background image

Umeda Center Bldg., 4-12, Nakazaki-Nishi 2-chome,

Kita-ku, Osaka, 530-8323 Japan 

3SB63850-2A

RXS20E2V1B,

 RXS25E2V1B,

 RXS35E2V1B,

 RKS20E2V1B,

 RKS25E2V1B,

 RKS35E2V1B,

 

RX20E2V1B,

 RX25E2V1B,

 RX35E2V1B,

 RK20E2V1B,

 RK25E2V1B,

 RK35E2V1B

D

AIKIN INDUSTRIES,

 L

T

D

.

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

,

74736-KRQ/EMC97-4957.

Daikin.TCF

.015

74736-KRQ/EMC97-4957

Daikin.TCF

.015

Noboru Murata

Manager Quality Control Department

Shiga, 1st of Dec. 2006

3SB63850-2A.fm  Page 1  Monday, October 16, 2006  11:11 AM

Summary of Contents for RX20E2V1B

Page 1: ...liano Portugues T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleidin...

Page 2: ...RQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin...

Page 3: ...y do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has l...

Page 4: ...ing on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit d...

Page 5: ...t required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shortest pipe length...

Page 6: ...t Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Draw ings 2 If drain work is necessary fol...

Page 7: ...ches Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas 2 To prevent gas leakage apply refrigeration machine oil on both inner and outer surfaces o...

Page 8: ...valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and...

Page 9: ...Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Thickness 0 8mm Thickness 10mm Min Filling a cylinder with an attached siphon Stand the cylinder...

Page 10: ...press the operation stop button CAUTION 1 When pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock 2 After closing the liquid stop valve clos...

Page 11: ...e recommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal board Observe the notes mentioned below when wiring to the power supply ter minal board Precaut...

Page 12: ...ems with the work may cause heat and fires 3 Pull the wire and make sure that it does not disconnect Then fix the wire in place with a wire stop Strip wire end to this point Excessive strip length may...

Page 13: ...turned off 1 3 Carry out the test operation in accordance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a...

Page 14: ...0704 HT 3P192882 1C M06B162B Two dimensional bar code is a code for manufacturing 00_CV_3P192882 1C fm Page 2 Tuesday March 6 2007 4 41 PM...

Reviews: