manual R32 Split system air conditioners English Installation manual R32 Split system air conditioners RXA20A5V1B8 RXA25A5V1B8 RXA35A5V1B8...

Page 2: ...s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v rob...

Page 3: ...tructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 f...

Page 4: ...diagnosis using LED on outdoor unit PCB 13 13 Disposal 14 14 Technical data 14 14 1 Wiring diagram 14 14 1 1 Unified wiring diagram legend 14 1 About the documentation 1 1 About this document WARNING...

Page 5: ...ew flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring i...

Page 6: ...ng a test operation is dangerous CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet Do NOT remove the fan guard When the fan is rotating at high speed it will cause injur...

Page 7: ...ise will cause no trouble Note If the sound is measured under actual installation conditions the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data bo...

Page 8: ...gerant Use phosphoric acid deoxidised seamless copper for refrigerant piping Piping material phosphoric acid deoxidised seamless copper Flare connections Only use annealed material Piping diameter Liq...

Page 9: ...g 5 3 1 To check for leaks NOTICE Do NOT exceed the unit s maximum working pressure see PS High on the unit name plate 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa...

Page 10: ...igerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When cha...

Page 11: ...thermistors are powered by the power supply Do NOT touch them with bare hands 7 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are...

Page 12: ...indoor unit fan to the highest speed Do NOT use this setting in residences or offices with people 10 Commissioning NOTICE General commissioning checklist Next to the commissioning instructions in thi...

Page 13: ...lementary to the instructions in this chapter and can be used as a guideline and reporting template during maintenance NOTICE Maintenance MUST be done by an authorised installer or service agent We re...

Page 14: ...ort circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual current device Heater Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink...

Page 15: ...e arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge Insulated gate bipolar transistor IGBT po...

Page 16: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P748894 1A 2023 09 Copyright 20...

Reviews: