background image

11 Maintenance and service

Installation manual

13

RXA-A8
R32 Split system air conditioners
3P748894-1A – 2023.09

The  specified  wires  are  used  for  the 

interconnection

cable

.

The 

fuses, circuit breakers,

 or locally installed protection

devices  are  installed  according  to  this  document,  and
have NOT been bypassed.

10.2

Checklist during commissioning

To perform an 

air purge

.

To perform a 

test run

.

10.3

To perform a test run

INFORMATION

If the unit runs into an error during commissioning, see the
service manual for the detailed troubleshooting guidelines.

Prerequisite: 

The power supply MUST be in the specified range.

Prerequisite: 

Test  run  may  be  performed  in  cooling  or  heating

mode.

Prerequisite: 

Refer  to  the  operation  manual  of  the  indoor  unit  for

setting temperature, operation mode….

1

In  cooling  mode,  select  the  lowest  programmable  temperature.
In heating mode, select the highest programmable temperature.
The test run can be disabled if necessary.

2

When  the  test  run  is  finished,  set  the  temperature  to  a  normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.

3

Make sure that all functions and parts are working properly.

4

The  system  stops  operating  3  minutes  after  the  unit  is  turned
OFF.

INFORMATION

▪ Even if the unit is turned OFF, it consumes electricity.

▪ When the power turns back on after a power break, the

previously selected mode will be resumed.

11

Maintenance and service

NOTICE

General  maintenance/inspection  checklist.

  Next  to  the

maintenance  instructions  in  this  chapter,  a  general
maintenance/inspection  checklist  is  also  available  on  the
Daikin Business Portal (authentication required).

The 

general 

maintenance/inspection 

checklist 

is

complementary  to  the  instructions  in  this  chapter  and  can
be  used  as  a  guideline  and  reporting  template  during
maintenance.

NOTICE

Maintenance  MUST  be  done  by  an  authorised  installer  or
service agent.

We  recommend  performing  maintenance  at  least  once  a
year. However, applicable legislation might require shorter
maintenance intervals.

NOTICE

Applicable  legislation  on 

fluorinated  greenhouse  gases

requires  that  the  refrigerant  charge  of  the  unit  is  indicated
both in weight and CO

2

 equivalent.

Formula  to  calculate  the  quantity  in  CO

2

  equivalent

tonnes:

  GWP  value  of  the  refrigerant  ×  total  refrigerant

charge [in kg] / 1000

DANGER: RISK OF ELECTROCUTION

Disconnect  the  power  supply  for  more  than  10  minutes,
and  measure  the  voltage  at  the  terminals  of  main  circuit
capacitors  or  electrical  components  before  servicing.  The
voltage MUST be less than 50 V DC before you can touch
electrical  components.  For  the  location  of  the  terminals,
see the wiring diagram.

DC-

DC+

h

e

d

c

b

f

a

g

a

Multimeter (DC voltage range)

b

S80 – reversing solenoid valve lead wire

c

S70 – fan motor lead wire

d

LED

e

S90 – thermistor lead wire

f

S20 – electronic expansion valve lead wire

g

S40 – thermal overload relay lead wire

h

DB1 – diode bridge

12

Troubleshooting

12.1

Fault diagnosis using LED on
outdoor unit PCB

LED is…

Diagnosis

flashing

Normal.

▪ Check the indoor unit.

ON

▪ Turn  the  power  OFF  and  back  ON,  and

check  the  LED  within  approximately  3
minutes.
If  the  LED  is  ON  again,  the  outdoor  unit
PCB is faulty.

OFF

1

Supply voltage (for power saving).

2

Power supply fault.

3

Turn  the  power  OFF  and  back  ON,  and
check  the  LED  within  approximately  3
minutes.

If the LED is OFF again, the outdoor unit
PCB is faulty.

DANGER: RISK OF ELECTROCUTION

▪ When the unit is NOT operating, the LEDs on the PCB

are turned OFF in order to save power.

▪ Even  when  the  LEDs  are  OFF,  the  terminal  block  and

the PCB may be powered.

Summary of Contents for RXA20A5V1B8

Page 1: ...Installation manual R32 Split system air conditioners English Installation manual R32 Split system air conditioners RXA20A5V1B8 RXA25A5V1B8 RXA35A5V1B8...

Page 2: ...s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v rob...

Page 3: ...tructions as amended S I 2008 1597 Supply of Machinery Safety Regulations 2008 S I 2016 1101 Electrical Equipment Safety Regulations 2016 S I 2016 1091 Electromagnetic Compatibility Regulations 2016 f...

Page 4: ...diagnosis using LED on outdoor unit PCB 13 13 Disposal 14 14 Technical data 14 14 1 Wiring diagram 14 14 1 1 Unified wiring diagram legend 14 1 About the documentation 1 1 About this document WARNING...

Page 5: ...ew flares to prevent refrigerant gas leakage Use flare nuts that are included with the unit Using different flare nuts may cause refrigerant gas leakage CAUTION Do NOT open the valves before flaring i...

Page 6: ...ng a test operation is dangerous CAUTION Do NOT insert fingers rods or other objects into the air inlet or outlet Do NOT remove the fan guard When the fan is rotating at high speed it will cause injur...

Page 7: ...ise will cause no trouble Note If the sound is measured under actual installation conditions the measured value might be higher than the sound pressure level mentioned in Sound spectrum in the data bo...

Page 8: ...gerant Use phosphoric acid deoxidised seamless copper for refrigerant piping Piping material phosphoric acid deoxidised seamless copper Flare connections Only use annealed material Piping diameter Liq...

Page 9: ...g 5 3 1 To check for leaks NOTICE Do NOT exceed the unit s maximum working pressure see PS High on the unit name plate 1 Charge the system with nitrogen gas up to a gauge pressure of at least 200 kPa...

Page 10: ...igerant Other substances may cause explosions and accidents R32 contains fluorinated greenhouse gases Its global warming potential GWP value is 675 Do NOT vent these gases into the atmosphere When cha...

Page 11: ...thermistors are powered by the power supply Do NOT touch them with bare hands 7 1 Specifications of standard wiring components NOTICE We recommend using solid single core wires If stranded wires are...

Page 12: ...indoor unit fan to the highest speed Do NOT use this setting in residences or offices with people 10 Commissioning NOTICE General commissioning checklist Next to the commissioning instructions in thi...

Page 13: ...lementary to the instructions in this chapter and can be used as a guideline and reporting template during maintenance NOTICE Maintenance MUST be done by an authorised installer or service agent We re...

Page 14: ...ort circuit connector Fuse Terminal INDOOR Indoor unit Terminal strip OUTDOOR Outdoor unit Wire clamp Residual current device Heater Symbol Colour Symbol Colour BLK Black ORG Orange BLU Blue PNK Pink...

Page 15: ...e arrester SR WLU Signal receiver SS Selector switch SHEET METAL Terminal strip fixed plate T R Transformer TC TRC Transmitter V R V Varistor V R Diode bridge Insulated gate bipolar transistor IGBT po...

Page 16: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P748894 1A 2023 09 Copyright 20...

Reviews: