Wiring

 WARNING

1) Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical 

shock, or fire.

2) Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

3) Be sure to install an earth leak detector. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to 
prevent malfunctioning of the earth leak detector itself.)

4) Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.

• Do not turn ON the safety breaker until all work is completed.

1) Strip the insulation from the wire (20mm).
2) Connect the connection wires between the 

indoor and outdoor units 

so that the termi-

nal numbers match.

 Tighten the terminal 

screws securely. We recommend a flathead 
screwdriver be used to tighten the screws. 
The screws are packed with the terminal 
board.

Observe the notes mentioned below when wiring to the power supply ter-
minal board.
Precautions to be taken for power supply wiring. 
Use a round crimp-style terminal for connection to the power supply  ter-
minal board. In case it cannot be used due to unavoidable reasons, be 
sure to observe the following instruction.
Place the round crimp-style terminals on the wires up to the covered part 
and secure in place.

1
2
3

1 2 3

L N

Safety 
breaker 
10A

Earth leakage 
circuit breaker

Earth

When wire length exceeds 10m, 
use 2.0mm diameter wires.

H05VV

Firmly fix the wires with 
the terminal screws.

Outdoor unit

Indoor 
unit

Power supply
50Hz 220-240V

Firmly fix the wires with 
the terminal screws.

Use 2.0mm diameter wires.

1

2

3

1

2

3

Use the specified wire type and 
connect it securely.

Firmly secure 
wire retainer so 
wire terminations 
will not receive 
external stress.

Shape wires so 
that the stop 
valve cover fit 
securely.

Power supply
terminal block

Electric Wire

Round crimp-style
terminal

01_EN_3P192882-1C.fm  Page 9  Tuesday, March 6, 2007  4:53 PM

Summary of Contents for RX20E2V1B

Page 1: ...liano Portugues T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleidin...

Page 2: ...RQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin...

Page 3: ...y do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has l...

Page 4: ...ing on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit d...

Page 5: ...t required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shortest pipe length...

Page 6: ...t Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Draw ings 2 If drain work is necessary fol...

Page 7: ...ches Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces o...

Page 8: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 9: ...Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Thickness 0 8mm Thickness 10mm Min Filling a cylinder with an attached siphon Stand the cylinder...

Page 10: ...press the operation stop button CAUTION 1 When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock 2 After closing the liquid stop valve clos...

Page 11: ...e recommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal board Observe the notes mentioned below when wiring to the power supply ter minal board Precaut...

Page 12: ...ems with the work may cause heat and fires 3 Pull the wire and make sure that it does not disconnect Then fix the wire in place with a wire stop Strip wire end to this point Excessive strip length may...

Page 13: ...turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a...

Page 14: ...0704 HT 3P192882 1C M06B162B Two dimensional bar code is a code for manufacturing 00_CV_3P192882 1C fm Page 2 Tuesday March 6 2007 4 41 PM...

Reviews: